Research paperFree to read2025

The Impact of Cable Routing on Thermal Performance in Data Center Halls: A CFD-Based Study

Original title Veri Merkezi Salonlarında Kablo Yerleşiminin Termal Performansa Etkisi: CFD Tabanlı Bir İnceleme

Akdeniz Mühendislik Dergisi · Emrah Yaylı, Turan Çakıl et al.

In a 528 m² free-cooled data centre in Ankara, moving cabling from under the raised floor to overhead trays lowers room temperature by an average 2.5 °C and cooling energy by about 5.5%.

On this page

Overview

This paper from Türksat and university researchers, published in the Akdeniz Journal of Engineering, examines how accumulated cable bundles disturb cold-air distribution in raised-floor data centres. When cables choke the plenum, less cold air leaves the perforated tiles, IT equipment is cooled poorly and room temperature rises.

The study uses a real hall of 528 m² with 146 cabinets and about 338 kW of IT load. Cooling comes from 3+2 STULZ ASD 1102 AU direct free-cooling units, each rated 110.9 kW, with an under-floor supply temperature of 18 °C. The hall has no cold-air containment and uses 103 grilles of 60 cm x 40 cm with 30% opening.

Two scenarios are modelled in 6Sigma CFD: the existing under-floor cabling and overhead cabling in 20 cm x 20 cm trays. Cable density is held constant and only the route changes. The model is compared with real data from 18 temperature sensors placed 2 m above the floor.

Results show overhead cabling lowers room temperature by an average 2.5 °C (8.33%). The average power of three air conditioning units falls over three-day comparison periods. The study rests on one hall and a short measurement window, and applies to an uncontained raised floor with dense cabling.

Key points

  1. Hall: 528 m², 146 cabinets, 2 UPS systems, 34 PDUs, about 338 kW IT load.
  2. Cooling: 3+2 STULZ ASD 1102 AU direct free cooling, 110.9 kW per unit, 18 °C under-floor supply.
  3. Sensor temperatures were 24.0-25.0 °C with under-floor cabling and 22.0-23.5 °C with overhead cabling.
  4. Average room temperature falls by 2.5 °C (8.33%).
  5. Share of cooling air leaving the grilles rises from 92.69% to 93.58%.
  6. Maximum inlet temperature falls from 44.21 °C to 42.23 °C.
  7. Average grille airflow is similar in both cases: 0.18 m³/s and 0.1817 m³/s.
  8. AC unit power: unit 1 8.15 kW to 7.14 kW (-12.39%), unit 2 16.41 kW to 15.6 kW (-4.94%), unit 3 10.66 kW to 10.57 kW (-0.84%).
  9. Overall cooling energy reduction of about 5.5% is reported.
  10. The paper notes that roughly 30-50% of data-centre energy goes to cooling.

Using it in design

  • In raised-floor halls, route heavy cable bundles outside the plenum in overhead trays and cap cable fill in the design.
  • Check the under-floor air path for obstructions from cables and pipes by CFD or measurement.
  • For room temperature mapping, place enough sensors (18 in the study) at 2 m above the floor.
  • In existing halls without cold aisle containment, remove air-path obstructions first and then consider raising supply temperature.
  • When using overhead trays, check airflow in the upper volume and fire detection positions together.

Who should read it

Engineers operating and refurbishing raised-floor data centres, and teams planning hall layout and structured cabling.

Document contents

  1. Introduction
  2. Materials and Method
  3. Results and Discussion
  4. Conclusion

Publication details

Authors
Emrah Yaylı; Turan Çakıl; Mücahit Furkan Yumşak; Mustafa Turan Arslan
Publisher
Akdeniz Mühendislik Dergisi
Year
2025
Document number
3(2), 138–149
Document language
Turkish
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Tam metin yayıncının veya üniversitenin açık kaynağından okundu. Açık erişim, ticari yeniden dağıtım izni olarak yorumlanmadı; yalnızca bağlantı, metadata ve özgün kısa özet tutulur. Özette 2,5 °C, sonuçta yaklaşık 2 °C ve ayrıca 1 °C ifadeleri bulunur; tek bir doğrulanmış sıcaklık düşüşü gibi kullanılmamalıdır. Tablo kW birimindedir; metindeki enerji sözcüğüne rağmen yıllık kWh tasarrufu olarak aktarılmadı. Yazarlar yaklaşık %5,5 aritmetik ortalama bildirir; bu ifade Tablo 2 değerleriyle tutarlı değildir. Üç yüzdelik değerin ortalaması yaklaşık %6,06, toplam güçteki azalma yaklaşık %5,42 olarak hesaplanır; bunlar editoryal aritmetik kontrollerdir, yeni ölçüm değildir.

Citation

Emrah Yaylı; Turan Çakıl; Mücahit Furkan Yumşak; Mustafa Turan Arslan (2025). Veri Merkezi Salonlarında Kablo Yerleşiminin Termal Performansa Etkisi: CFD Tabanlı Bir İnceleme. Akdeniz Mühendislik Dergisi. 3(2), 138–149. https://dergipark.org.tr/tr/download/article-file/4865163

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.