TRC-S Series Closed Circuit Cooler (Truwater TRCS catalogue and specification)
Original title TRC-S Series Closed Circuit Cooler
Truwater
Truwater TRC-S is an induced-draft counterflow closed-circuit cooler; the brochure gives drift loss up to 0.005% of circulating flow, SS304 coil, a component material list and a guide specification.
On this page
Overview
Truwater presents the TRC-S series as an induced-draft counterflow closed-circuit cooler for equipment cooling, industrial process cooling, manufacturing and data-centre applications. The closed-circuit coil has no contact with the environment, so the cooling medium stays clean. External circulating water wets the full coil; drift eliminators hold drift loss to 0.005% of circulating flow. The fan is direct-drive, giving minimum transmission loss.
The brochure lists four benefits: lower water consumption all year thanks to the closed coil and drift eliminator, high-efficiency coils with low pump head requirement, simplified control of fan, spray pumps and regulating valve from one point, and a modular build that can ship containerised for faster installation.
The parts list gives materials: fan assembly aluminium alloy, drift eliminator PVC, non-clog spray nozzle ABS, hot water inlet and cold water outlet HDG steel, louver PVC, internal and external water distribution piping PVC, coil and coil frame SS304, coil support HDG steel, spray pump cast iron, casing and cold water basin GI, and motor TEFC or weather-proof type. In the model code the structure material is S (HDG steel) or X (stainless steel) and the drive is D (direct), B (belt and pulley) or G (gear reducer).
The specification section defines an induced-draft, counterflow, closed-circuit, HDG steel mainframe cooler with a service platform and caged ladder to OSHA standards, a performance warranty and construction requirements. Motors are TEFC, 3-phase/50 Hz/380-415 V; the spray system uses PVC header and lateral pipes, the nozzle outlet must be the lowest point in the system and no rotating mechanical sprinkler is allowed. The cold water basin has suction strainer, make-up ball valve, overflow and drain, with equalising pipes between basins on multiple towers. There is no separate model flow or thermal rating table.
Key points
- TRC-S: induced-draft counterflow closed-circuit cooler for equipment and process cooling and data-centre applications.
- Drift loss is up to 0.005% of circulating flow.
- The fan is direct-drive; belt-and-pulley and gear-reducer options exist in the model code.
- Coil and coil frame are SS304; main frame is HDG steel or stainless steel.
- Motors are TEFC or weather-proof, 3-phase/50 Hz/380-415 V.
- The spray nozzle outlet must be the lowest point in the system; rotating mechanical sprinklers are not allowed.
- The basin has strainer, make-up float valve, overflow and drain; multiple towers need equalising pipes.
- Service platform and caged ladder must meet OSHA standards.
Using it in design
- Where a clean cooling medium is needed (GPU, process or chiller condenser loops) evaluate the closed-circuit cooler as an alternative to an open tower; water consumption falls.
- On multi-tower layouts add equalising pipes between basins and a common water level.
- Verify the coil material (SS304) against fluid chemistry; choose galvanised or stainless main frame by corrosion environment.
- With no separate flow-capacity table, request project-specific thermal performance data from the manufacturer for selection.
Who should read it
Data-centre and industrial mechanical designers writing or comparing closed-circuit evaporative cooler specifications.
Document contents
- Introduction
- Parts and materials list
- Model coding
- Closed Circuit Cooler Specification: 1.0 General, 2.0 Capacity, 3.0 Performance Warranty, 4.0 Construction, 5.0 Mechanical Equipment, 6.0 Closed Circuit Coil, 7.0 Water Spraying System, 8.0 Cold Water Basin, 9.0 Access and Safety
Publication details
- Authors
- Truwater
- Publisher
- Truwater
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Truwater TRC-S Series Closed Circuit Cooler. Truwater. https://www.truwater.com.my/wp-content/uploads/2021/08/TRCS-catalogue_web.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
