Technical guideFree to read2025

Data Centers and Their Energy Consumption: Frequently Asked Questions

Congressional Research Service · Martin C. Offutt, Ling Zhu

US Congressional Research Service report R48646 (26 August 2025): US data centres used about 176 TWh in 2023, 4.4% of US electricity, and could double or triple by 2028 to reach up to 12%.

On this page

Overview

This 11-page question-and-answer report from the Congressional Research Service (CRS) summarises for Congress what data centres are, how much energy they use, how they are cooled and which rules apply. It makes no new measurement; it relies mainly on the Lawrence Berkeley National Laboratory (LBNL) December 2024 US data centre energy report, an EPRI analysis and an IEA estimate. Cryptocurrency mining is not included in the LBNL figures unless stated.

The key figures: annual US data centre energy use in 2023 was about 176 TWh, around 4.4% of annual US electricity consumption, with EPRI estimating 4%. Some projections show consumption could double or triple by 2028 and reach up to 12% of US electricity. EPRI estimates AI uses 10% to 20% of data centre energy. For hyperscale data centres, industry analysts use at least 5,000 servers, 10,000 square feet and power above 100 MW, and 100 MW can supply about 80,000 US households.

On energy use, roughly half or more of electricity demand comes directly from IT equipment, and much of the rest is cooling. Cooling uses centralised systems, moving chilled air through ductwork or chilled water in a piped loop that exchanges heat with the environment, or room-scale computer room air conditioners (CRACs) common in smaller facilities. According to an IEA estimate, a 100 MW US data centre consumes roughly as much water directly as 2,600 households, averaged across cooling strategies. Data-centre-class CPUs have TDP ratings of 150-350 W and advanced GPUs 350-700 W.

On regulation, no legally binding energy standard applies explicitly to private-sector data centre operation. The US Department of Energy has published guidance for federal data centres, Energy Star certifies buildings and infrastructure on a voluntary basis, and DOE has regulated CRAC efficiency since 2012. Data collection is limited: the EIA's 2021 pilot of 50 data centres got only 9 responses, and the Clean Cloud Act (S. 1475) would give authority to collect electricity consumption data from data centres.

Key points

  1. US data centres used about 176 TWh in 2023, about 4.4% of US electricity (LBNL; excluding cryptocurrency); EPRI estimates 4%.
  2. Some projections show consumption could double or triple by 2028 and reach up to 12% of US electricity.
  3. EPRI: AI uses 10-20% of data centre energy.
  4. Roughly half or more of electricity demand comes from IT equipment; much of the rest is cooling.
  5. Hyperscale benchmark used by industry analysts: at least 5,000 servers, 10,000 square feet and power above 100 MW; 100 MW supports about 80,000 US households.
  6. 74% of servers in 2023 were in whole-building (hyperscale and colocation) data centres (LBNL).
  7. IEA estimate: a 100 MW US data centre uses about as much water directly as 2,600 households.
  8. TDP of data-centre-class CPUs is 150-350 W and of advanced GPUs 350-700 W.
  9. No legally binding energy standard applies to private-sector data centre operation; Energy Star is voluntary and DOE has regulated CRAC efficiency since 2012.
  10. The EIA's 2021 pilot received 9 responses from 50 data centres; S. 1475 (Clean Cloud Act) would authorise data collection.

Using it in design

  • For US demand and grid-impact scenarios, use the 176 TWh (4.4%) baseline and the double-to-triple by 2028 projection as a range.
  • Use the IT-to-cooling load split (IT about half or more) as a starting assumption for the facility energy balance and PUE target, then verify against your own design values.
  • In a water-use assessment, separate direct water consumption by cooling technology; the IEA example of 100 MW equal to about 2,600 households is a comparison point.
  • Record in the compliance matrix that no binding federal standard exists, while Energy Star, DOE guidance and state-level rules may apply.
  • Build energy metering infrastructure to be reporting-ready in case of new data collection and reporting rules (such as S. 1475).

Who should read it

Policy specialists, investors and design teams new to US data centre energy demand, cooling and the regulatory framework.

Document contents

  1. Introduction
  2. What is a data center?
  3. What do data centers look like?
  4. How have data centers been defined in federal law and guidance?
  5. What are the energy requirements of data centers?
  6. Why are data centers energy-intensive? What equipment uses energy?
  7. What contributes to the need for cooling? How are data centers cooled? Additional cooling strategies
  8. Potential concerns about water consumption
  9. Which federal regulations cover data center energy consumption?
  10. Reports on actual energy use of US data centers

Publication details

Authors
Martin C. Offutt; Ling Zhu
Publisher
Congressional Research Service
Year
2025
Document number
R48646
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official Congress-hosted PDF text opened. Link-only metadata policy retained; third-party content rights were not cleared for redistribution.

Citation

Martin C. Offutt; Ling Zhu (2025). Data Centers and Their Energy Consumption: Frequently Asked Questions. Congressional Research Service. R48646. https://www.congress.gov/crs_external_products/R/PDF/R48646/R48646.2.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.