Visiontec FanWall Systems for Data Centers and Critical Environments, 2024

Original title Visiontec FANWALL Systems: VSFW 2024 Version 1.0

Visiontec

Visiontec's 2024 brochure presents chilled-water VSFW fan wall units of 150 to 350 kW (15/22 °C water, 34,405 to 77,305 CFM, 400 V) and DX options with a guide specification.

On this page

Overview

The document is the 8-page 2024 brochure (VSFW, version 1.0) for FanWall air handling units from the Malaysian maker Visiontec, aimed at hyperscale data centers and critical spaces. The unit acts as precision air conditioning, controlling cooling, reheat, humidification and dehumidification by microprocessor and monitoring hot and cold aisle conditions. The panel touch screen has IP65 protection.

Construction: a heliarc-welded steel frame, an epoxy-coated double-skin cabinet and front and rear service access. Coils are seamless copper tube with hydrophilic-coated aluminium fins, and chilled water models have a built-in pressure-independent control valve (PIBCV). Fans are variable-speed EC centrifugal in a draw-through layout, with direct-drive IE4 motors. DX models use scroll compressors, multiple independent refrigerant circuits and an outdoor condenser (950 rpm fans). The electric reheat is three-stage stainless steel; a built-in ATS can be added for Tier 3 and Tier 4 designs.

The technical data table gives models VSFW150CH, 200CH, 250CH, 300CH and 350CH at 151.9, 200.5, 250.0, 300.0 and 350.0 kW total (equal sensible) capacity, 34,405 to 77,305 CFM airflow, 4 or 6 fans, 5.73 to 13.27 kW unit power, 5.2 to 12.0 L/s water flow and 60 kPa pressure drop. Performance is at 15/22 °C water and standard airflow. The brochure also describes TB1 thermal bridging class and condensation-protected casing, airtight doors, and filters (G4, 90% arrestance). The figures are manufacturer claims.

Key points

  1. Chilled water models: VSFW150CH, 200CH, 250CH, 300CH, 350CH; total and sensible capacity 151.9, 200.5, 250.0, 300.0 and 350.0 kW.
  2. Airflow is 34,405, 44,514, 56,057, 66,260 and 77,305 CFM; EC fan count is 4 (150 to 250) and 6 (300 and 350).
  3. Unit power is 5.73, 6.91, 10.43, 10.22 and 13.27 kW; supply 400 V, 3-phase, 50 Hz.
  4. Water flow is 5.2, 6.9, 8.6, 10.3 and 12.0 L/s; water pressure drop 60 kPa; connections DN80 and DN100; weight 920 to 1,860 kg.
  5. Performance is given at 15/22 °C chilled water and standard airflow; other temperatures can be custom designed.
  6. Variable-speed EC fans, IE4 direct-drive motors, redundant fan wall; vertical or horizontal installation.
  7. Built-in PIBCV valve on chilled water units; scroll compressors and independent circuits on DX models.
  8. Optional built-in ATS for Tier 3 and Tier 4 designs; three-stage stainless electric reheat (optional SCR, hot gas or hot water).
  9. Casing thermal bridging class TB1; tropical version adds condensation protection; G4 filter at 90% arrestance (ASHRAE 52-76) or EU4.

Using it in design

  • In large data halls, consider the fan wall as modular capacity in the 150 to 350 kW range; plan an extra unit or fan redundancy for N+1.
  • Match the 15/22 °C water temperature to the facility water loop; ask the manufacturer for custom selection at other temperatures.
  • Check unit size (for example 2489 to 3658 mm wide, 1981 mm deep, 2210 or 2972 mm high) and weight (920 to 1,860 kg) against floor loading and layout.
  • Include the built-in PIBCV and 60 kPa pressure drop in pump selection and ΔT control strategy.
  • In humid climates evaluate TB1 and the tropical version for condensation risk.

Who should read it

Mechanical designers selecting fan wall type precision cooling for hyperscale and large data centers.

Document contents

  1. Cover: FanWall systems for data centers and critical environment
  2. Unit design and construction features
  3. Model identification
  4. Guide specification (general, indoor unit, frame and cabinet, coil, blower, compressor, filters, electric reheat, outdoor unit, monitoring and control)
  5. Energy efficiency and operational reliability solutions
  6. FanWall series technical data (chilled water type)

Publication details

Authors
Visiontec
Publisher
Visiontec
Year
2024
Document number
VSFW / 2024 / VERSION 1.0
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Visiontec (2024). Visiontec FANWALL Systems: VSFW 2024 Version 1.0. Visiontec. VSFW / 2024 / VERSION 1.0. https://pavision.com.my/images/2024/VS_FanWall_V1_Sept2024.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.