The Advantages of Using Lithium-Ion Batteries in Single-Phase UPS Applications for Edge Data Centers
Vertiv
This 2023 Vertiv paper makes the case for lithium-ion batteries in single-phase UPSs serving branch offices, server rooms, network closets and edge sites.
On this page
Overview
The paper first lists the weaknesses of VRLA: string failure risk, a 3-5 year life, temperature sensitivity and weight. A 2013 Ponemon study attributed 55% of unplanned outages and one third of UPS failures to VRLA battery failure. VRLA needs about 25°C room temperature for a 3-5 year life, each 15°C rise halves useful life, and end of life is defined at 80% capacity.
On the Li-ion side, UPS chemistries are LFP, LMO and NMC (or LMO/NMC blends). Li-ion has an 8-10 year design life and is still at about 93% capacity when VRLA reaches 80%; it is about 60% lighter, up to 70% smaller and operates at 30°C without life loss. Li-ion rack systems recharge to 90% in under 2 hours versus over 4 hours for VRLA, with up to 24 hours for a full VRLA recharge.
The cost comparison is the paper's decision point: Li-ion's initial cost is 1.75-2.25 times VRLA, yet the 10-year TCO for a 1500 VA UPS is $1,000 against $1,700, a 41% saving, with payback within five years. The saving comes from avoiding battery replacements at remote sites. The document focuses on small single-phase UPSs and does not cover large three-phase systems.
Key points
- 2013 Ponemon study: 55% of unplanned outages and one third of UPS failures attributed to VRLA battery failure.
- VRLA needs ~25°C room temperature for a 3-5 year life; each 15°C increase halves useful life; end of life is at 80% capacity.
- UPS Li-ion chemistries are LFP, LMO and NMC (or LMO/NMC blends).
- Li-ion: 8-10 year design life (still ~93% capacity when VRLA reaches 80%), ~60% lighter, up to 70% smaller, operates at 30°C without life loss.
- Li-ion rack systems recharge to 90% in under 2 h versus over 4 h for VRLA (up to 24 h for full recharge).
- Initial Li-ion cost is 1.75-2.25x VRLA.
- 10-year TCO for a 1500 VA UPS is $1,000 vs $1,700 (41% saving), with payback within five years.
Using it in design
- For edge and closet designs, default the single-phase UPS battery to Li-ion where room temperature is uncontrolled, and show replacement cycles in lifecycle cost (VRLA 3-5 y, Li-ion 8-10 y).
- Compare battery design life, recharge time to 90% and maximum ambient temperature before derating.
- Warn when VRLA is placed in spaces above 25°C.
- Include travel and labour cost per replacement for remote sites in TCO.
Who should read it
IT and facilities managers choosing single-phase UPS batteries for many branch and edge sites.
Related standards
- IEC 62040-1
- IEC 62619
- UL 1973
Publication details
- Authors
- Vertiv
- Publisher
- Vertiv
- Year
- 2023
- Document number
- SL-70595
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Vertiv (2023). The Advantages of Using Lithium-Ion Batteries in Single-Phase UPS Applications for Edge Data Centers. Vertiv. SL-70595. https://www.vertiv.com/493b19/globalassets/shared/vertiv_liebert_psi5_lio_advantages-of-using-lithium-ions-batteries-sl-70595.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.