Vertiv Liebert CW System Design Catalog, 38 to 181 kW (10 to 52 ton), 60 Hz, 2024
Original title Liebert CW System Design Catalog
Vertiv
Vertiv's 2024 Liebert CW catalog covers 38 to 181 kW (10 to 52 ton) chilled water upflow and downflow precision air-conditioning units: model code, capacity, electrical, planning, piping and guide specification data.
On this page
Overview
The document is the 2024 system design catalog (60 Hz) for the Vertiv Liebert CW floor-mounted chilled water precision cooling series. The series has ten nominal capacities: 38, 41, 51, 60, 76, 84, 106, 114, 146 and 181 kW, in upflow (U) and downflow (D) configurations; the 146 and 181 kW models are downflow only. The model number defines unit family, capacity, air distribution, cooling type, fan type (forward curved with standard motor, forward curved with variable speed drive, EC fan, EC fan with THD), voltage (208, 230, 380, 460, 575 V, 3 phase, 60 Hz) and valve type (2-way or 3-way high pressure).
The system data section gives total and sensible capacity, water flow and unit pressure drop tables for several room air conditions (such as 75 °F dry-bulb, 44% RH) at water conditions like 50 °F entering and 62 °F leaving. For example, at 50/62 °F water and 80 °F dry-bulb, 38% RH air on, the EC-fan CW038 reaches 30.8 kW total and the CW181 180 kW. Physical data, electrical power requirements and field connections are separate sections.
The planning section covers location, shipping dimensions and weights, and planning dimensions; about 34 inches (864 mm) of service clearance is advised, with a minimum of 18 inches (457 mm). The piping section lists schematics and connection locations. Appendices cover technical support, an optional seismic application configuration, the Liebert Air Economizer (conditioning with cool outdoor air in mild climates, for iCOM-controlled downflow CW and DS units), submittal drawings and guide specifications. The catalog recommends a monitored fluid detection system and coolant supply and return shut-off valves.
Key points
- Capacity range is 38 to 181 kW (10 to 52 ton), 60 Hz; ten models: 038, 041, 051, 060, 076, 084, 106, 114, 146, 181.
- Air distribution is upflow (U) or downflow (D); models 146 and 181 are downflow only.
- Fan options: forward curved with standard motor, forward curved with variable speed drive, EC fan, EC fan with THD.
- Voltages: 208, 230, 380, 460 and 575 V, 3 phase, 60 Hz; valve: 2-way or 3-way high pressure.
- Net capacity example (EC fan, 50/62 °F water, 80 °F DB, 38% RH): CW038 gives 30.8 kW and CW181 180 kW total; sensible equals total at this condition.
- Water flow example (same condition): CW038 18.8 GPM (1.2 L/s) and CW181 108 GPM (6.8 L/s).
- Service clearance: about 34 inches (864 mm) recommended at left, right and front; minimum 18 inches (457 mm).
- Appendices: seismic application option, Liebert Air Economizer (downflow CW and DS units), submittal drawings and guide specification.
- Vertiv recommends a monitored fluid detection system that closes shut-off valves automatically on leakage.
Using it in design
- Select capacity from the ten model sizes (38 to 181 kW) for the data hall; have net capacity recalculated by the manufacturer for your room condition (for example 24 to 29 °C dry-bulb) and water temperature other than 50/62 °F.
- Choose downflow (raised floor) or upflow (ducted) by layout; the large 146 and 181 kW models are downflow only.
- Match the EC fan and THD EC fan option to harmonic and energy requirements, and the valve type (2-way or 3-way) to the hydraulic design.
- Carry service clearance (34 in recommended, 18 in minimum) and shipping weights into the layout plan.
- Add monitored fluid detection with automatic shut-off valves to the chilled water lines; consider the seismic option in seismic zones and the air economizer in mild climates.
Who should read it
Data center mechanical designers, consultants and installers selecting and placing chilled water precision air conditioners.
Document contents
- 1 Nomenclature and components (model number, component location, blower configurations)
- 2 System data (capacity and performance data, physical data)
- 3 Electrical power requirements
- 4 Planning guidelines (location, shipping dimensions and weights, planning dimensions)
- 5 Piping
- Appendix A: Technical support and contacts
- Appendix B: Optional configuration for seismic application
- Appendix C: Optional Liebert Air Economizer
- Appendix D: Submittal drawings
- Appendix E: Guide specifications
Publication details
- Authors
- Vertiv
- Publisher
- Vertiv
- Year
- 2024
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Vertiv (2024). Liebert CW System Design Catalog. Vertiv. https://www.vertiv.com/globalassets/products/thermal-management/room-cooling/liebert-cw-system-design-manual_00.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
