How to Read a Pump Curve? Q-H Curve and Proper Pump Selection

Original title How to Read a Pump Curve: Q-H Curve and Pump Selection

Vansan

Vansan's October 2026 technical guide explains how to read the flow (Q) and head (H) curve in pump selection together with the operating point, efficiency and power curves.

On this page

Overview

The guide is a technical blog post published by Vansan (9 October 2026). It argues that for centrifugal and submersible pump selection, looking only at maximum flow or maximum head is not enough; the head the pump gives at a specific flow must be determined. The graph of this relationship is the Q-H curve, with flow on the horizontal axis and head on the vertical axis.

The article explains the terms one by one. Q is the amount of liquid pumped per unit time, and choosing more flow than needed also changes pipe velocity and friction losses. H is the energy imparted to the liquid and not just physical lift; static elevation, system friction losses and required discharge conditions are assessed together. The operating point is the intersection of the pump curve and the system requirement curve.

The efficiency curve matters in systems that run for long periods; ignoring years of electricity consumption in favour of initial cost is not appropriate. The power curve guides motor selection: the motor must safely cover the pump's required power without being needlessly oversized.

Common mistakes are assuming maximum flow and maximum head are available together, and selecting from vertical elevation alone without pipe, valve and elbow losses. For a submersible pump, flow is set first, then total head from the well's dynamic water level, piping, elevation difference and pressure needs; where several models meet the same operating point, efficiency, motor power, size and materials decide. The article contains no numerical design values.

Key points

  1. The Q-H curve shows head against flow for a pump.
  2. Maximum flow and maximum head are not achieved together.
  3. The operating point is where the pump curve meets the system curve.
  4. Total head includes static elevation, friction losses and discharge conditions.
  5. The efficiency curve determines long-run energy cost.
  6. The power curve drives motor selection; the motor should be neither undersized nor needlessly large.
  7. If several models meet the same operating point, compare efficiency, motor power, size and materials.
  8. Ignoring system losses leads to missing the expected flow.

Using it in design

  • Calculate operating flow first, then total head including pipe, valve, heat exchanger and filter losses, and mark that point on the curve.
  • Plot the system curve with the pump curve and confirm the operating point sits near the peak efficiency region.
  • Select motor power from the required power curve, with the remaining margin.
  • For losses that grow with time such as filter fouling, check operating points at the upper and lower system curve bounds.

Who should read it

Mechanical designers new to pump selection and technical sales engineers.

Document contents

  1. What is a Q-H curve
  2. What does flow rate Q mean
  3. What does head H mean
  4. What is an operating point
  5. Why is the efficiency curve important
  6. How should the power curve be evaluated
  7. Most common mistakes when reading pump curves
  8. Using a pump curve when selecting a submersible pump
  9. Why reading a pump curve correctly is important

Publication details

Authors
Vansan
Publisher
Vansan
Year
2026
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Vansan (2026). How to Read a Pump Curve: Q-H Curve and Pump Selection. Vansan. https://www.vansan.com.tr/blog-en/how-to-read-a-pump-curve-q-h-curve-and-proper-pump-selection

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.