Uzman Soğutma Radial-Fan Cooling Tower Catalogue, URK series
Original title Uzman Soğutma Radyal Fanlı Soğutma Kuleleri Kataloğu
Uzman Soğutma
Uzman Soğutma's URK series is an 11-model, centrifugal-fan counterflow cooling tower for 24-330 m³/h, 7.47-74.0 tower units, drift loss under 0.2 % and selection by K factor.
On this page
Overview
The catalogue presents the URK series of radial-fan towers from Uzman Soğutma Sistemleri of Istanbul. Cooling takes place by counterflow contact of air and water. What sets it apart from an axial tower is that the centrifugal fan can build high static pressure, so the fan outlet can be ducted; the tower can therefore be placed inside a building, a basement or a closed plant room and the humid air is ducted out.
The body is complete galvanized sheet with electrostatic powder coating. The fill is flame-retardant PVC, tolerating up to 50 °C; eliminators are PVP plastic with drift loss below 0.2 %. The fan is belt-and-pulley driven and flexibly connected. A basin electric heater can be added for winter operation.
Selection follows the K factor method: tower capacity or water flow, entering and leaving water temperature and wet-bulb temperature must be known; K is read from separate charts for 20-30 °C wet bulb. Water flow is V = Q / (rho x Cp x deltaT) and tower unit = V / K. In the worked example, 380,000 kcal/h, 38/33 °C water and 28 °C wet bulb give K = 4.5, V = 76 m³/h and 16.9 tower units, so URK 6 (17.5) is selected.
Table 1 gives tower units, fan count, motor power (1.5 to 4 x 7.5 HP), basin volume (0.4 to 4.0 m³) and empty and full weight (510-910 kg to 3,400-7,400 kg). Table 2 gives flow and head at three operating points per model (4 to 8 mWC) and Table 3 gives dimensions and connections. In siting, air intake and discharge must not be obstructed and service clearance left around the fan section.
Key points
- 11 standard models (URK 1 to URK 11); water flow 24-330 m³/h; tower units 7.47-74.0.
- Centrifugal fan, counterflow; can be ducted and placed indoors.
- Drift loss below 0.2 %; flame-retardant PVC fill (up to 50 °C).
- Selection: V = Q / (rho x Cp x deltaT), tower unit = V / K; K is read from 20-30 °C wet-bulb charts.
- Worked example: 380,000 kcal/h, 38/33 °C, 28 °C wet bulb, K = 4.5, 76 m³/h, 16.9 tower units, URK 6 selected.
- Fan motor 1.5 HP (URK 1, 2) to 4 x 7.5 HP (URK 11); basin volume 0.4-4.0 m³.
- Weight (empty / full): URK 1 510 / 910 kg; URK 6 1,050 / 2,144 kg; URK 11 3,400 / 7,400 kg.
- Tower head requirement at the operating points is 4-8 mWC; suction NW100-NW200, discharge NW65.
Using it in design
- Select the tower by the K factor method against design wet bulb and water regime, not by tonnage; take the first model equal to or larger than the calculated tower unit.
- For ducted or basement installations, add the duct pressure loss to the fan selection and confirm fan pressure with the manufacturer.
- For pump selection, use the Table 2 operating-point flow and the 4-8 mWC tower head requirement.
- Add the full weight (7,400 kg for URK 11) to the structural calculation and leave service clearance around the fan section.
- Where winter operation is needed, put the basin heater option into the specification; use local data for wet bulb.
Who should read it
Mechanical designers selecting cooling towers, including for indoor placement.
Document contents
- Product introduction and operating principle
- Tower components
- Tower selection, K factor method
- Technical tables (Table 1 and Table 2)
- Dimensions and connections
- Radial or axial?
Publication details
- Authors
- Uzman Soğutma
- Publisher
- Uzman Soğutma
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Uzman Soğutma Uzman Soğutma Radyal Fanlı Soğutma Kuleleri Kataloğu. Uzman Soğutma. https://uzmansogutma.tr/radyal-kule-katalogu.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.