Wieland Dry Coolers: High-Efficiency Air Heat Exchangers

Wieland

Wieland's 2026 dry cooler brochure presents flat, V-shape and adiabatic families covering 20 kW to 2500 kW, with EC fan control and coil coating options.

On this page

Overview

The brochure introduces Wieland's dry cooler range for free cooling, process heat rejection and energy recovery. Listed applications are HVAC-R, data centres, industrial cooling and power plants, with the data-centre emphasis on high performance and redundancy.

The range has three families. The flat configuration (FN, FND) covers 20 to 1000 kW with 1 to 14 fans and vertical or horizontal airflow. The V-shape configuration (FLV, GLV) covers 50 to 2000 kW with 1 to 20 fans in a reduced footprint. The adiabatic families (FVD, MVD, FVSM, Dual Stage) cover 50 to 2500 kW with 1 to 11 fans. Only family ranges are given, not individual model data.

The adiabatic system pre-cools air by water evaporation before it reaches the coil. The worked example takes air at 35 °C and 39% RH down to 25 °C and 90% RH. Three methods are offered: a cellulose or synthetic pad, basic nozzle spray and an atomiser system fed by a 10 bar pump group. The system activates only at high ambient temperature, which limits water use and operating cost.

Options include a control panel for EC motors with 0-10 V and RS485/Modbus, an analogue input for BMS integration, threaded or PN16 flanged connections, an air vent valve and a three-way valve that diverts flow between the free cooler and the chiller. Fin coatings span five corrosion levels from bare aluminium to Heresite and Electrofin, and tubes may be copper, AISI 304 or AISI 316L. Final selection is referred to the online Wieland Selector.

Key points

  1. Flat family (FN, FND): 20-1000 kW, 1-14 fans, vertical or horizontal airflow.
  2. V-shape family (FLV, GLV): 50-2000 kW, 1-20 fans, reduced footprint.
  3. Adiabatic families (FVD, MVD, FVSM, Dual Stage): 50-2500 kW, 1-11 fans.
  4. Adiabatic pre-cooling example: air at 35 °C and 39% RH drops to 25 °C and 90% RH.
  5. Three adiabatic methods: pad (PD), basic spray (BS) and 10 bar atomiser spray (OS).
  6. EC fan control: 0-10 V, RS485/Modbus and 4-20 mA for BMS connection.
  7. Flanged connections are PN16; a three-way valve switches between free cooling and chiller.
  8. Fin coatings: bare, hydrophilic, pre-painted, Blygold, Heresite, Electrofin; tubes copper, AISI 304 or AISI 316L.

Using it in design

  • Pre-size the dry cooler with the family range, but make the model selection with the Wieland Selector output and the project conditions.
  • In hot climates, when considering the adiabatic family, specify water supply, water quality and the requirement that spray runs only at high ambient temperature.
  • In coastal or chemical environments choose the coating by exposure class: standard or hydrophilic for commercial HVAC, Blygold for coastal, Heresite or Electrofin for chemical sites.
  • On free-cooling circuits show the three-way valve and air vent in the schematic, and list 0-10 V or Modbus points for the BMS.
  • Define fan speed control as its own requirement for sound level and part-load energy.

Who should read it

Data-centre cooling designers and mechanical engineers specifying free cooling and heat rejection.

Document contents

  1. Applications
  2. Dry coolers range
  3. Adiabatic system
  4. Fan speed control and regulation
  5. Hydraulic connections
  6. Handling and installation
  7. Coil coating solutions
  8. Tube material options
  9. Software and design: Wieland Selector

Publication details

Authors
Wieland
Publisher
Wieland
Year
2026
Document number
WCAT-DRY-001.R01.082026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Wieland (2026). Wieland Dry Coolers: High-Efficiency Air Heat Exchangers. Wieland. WCAT-DRY-001.R01.082026. https://onda-it.com/wp-content/uploads/2023/03/260914-dry-cooler-web.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.