Urker US AK Series Axial Cooling Tower Catalogue

Original title Ürker Chiller US AK aksiyal su soğutma kuleleri

Ürker Chiller

Urker's US AK catalogue lists 17 axial-fan cooling tower models from 22,500 to 1,000,000 kcal/h, with epoxy-painted or galvanized steel casings, flame-retardant PVC fill and 380 V fan motors.

On this page

Overview

This four-page Turkish catalogue presents Urker's axial water cooling towers. The capacity range is 22,500-1,000,000 kcal/h. The casing is steel sheet, epoxy painted as standard and hot-dip galvanized on request. The tower consists of flame-retardant plastic fill, an axial fan and a design aimed at minimum water loss.

The first section describes the tower components in 11 items: main casing, lower basin, return water basin (with plastic spray nozzles), plastic PVC fill, plastic eliminator, fan motor (380 V, 50 Hz, direct or belt-and-pulley drive), safety cage, aerodynamic fan cowl, water inlet and outlet connections, air inlet louvre and make-up float valve.

The table in the second section gives, for 17 models, cooling capacity, fan count and diameter, fan speed, motor power, maximum and minimum flow, dimensions, connection size and basin volume. Model US AK.13 has 22,500 kcal/h, a 1 x 460 mm fan, 0.37 kW, maximum flow 4.5 m³/h and a DN50 connection. Model US AK.47175 has 1,000,000 kcal/h, a 1 x 1,500 mm fan, 7.5 kW, maximum flow 159 m³/h and a DN150 connection.

The catalogue covers axial towers only; it notes that radial and evaporative towers are also made and that the manufacturer should be contacted for details. It contains no selection chart or wet-bulb-based capacity correction.

Key points

  1. Capacity range 22,500-1,000,000 kcal/h; 17 models (US AK.13 to US AK.37 and AK.47100 to AK.47175).
  2. Casing is epoxy-painted steel sheet as standard; hot-dip galvanized on request.
  3. Fan motor 380 V, 50 Hz; direct-coupled or belt-and-pulley drive.
  4. US AK.13: 22,500 kcal/h, fan 1 x 460 mm, 0.37 kW, flow 2.7-4.5 m³/h, DN50, 107 l basin.
  5. US AK.29: 225,000 kcal/h, fan 1 x 910 mm, 2.2 kW, flow 23.6-45 m³/h, DN100, 422 l basin.
  6. US AK.37: 600,000 kcal/h, fan 1 x 1,220 mm, 5.5 kW, flow 59.5-119 m³/h, DN150, 1,328 l basin.
  7. US AK.47175: 1,000,000 kcal/h, fan 1 x 1,500 mm, 7.5 kW, flow 39.77-159 m³/h, DN150, 2,258 l basin.
  8. Fill is flame-retardant PVC; eliminator is plastic; make-up float valve is standard.

Using it in design

  • Capacity is given in kcal/h; convert with 1 kW = 860 kcal/h (for example 1,000,000 kcal/h is about 1,163 kW).
  • The catalogue does not state the wet-bulb and water temperature behind the capacity, so obtain capacity confirmation from the manufacturer for the design wet bulb and entering and leaving water temperatures.
  • Check the maximum-to-minimum flow range (for example 59.5-119 m³/h for US AK.37) for variable-flow and part-load operation.
  • Carry basin volume, dimensions and the DN connection size (DN50-DN150) into the piping, floor and structure plan.
  • Settle local conditions such as freeze protection with the manufacturer.

Who should read it

Mechanical designers and procurement engineers selecting cooling towers for data centres and facilities.

Document contents

  1. General information (tower components)
  2. US AK series technical tables (AK.13-AK.29)
  3. US AK series technical tables (AK.31-AK.47175)

Publication details

Authors
Ürker Chiller
Publisher
Ürker Chiller
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Ürker Chiller Ürker Chiller US AK aksiyal su soğutma kuleleri. Ürker Chiller. https://www.urkerchillers.com/tr/img/pdf/Su-Sogutma-Kulesi-Katalogu.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.