Investigation of Energy Efficiency and Cost Effect in Industrial Processes: Case Study (free cooling)
Original title Endüstriyel Proseslerde Enerji Verimliliği ve Maliyet Etkisinin İncelenmesi: Örnek Uygulama
Türk Tesisat Mühendisleri Derneği · M. Ziya Söğüt, Hamit Mutlu
A TTMD Journal article (January-March 2020): in a metal processing plant, a free-cooling-assisted solution in place of a classical chiller cuts energy use 65.77 percent with a payback of about 3.22 years.
On this page
Overview
The article is by Assoc. Prof. M. Ziya Söğüt of Piri Reis University and Hamit Mutlu of Mekanik Proje. It stresses that industry accounts for about 30 percent of total energy consumption and that manufacturing process cooling is decisive for efficiency and sustainability. It states that free cooling potential in Turkish climate conditions can reach 70 percent.
The method rests on BIN hour analysis. Process cooling mostly uses fluid in the 7-35 °C range; for processes at 15-35 °C, free cooling of process water is easy. Free cooling capacity is calculated together with annual consumption from the hours at relevant BIN temperatures, enthalpy values and process and coolant specific heats, and the chiller's annual consumption is compared with that of the free cooling system.
The case is a metal processing and production plant. The existing cooling system was surveyed first: a 1,500 kW chiller was running at about 50 percent load, header pump flow was well below the chiller capacity and piping flows showed high energy losses. Pump analyser measurements were taken and pump selections (for example 15 kW for 64 m³/h and 42 mWC, and 4 kW for process-2 at 4 x 10.1 m³/h and 33 mWC) were re-evaluated.
The proposed free-cooling-assisted process gives 65.77 percent energy saving over the existing system with a payback of about 3.22 years. The article also calculates the saving's effect on CO2 emissions. The study is for a production plant, not a data centre, but its method (BIN hour analysis, free cooling share, payback) adapts directly to data centre chilled water circuits.
Key points
- The proposed free-cooling-assisted system saves 65.77 percent of energy; payback is about 3.22 years.
- Free cooling potential in Turkish climate conditions can reach 70 percent.
- Industry accounts for about 30 percent of total energy consumption.
- Process cooling mostly uses fluid at 7-35 °C; free cooling is easy for processes at 15-35 °C.
- The existing 1,500 kW chiller runs at about 50 percent load and pump flows are far below the chiller's.
- Method: BIN hour distribution and an annual consumption comparison based on enthalpy and specific heats.
- Pump example: 15 kW for 64 m³/h and 42 mWC; 4 kW pumps for process-2 at 4 x 10.1 m³/h and 33 mWC.
- The saving's effect on CO2 emission potential is also assessed.
Using it in design
- For data centre circuits designed with high chilled water temperature, calculate the free cooling share from local BIN hour data.
- Compare chiller capacity with actual load; constant part-load operation (for example 50 percent) signals a need to revisit pump and pipe losses.
- Verify pump selections with analyser measurements and the real flow-head point; oversized pumps waste energy.
- Subject the payback to sensitivity analysis on energy price scenarios.
- When adapting the results to a data centre, consider the continuity of IT load and redundancy requirements rather than process behaviour.
Who should read it
Mechanical engineers studying chilled water circuits and free cooling efficiency, and consultants doing energy audits.
Document contents
- Abstract
- Introduction
- Free cooling and the BIN method
- Load and energy analyses in cooling applications
- Case study: existing system assessment
- Pump and saving analysis
- Conclusion
Publication details
- Authors
- M. Ziya Söğüt; Hamit Mutlu
- Publisher
- Türk Tesisat Mühendisleri Derneği
- Year
- 2020
- Document number
- TTMD Dergisi 125, Ocak–Mart 2020, s. 72–81
- Document language
- Turkish
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Yayıncının açık PDF dosyası okundu. Açık erişim yeniden dağıtım izni anlamına gelmez; yalnızca künye, özgün kısa özet ve sayfa atıfları kaydedildi. Kayıt yalnızca Söğüt ve Mutlu imzalı makaleye aittir; derginin diğer içerikleri özetlenmemiştir.
Citation
M. Ziya Söğüt; Hamit Mutlu (2020). Endüstriyel Proseslerde Enerji Verimliliği ve Maliyet Etkisinin İncelenmesi: Örnek Uygulama. Türk Tesisat Mühendisleri Derneği. TTMD Dergisi 125, Ocak–Mart 2020, s. 72–81. https://www.ttmd.org.tr/upload/files/13503ttmd-dergisi-125.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.