The Impact of Cable Routing on Thermal Performance in Data Center Halls: A CFD-Based Study
Original title Veri Merkezi Salonlarında Kablo Yerleşiminin Termal Performansa Etkisi: CFD Tabanlı Bir İnceleme
Akdeniz Mühendislik Dergisi · Emrah Yaylı, Turan Çakıl et al.
In a 528 m² free-cooled data centre in Ankara, moving cabling from under the raised floor to overhead trays lowers room temperature by an average 2.5 °C and cooling energy by about 5.5%.
On this page
Overview
This paper from Türksat and university researchers, published in the Akdeniz Journal of Engineering, examines how accumulated cable bundles disturb cold-air distribution in raised-floor data centres. When cables choke the plenum, less cold air leaves the perforated tiles, IT equipment is cooled poorly and room temperature rises.
The study uses a real hall of 528 m² with 146 cabinets and about 338 kW of IT load. Cooling comes from 3+2 STULZ ASD 1102 AU direct free-cooling units, each rated 110.9 kW, with an under-floor supply temperature of 18 °C. The hall has no cold-air containment and uses 103 grilles of 60 cm x 40 cm with 30% opening.
Two scenarios are modelled in 6Sigma CFD: the existing under-floor cabling and overhead cabling in 20 cm x 20 cm trays. Cable density is held constant and only the route changes. The model is compared with real data from 18 temperature sensors placed 2 m above the floor.
Results show overhead cabling lowers room temperature by an average 2.5 °C (8.33%). The average power of three air conditioning units falls over three-day comparison periods. The study rests on one hall and a short measurement window, and applies to an uncontained raised floor with dense cabling.
Key points
- Hall: 528 m², 146 cabinets, 2 UPS systems, 34 PDUs, about 338 kW IT load.
- Cooling: 3+2 STULZ ASD 1102 AU direct free cooling, 110.9 kW per unit, 18 °C under-floor supply.
- Sensor temperatures were 24.0-25.0 °C with under-floor cabling and 22.0-23.5 °C with overhead cabling.
- Average room temperature falls by 2.5 °C (8.33%).
- Share of cooling air leaving the grilles rises from 92.69% to 93.58%.
- Maximum inlet temperature falls from 44.21 °C to 42.23 °C.
- Average grille airflow is similar in both cases: 0.18 m³/s and 0.1817 m³/s.
- AC unit power: unit 1 8.15 kW to 7.14 kW (-12.39%), unit 2 16.41 kW to 15.6 kW (-4.94%), unit 3 10.66 kW to 10.57 kW (-0.84%).
- Overall cooling energy reduction of about 5.5% is reported.
- The paper notes that roughly 30-50% of data-centre energy goes to cooling.
Using it in design
- In raised-floor halls, route heavy cable bundles outside the plenum in overhead trays and cap cable fill in the design.
- Check the under-floor air path for obstructions from cables and pipes by CFD or measurement.
- For room temperature mapping, place enough sensors (18 in the study) at 2 m above the floor.
- In existing halls without cold aisle containment, remove air-path obstructions first and then consider raising supply temperature.
- When using overhead trays, check airflow in the upper volume and fire detection positions together.
Who should read it
Engineers operating and refurbishing raised-floor data centres, and teams planning hall layout and structured cabling.
Document contents
- Introduction
- Materials and Method
- Results and Discussion
- Conclusion
Publication details
- Authors
- Emrah Yaylı; Turan Çakıl; Mücahit Furkan Yumşak; Mustafa Turan Arslan
- Publisher
- Akdeniz Mühendislik Dergisi
- Year
- 2025
- Document number
- 3(2), 138–149
- Document language
- Turkish
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Tam metin yayıncının veya üniversitenin açık kaynağından okundu. Açık erişim, ticari yeniden dağıtım izni olarak yorumlanmadı; yalnızca bağlantı, metadata ve özgün kısa özet tutulur. Özette 2,5 °C, sonuçta yaklaşık 2 °C ve ayrıca 1 °C ifadeleri bulunur; tek bir doğrulanmış sıcaklık düşüşü gibi kullanılmamalıdır. Tablo kW birimindedir; metindeki enerji sözcüğüne rağmen yıllık kWh tasarrufu olarak aktarılmadı. Yazarlar yaklaşık %5,5 aritmetik ortalama bildirir; bu ifade Tablo 2 değerleriyle tutarlı değildir. Üç yüzdelik değerin ortalaması yaklaşık %6,06, toplam güçteki azalma yaklaşık %5,42 olarak hesaplanır; bunlar editoryal aritmetik kontrollerdir, yeni ölçüm değildir.
Citation
Emrah Yaylı; Turan Çakıl; Mücahit Furkan Yumşak; Mustafa Turan Arslan (2025). Veri Merkezi Salonlarında Kablo Yerleşiminin Termal Performansa Etkisi: CFD Tabanlı Bir İnceleme. Akdeniz Mühendislik Dergisi. 3(2), 138–149. https://dergipark.org.tr/tr/download/article-file/4865163
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.