Üstünel Product Catalogue: In-line stainless steel VMS pumps (HCR)
Original title Üstünel Product Catalogue: In-line stainless steel VMS pumps
Üstünel
In the 183-page Üstünel catalogue the HCR in-line stainless steel vertical multistage pumps run from 5HCR to 150HCR, 2-200 m³/h, with single, double and triple pump set dimensions.
On this page
Overview
İzmir-based Üstünel states it was founded in 1978; the bilingual (Turkish and English) catalogue covers polycarbonate, Noryl, cast iron, radial and stainless submersible pumps, water-filled and oil-filled submersible motors, Noryl and in-line stainless steel vertical multistage (booster) pumps, and drainage pumps. The company test laboratory was accredited by TÜRKAK to TS EN ISO/IEC 17025 in 2018 and its R&D centre was registered in 2019.
The in-line stainless steel HCR series is offered for water supply and process water transfer, high-pressure uses, fire-fighting systems and multi-storey buildings, hotels, hospitals and industrial sites where mains pressure is insufficient. Liquid temperature is -20 to +120°C, maximum operating pressure 25 bar, three-phase motor power 2.2-55 kW and single-phase 0.37-2.2 kW. The pump shaft is AISI 304 stainless steel, stages and impellers are stainless steel, lower and upper interconnectors are EN-GJL-250 cast iron and the mechanical seal is SiC/SiC/Viton/SS304.
The series comprises 5, 10, 15, 20, 32, 45, 64, 90, 120 and 150 HCR sizes. The general data table gives flow 2-7 m³/h for 5HCR and 60-200 m³/h for 150HCR, motor power 0.37-4 kW up to 15-55 kW, and flanges DN25 to DN125. The pump code (for example 20 HCR 05/05) shows nominal flow, type, motor power (HP) and stage count.
Model tables give each size's monoblock pump with stage count, suction and outlet ports, length dimensions and weight; for example 5HCR 0,5/02 is 0.37 kW with 2 stages, 5HCR 05/22 is 4 kW with 22 stages, 10HCR 01/02 is 0.75 kW and 10HCR 10/22 is 7.5 kW. A separate table gives dimensions and weights for single, double and triple pump sets (34, 60 and 82 kg for 5HCR 0,5/02). Performance curves are at 50 Hz with ISO 9906:2012 Grade 3B tolerance.
Key points
- HCR series in-line stainless steel vertical multistage pumps: 5, 10, 15, 20, 32, 45, 64, 90, 120 and 150 HCR.
- Flow range is 2-7 m3/h for 5HCR and 60-200 m3/h for 150HCR.
- Motor power is 0.37-4 kW for 5HCR and 15-55 kW for 150HCR; flanges DN25-DN125.
- Liquid temperature -20 to +120°C; maximum operating pressure 25 bar.
- Shaft AISI 304; stages and impellers stainless steel; interconnectors EN-GJL-250; mechanical seal SiC/SiC/Viton/SS304.
- Pump code 20 HCR 05/05: nominal flow, type, motor power (HP), stage count.
- 5HCR 0,5/02: 0.37 kW, 2 stages; 5HCR 05/22: 4 kW, 22 stages.
- 5HCR 0,5/02 single, double and triple set weights are 34, 60 and 82 kg.
- Curves are at 50 Hz with ISO 9906:2012 Grade 3B tolerance.
Using it in design
- In single, double or triple parallel pump arrangements read the flow column by arrangement; carry set weight and size (for example 82 kg for a triple set) into floor and layout planning.
- Select the pump at the intersection of system and pump curves, not at one flow-head point, and allow for the ISO 9906 Grade 3B tolerance.
- For cooling and process water compare liquid temperature (-20 to +120°C) and the 25 bar limit with system pressure.
- Do not read rated motor power as measured power; do energy calculations from total efficiency at the duty point.
- Set the number of parallel pumps (N+1) for redundancy against system flow and give each pump its own isolation valve.
Who should read it
Mechanical designers selecting stainless steel multistage pumps for cooling water, pressure boosting and fire circuits.
Document contents
- About us
- Polycarbonate, Noryl, cast iron, radial and stainless submersible pumps
- Water-filled and oil-filled submersible motors
- Noryl vertical multistage pumps
- In-line stainless steel vertical multistage pumps (HCR): general data, components, 5HCR-150HCR tables
- Drainage pumps
Publication details
- Authors
- Üstünel
- Publisher
- Üstünel
- Year
- Year not stated
- Document language
- Multilingual
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Üstünel Üstünel Product Catalogue: In-line stainless steel VMS pumps. Üstünel. https://www.ustunel.com.tr/wp-content/uploads/2026/01/ustunel-urunler-katalogu.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.