Windmason Cooling Tower Catalogue (WM-CTA, CTB, CTE, CTD series)
Original title Windmason Cooling Towers Catalogue
Windmason
The Windmason catalogue covers modular cross-flow open-loop (WM-CTA), closed-loop (WM-CTB), evaporative condenser (WM-CTE) and dry air-cooling (WM-CTD) towers, with data centres among the applications.
On this page
Overview
The seven-page catalogue presents four tower series from Saudi-based Windmason Arabia. All are modular and can work in series or in a grid for larger capacity. Dimensions are customised to suit standard containers or project conditions. Applications are HVAC, compressors, furnaces, data centres, ground-source heat pumps, generators, transformers, and food and chemical lines.
WM-CTA is an open-loop cross-flow tower: nominal 30 tons, a two-layer casing (powder-coated galvanized steel outside, reinforced fibreglass inside), PVC fill and eliminators with a cellulose layer to reduce scaling, PVC nozzles, backward-curve aluminium centrifugal fans and a washable aluminium air filter. Capacity is based on DBT 45 °C, WBT 20 °C and 600 m altitude.
WM-CTB is a closed-loop tower: nominal 20 tons, with heat-exchange coils in stainless steel or red-copper coated. The table lists nominal capacity from 30 to 366 tons, fan power (for example 1.1 x 2 kW to 4 x 4 kW), spray pump power (1.5-5.5 kW), flow (45-160 T/h) and connection size (DN80-DN150). Nominal tons are based on a 35/29.5 °C (95/85 °F) drop, 25.5 °C (76 °F) WBT and 0.681 m³/h per ton.
WM-CTE is an evaporative condenser aimed at reducing the efficiency loss of air-conditioning, refrigeration and chillers when ambient exceeds 48 °C; nominal 30 tons, with its own condenser coil, and stated to reach 85 % of the wet-bulb temperature. WM-CTD is a dry air-cooling unit with 30 tons nominal at the same DBT 45 °C and WBT 20 °C condition as WM-CTA.
Key points
- Four series: WM-CTA open loop (nominal 30 tons), WM-CTB closed loop (nominal 20 tons), WM-CTE evaporative condenser (30 tons), WM-CTD dry air-cooling (30 tons).
- WM-CTA and WM-CTD capacity condition: DBT 45 °C, WBT 20 °C, altitude 600 m.
- WM-CTB table: 30-366 nominal tons; fan power 1.1 x 2 to 4 x 4 kW; spray pump 1.5-5.5 kW; flow 45-160 T/h.
- Nominal ton condition: 35/29.5 °C (95/85 °F), WBT 25.5 °C (76 °F), 0.681 m³/h per ton.
- Casing: galvanized steel outside, fibreglass inside; PVC fill with cellulose layer; washable aluminium air filter.
- Coils: stainless steel or red-copper coated (CTB).
- The evaporative condenser aims to reduce efficiency loss above 48 °C ambient; it reaches 85 % of wet bulb.
- Modular; extendable in series or grid; dimensions customisable to containers.
Using it in design
- In hot and arid climates (DBT 45 °C, WBT 20 °C, 600 m altitude), check the condition behind each capacity and compare it with the site wet bulb.
- Evaluate a closed-loop tower to isolate the cooling water circuit from open air and reduce fouling; include coil material and spray pump power in operating cost.
- Compare the dry air-cooling option for lower water use with the evaporative condenser for keeping chiller efficiency in hot weather.
- Carry modular N+1 arrangements and container-size shipping into project logistics.
- Add water quality and the filter maintenance plan (washable aluminium filter) to the operating procedure.
Who should read it
Mechanical engineers designing heat rejection for data centres in hot climates.
Document contents
- WM-CTA cross-flow open-loop tower
- WM-CTB cross-flow closed-loop tower and technical table
- WM-CTE evaporative condenser tower
- WM-CTD dry air-cooling unit
Publication details
- Authors
- Windmason
- Publisher
- Windmason
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Windmason Windmason Cooling Towers Catalogue. Windmason. https://windmason.sa/wp-content/uploads/2025/10/Windmason-Cooling-Tower-Catalogue.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.