Liebert XDH Installation and User Manual (50 and 60 Hz)
Original title Liebert XDH User Manual, 50/60 Hz
Vertiv
The Vertiv Liebert XDH manual describes a half-rack-width, in-row pumped R-134a cooling module (XDH32: 30 kW nominal, 34 kW maximum) with installation, piping and CANbus details.
On this page
Overview
The Vertiv Liebert XDH manual describes a half-rack-wide cooling module placed within a row of computer cabinets in a hot-aisle and cold-aisle arrangement. The module draws hot air from the rear, passes it over air-to-fluid heat exchangers and discharges it from the front in a diffuse pattern into the cold aisle. The refrigerant is R-134a, supplied by a Liebert XDP pumping unit or a Liebert XDC chiller. It has two refrigeration circuits (upper and lower half), which allows interlaced connection of two XD sources for greater reliability.
The manual follows the installation sequence: room preparation, unpacking and taking the module off the pallet, placement in the row, the tie-down bracket, airflow direction and diffusers, piping, electrical and CANbus network, checklist, startup, maintenance and specifications. The piping chapter covers EU fluorinated greenhouse gas requirements, flexible pipe connection methods, recommended pipe sizes, slope, insulation, leak checking and evacuation.
The piping table gives pumped-refrigerant sizes by distance: the XDP supply line is 1-1/8 inch up to 18.3 m and 1-3/8 inch from 18.3 to 53 m; the return line is 2-1/8 and 2-5/8 inch. Branch supply drops are 1/2 inch up to 3 m, and return drops are 7/8 inch up to 3 m and 1-1/8 inch for 3-7.6 m. Piping must not be oversized because that requires excess refrigerant.
Electrically, the module has dual power inputs so fans keep running if one source fails. Optional smart modules provide remote shutdown, fan failure alarms, condensate detection and switching of one fan per bank on and off to save energy. The total CANbus network length is limited to 45 m without an isolator and 91 m with one, including remote temperature and humidity sensor cable. The document is revision 14 from 2017.
Key points
- XDH32: nominal cooling 30 kW (8.5 tons) at 50 and 60 Hz, maximum 34 kW (9.7 tons); rated at 13°C entering fluid and dew point 10°C or lower.
- XDH20: nominal 21.6 kW (50 Hz) and 22 kW (60 Hz); maximum 25.3 kW; same 13°C fluid condition.
- XDH32 dimensions: height 1981 mm, width 305 mm, depth 1048 mm; module weight 112 kg, shipping weight 150 kg.
- Six fans; nominal airflow 6796 m³/h (60 Hz) and 6541 m³/h (50 Hz); sound power 86 dBA.
- Power consumption is nominal 1200 W (60 Hz) and 1150 W (50/60 Hz version); 220-240 V, 1-phase, 50 Hz (CE).
- Pipe connections: supply 1/2 inch, return 7/8 inch copper (OD).
- For EU CE 50 Hz systems the installer must fit a discharge relief valve rated at most 7.2 bar (105 psi).
- CANbus total network length is 45 m without an isolator and 91 m with one.
Using it in design
- Place the module in the row in a hot-aisle and cold-aisle layout and choose a uni- or bi-directional diffuser to suit airflow direction.
- Size pumped R-134a pipes to the distance limits in the table; avoid oversizing and minimise elbows.
- Consider interlacing two separate XD sources so the upper and lower circuits sit on different sources in the redundancy scheme.
- For CE 50 Hz installations include the 7.2 bar relief valve and the rule that no shutoff valve sits between it and the pump.
- Keep total CANbus cable length including sensors under 45 m, or 91 m with an isolator; connect the dual power inputs to two separate feeds.
Who should read it
Field engineers and mechanical and electrical designers installing pumped-refrigerant in-row cooling.
Document contents
- General safety guidelines
- Component locations and model number nomenclature
- Introduction
- General product information
- Mechanical considerations
- Installing the module
- Piping
- Electrical connections
- CANbus Liebert XDP or XDC interconnection with smart modules
- Installation checklist and system fill for startup
- Operation
- Maintenance
- Specifications
Publication details
- Authors
- Vertiv
- Publisher
- Vertiv
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Vertiv Liebert XDH User Manual, 50/60 Hz. Vertiv. https://vertiv.com/49c969/globalassets/shared/liebert-xdh-50-60hz-user-manual_00.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
