Vertiv Liebert CWA thermal wall

Original title Liebert CWA Chilled Water Thermal Wall

Vertiv

Vertiv Liebert CWA is a 200-500 kW chilled-water Thermal Wall unit for non-raised-floor halls; models CA40, CA60 and CA80 give 250, 350 and 500 kW net sensible capacity.

On this page

Overview

This February 2023 Vertiv brochure presents the Liebert CWA chilled-water Thermal Wall unit, designed for slab-floor applications installed on the gallery side. It is offered from 200 to 500 kW with 4 to 8 fans, and its structure is specified to IBC 2018. Main components are factory-installed, which lowers on-site installation cost.

The efficiency case rests on internal design: filter surface, panel and piping layout reduce internal air pressure drop compared with a standard AHU, and the latest EC fan generation raises cooling capacity by more than 5% in the same footprint. A pressure-independent control valve keeps flow constant and improves water distribution. Performance is stated to be certified by laboratory tests.

For continuity, the unit can be split into two independent modules in one frame, so if one fails the other keeps cooling. Maximum return air temperature is 45 °C. A cooling override function limits interruption during control failure and reboot. The Liebert iCOM control supports teamwork of up to 32 units, standby rotation, lead-lag and cascade operation.

The technical table gives single-circuit models CA40, CA60 and CA80: net sensible capacity 250, 350 and 500 kW, power input 10.2, 12.1 and 21.7 kW. Airflow ranges of 15,000-47,500, 30,000-110,000 and 45,000-150,000 m³/h are adjustable ranges. Values are at 36 °C return air, 30% RH, 20-32 °C water and 20 Pa external static pressure.

Key points

  1. Capacity 200-500 kW; 4-8 fans; structure to IBC 2018.
  2. CA40/CA60/CA80 net sensible capacity 250/350/500 kW.
  3. Power input 10.2/12.1/21.7 kW; spare capacity 15/20/10%.
  4. Adjustable airflow ranges 15,000-47,500, 30,000-110,000 and 45,000-150,000 m³/h.
  5. Table condition: 36 °C return air, 30% RH, 20-32 °C water, 20 Pa external static pressure.
  6. Maximum return-air operating temperature 45 °C.
  7. Powerful EC fans raise capacity by more than 5% in the same footprint.
  8. Control: iCOM, teamwork of up to 32 units; dual power supply and cooling override options.

Using it in design

  • The tabulated net sensible capacity belongs to one point within an adjustable airflow range; confirm capacity with the manufacturer at the project airflow and return temperature.
  • Treat the two-independent-module option in one frame as one redundancy unit in the N+1 scheme.
  • Specify the pressure-independent control valve for flow balancing in chilled-water distribution.
  • Match the footprint (width 2,230-3,960 mm, height 3,670 mm) for gallery-side placement to the building structure.
  • Evaluate the return-air range up to 45 °C together with the hot-aisle design and water temperatures.

Who should read it

Mechanical designers selecting chilled-water cooling units for large slab-floor, gallery-side data halls.

Document contents

  1. Liebert CWA versions and features
  2. Standardised unit, energy efficiency, cooling continuity, smart control
  3. Customer Experience Center and test labs
  4. Technical data table
  5. Service and global presence

Publication details

Authors
Vertiv
Publisher
Vertiv
Year
2023
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Vertiv (2023). Liebert CWA Chilled Water Thermal Wall. Vertiv. https://www.vertiv.com/492f3d/globalassets/products/thermal-management/room-cooling/vertiv-liebert-cwa-chilled-water-thermal-wall-unit-from-200-to-500kw/vertiv-liebert-cwa-brochure---english---emea_mka4l0ukcwa---rev.-3-02.2023-id-374354.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.