Thermal Environment Assessment for Energy-Efficient Cooling in Air-Cooled Data Centers: Measurement, CFD, and Predictive Models
Buildings (MDPI AG) · Haijun Tan, Shanran Wang et al.
A systematic review of 77 studies since 2010 covering thermal measurement, CFD and predictive (ML, reduced-order and surrogate) modelling of air-cooled data halls.
CC BY 4.0 — share with attribution
On this page
Overview
The review fills a gap: thermal environment measurement, modelling approaches and their contribution to energy-efficient cooling had not been synthesised systematically. 77 studies published since 2010 were analysed for experimental measurement, CFD simulation and predictive modelling; measurement layouts, CFD software, turbulence models, mesh density, rack representation and validation errors were tabulated, and surrogate inference times were compared with CFD run times.
Findings: of the 39 experimental studies, only about 30.7% included power measurements, which limits evidence linking thermal fixes to energy savings. Temperature was measured in 100% of studies and air velocity in 66.7%, whereas power, airflow rate and pressure were monitored less. Of the 58 CFD studies, Fluent was used in 24 (41.4%) and 6SigmaDC in 12; standard k-epsilon was used in 41 (about 70.7%), with RNG, realizable, SST k-omega and LES less common. Reported CFD validation errors ranged from 0.22% to above 30% relative (mostly below 20%) and from 0.1 to 4 °C absolute; few studies checked velocity.
Mesh densities ranged from about 112 to 41,361 cells/m³, with mesh counts typically 10^5 to 10^7 for domains of tens to about 1000 m³; resolution depends more on the study's objective than on room size. Racks were modelled as porous media in about 36% of studies and as black boxes in about 31%, and porous models better capture rack pressure drop and recirculation. Of 17 predictive-model studies, 70.6% were trained on CFD-generated data; CFD runs took 5 min to 200 h, against 0.097 to 2250 s for surrogate predictions.
Limits: validation is mostly temperature-only, airflow and power are seldom measured, and most surrogates are trained on CFD output rather than measurements; the authors therefore propose a collaborative, hierarchical framework for measurement, CFD and predictive modelling.
Key points
- Of the 39 experimental studies, only about 30.7% included power measurements, which limits evidence linking thermal fixes to energy savings.
- Of the 58 CFD studies, Fluent was used in 24 (41.4%) and 6SigmaDC in 12; standard k-epsilon in 41 (about 70.7%).
- Reported CFD validation errors ranged from 0.22% to above 30% relative (mostly below 20%) and from 0.1 to 4 °C absolute; few studies checked velocity.
- Mesh densities ranged from about 112 to 41,361 cells/m³, with mesh counts typically 10^5-10^7; resolution depends more on the study's objective than on room size.
- Racks were modelled as porous media in about 36% of studies and as black boxes in about 31%; porous models better capture rack pressure drop and recirculation.
- Of 17 predictive-model studies, 70.6% were trained on CFD-generated data; CFD runs took 5 min to 200 h, against 0.097 to 2250 s for surrogate predictions.
- Temperature was measured in 100% of studies and air velocity in 66.7%; power, airflow rate and pressure less often.
Using it in design
- In a design tool, set CFD accuracy expectations from this review's ranges (0.1-4 °C absolute, relative mostly below 20%) and do not limit validation scope to temperature; ask for velocity and pressure too.
- Make the porous-medium rack representation the default; a black-box rack model captures pressure drop and recirculation less well.
- Include power measurement in the measurement plan so thermal improvements can be tied to energy savings (only 30.7% of studies had it).
- If a surrogate was trained on CFD, state that it is only as accurate as the CFD and validate it against real measurements.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Engineers and researchers choosing data-centre thermal measurement, CFD and surrogate modelling approaches and setting accuracy expectations.
Document contents
- 1. Introduction
- 2. Methodology (2.1 Search Strategy, 2.2 Methodology and Objectives)
- 3. Experimental Measurement and Analysis in Data Centers (3.1 Links Between Measurements, Thermal Metrics, and Cooling Energy Use, 3.2 Classification of Data Center Experimental Measurement Data, 3.3 Limitations of Existing Measurement Data, 3.4 Objective-Specific Measurement Parameters and Sensor Layouts)
- 4. CFD Modeling of Thermal Flow Field Within Data Centers (4.1 Classification and Organization of CFD Modeling, 4.2 Boundary Conditions and Model Validation, 4.4 CFD-Supported Thermal Diagnosis and Applications)
- 5. Predictive Models for Data Center Thermal Environments (5.1 Thermal Environment Prediction Models, 5.2 Factors Affecting Model Prediction, 5.3 Analysis of Model Prediction Efficiency)
- 6. Discussion (6.1 Comparison and Assessment of Experimental Measurements, CFD, and Predictive Models, 6.2 Collaborative Framework, 6.3 Challenges and Future Directions)
- 7. Conclusions
Related standards
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
Read the document
air-cooled-dc-thermal-assessment-2026.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Haijun Tan; Shanran Wang; Wenli Liu; Pin Li
- Publisher
- Buildings (MDPI AG)
- Year
- 2026
- Volume
- 16
- Issue
- 19
- Pages
- 3857
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1: Copyright 2026 by the authors; distributed under the Creative Commons Attribution (CC BY) license.
Citation
Haijun Tan; Shanran Wang; Wenli Liu; Pin Li (2026). Thermal Environment Assessment for Energy-Efficient Cooling in Air-Cooled Data Centers: Measurement, CFD, and Predictive Models. Buildings (MDPI AG). 16(19), 3857. https://doi.org/10.3390/buildings16193857
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.