Research paperPDF2024

Effects and optimization of airflow on the thermal environment in a data center

Frontiers in Built Environment (Frontiers Media SA) · Di Jiang

A 6SigmaRoom CFD study of a 153 m² room with 55 cabinets at 6 kW each compares three cooling arrangements: raised-floor perimeter units, in-row units and rear-door heat-pipe coolers, in seven cases.

CC BY 4.0 — share with attribution

On this page

Overview

The study addresses rising data-centre energy consumption by optimising airflow organisation, comparing three cooling systems that are usually considered in isolation. The room is 16.2 m × 9.45 m × 5.125 m (about 153 m²) with 55 cabinets of 600 × 1200 × 2200 mm at 6 kW each, laid out in three rows in a hot/cold aisle pattern. In the raised-floor case, two perimeter units of up to 230 kW and 45,900 m³/h each supply 20 °C air through a 0.64 m raised floor and 0.6 × 0.6 m floor grilles at 50% open area.

The raised-floor and in-row cases were each run open, with cold-aisle containment (CAC) and with hot-aisle containment (HAC), giving seven cases. Air supply efficiency (ASE), air return efficiency, a recirculation index, RTI, SHI and RHI were tabulated. Raised floor without containment gave ASE 65.69%, RTI 77.94% and SHI 0.141; with CAC, ASE 85.57% and SHI 0.0027; with HAC, ASE 90.25%, RTI 90.94% and SHI 0.0024. Without containment, cabinet No. 19 had a mean inlet temperature of 30.1 °C and a maximum of 36.7 °C, and ten cabinets went above the 27 °C specification limit.

In the in-row case, three units of 51.1 kW sensible and 10,200 m³/h each gave ASE 71.29% and SHI 0.145 without containment, and with CAC ASE 92.16%, ARE 99.88% and SHI 0.0015. With 6 kW heat-pipe rear-door coolers, cabinet inlet temperatures averaged about 21.5 °C and varied by no more than 2 °C within a cabinet, and the room stayed at about 22 °C without aisle containment.

Limits: the hall was still being built, so the model was checked against a second CFD code rather than measurements: COMSOL against 6SigmaRoom gave a mean cabinet inlet temperature error below 10%. There is no measurement validation.

Key points

  1. The room is 16.2 m × 9.45 m × 5.125 m (about 153 m²) with 55 cabinets of 600 × 1200 × 2200 mm at 6 kW each in three rows in a hot/cold aisle pattern.
  2. Raised-floor case: two perimeter units of up to 230 kW and 45,900 m³/h each, 20 °C supply, a 0.64 m raised floor and 0.6 × 0.6 m floor grilles at 50% open area.
  3. Raised floor without containment: ASE 65.69%, RTI 77.94%, SHI 0.141. With CAC: ASE 85.57%, SHI 0.0027. With HAC: ASE 90.25%, RTI 90.94%, SHI 0.0024.
  4. Without containment, cabinet No. 19 had a mean inlet temperature of 30.1 °C and a maximum of 36.7 °C, and ten cabinets went above the 27 °C limit.
  5. In-row case: three units of 51.1 kW sensible and 10,200 m³/h each. Without containment ASE was 71.29% and SHI 0.145; with CAC, ASE 92.16%, ARE 99.88% and SHI 0.0015.
  6. With 6 kW heat-pipe rear-door coolers, cabinet inlet temperatures averaged about 21.5 °C and varied by no more than 2 °C within a cabinet; the room stayed at about 22 °C without aisle containment.
  7. Validation was code-to-code only: COMSOL against 6SigmaRoom gave a mean cabinet inlet temperature error below 10%, because the room was still under construction.

Using it in design

  • Make aisle containment the default in raised-floor or in-row cooling: containment raised ASE from 65.69% to 85.57-90.25% and brought SHI close to zero.
  • Show temperature-limit exceedance by cabinet (ten cabinets above 27 °C without containment) and check the worst cabinet (30.1 °C mean, 36.7 °C maximum) separately.
  • Where aisle separation is not possible in high-density cabinets, consider heat-pipe rear-door coolers (for 6 kW cabinets, inlet about 21.5 °C) as an option.
  • Label results that rest only on code-to-code validation in a hall under construction as preliminary design, not firm values.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Cooling designers comparing raised-floor, in-row and rear-door cooling arrangements for new data halls.

Document contents

  1. 1 Introduction
  2. 2 Materials and methods (2.1 Physical model, 2.2 Numerical simulation: mathematical model, boundary conditions and solution settings, grid independence study and model)
  3. 3 Results and discussion (3.1 Option 1: precision air conditioners delivering air from the raised floor: without containment, CAC, HAC, quantitative analysis; 3.2 Option 2: horizontal air supply of inter-column air conditioners: without containment, CAC, HAC, quantitative analysis; 3.3 Option 3: backplane air conditioning and temperature field analysis)
  4. 4 Conclusion

Related standards

  • ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments

Read the document

dc-airflow-thermal-optimization-2024.pdf

PDF · 2.1 MB · English

CC BY 4.0 — share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Di Jiang
Publisher
Frontiers in Built Environment (Frontiers Media SA)
Year
2024
Volume
10
Pages
1362861
Document language
English
Source type
Scientific
Access
Open licence — downloadable
Licence
CC BY 4.0 — share with attribution
Licence evidence
www.frontiersin.org
Original licence note

PDF p.1 copyright notice: open-access article distributed under the terms of the Creative Commons Attribution License (CC BY).

Citation

Di Jiang (2024). Effects and optimization of airflow on the thermal environment in a data center. Frontiers in Built Environment (Frontiers Media SA). 10, 1362861. https://doi.org/10.3389/fbuil.2024.1362861

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.