Emergence and Expansion of Liquid Cooling in Mainstream Data Centers
ASHRAE TC 9.9
This 2021 ASHRAE TC 9.9 white paper urges mainstream facilities to plan for liquid cooling as CPU/GPU power rises and allowable case temperatures fall. It introduces the high-density air class H1 and the renamed W facility-water classes.
On this page
Overview
The paper brings two classification changes. For high-density air-cooled ITE it defines class H1: allowable 15-25 degC and recommended 18-22 degC. Facility-water classes are renamed by their upper supply limit: W17 (was W1), W27 (W2), W32 (W3), W40 (new), W45 (W4) and W+ (W5), all with a 2 degC lower limit. The limits of air cooling are put in numbers.
Server fans can consume up to about 20% of server power, which in a 50 kW rack is at least 5 kW. A 40-50 kW rack can need about 5,000 cfm while the best-in-class perforated tile passes about 1,900 cfm, so beyond a certain density a single raised-floor tile is physically insufficient. The energy section states liquid cooling can bring PUE below 1.1, and a case study using warm water (40-45 degC) with absorption chilling reached a cooling pPUE under 0.07.
The key planning warning is that facilities running W32 today may have to move to W27 as chip power rises, hence the recommendation to design new data centers to accommodate liquid cooling later. It is a classification and planning white paper; it does not give detailed hydraulic design or CDU sizing. For context it also cites A1 allowable maximum 32 degC and A4 maximum 45 degC, and should be read with the 5th edition of ASHRAE Thermal Guidelines and the Liquid Cooling Guidelines.
Key points
- Class H1: allowable 15-25 degC, recommended 18-22 degC.
- Liquid classes: W17 (was W1), W27 (W2), W32 (W3), W40 (new), W45 (W4), W+ (W5); all with 2 degC lower limit.
- Server fans can use up to about 20% of server power; at least 5 kW in a 50 kW rack.
- A 40-50 kW rack can need about 5,000 cfm; best-in-class perforated tile about 1,900 cfm.
- Liquid cooling can bring PUE below 1.1; 40-45 degC water with absorption chilling gave cooling pPUE under 0.07 in a case study.
- Facilities on W32 today may need to move to W27 as chip power rises.
- Context: A1 allowable max 32 degC, A4 max 45 degC.
Using it in design
- Add class H1 and the W17/W27/W32/W40/W45/W+ facility-water classes to the thermal catalog as enumerations.
- Above about 1,900 cfm per rack (about 12-15 kW at 20 degF dT) one tile is not enough; require containment, in-row cooling or liquid.
- Add a 'liquid-ready' option that reserves pipe routes, CDU space and room for W32 or colder water.
- Check facility-water capacity against a move down to W27, not just the first chip generation.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Thermal and mechanical designers preparing an air-cooled facility for liquid cooling or planning a new one.
Related standards
- ASHRAE Thermal Guidelines for Data Processing Environments 5th ed.
- ASHRAE Liquid Cooling Guidelines for Datacom Equipment Centers
- ASHRAE 90.4
Publication details
- Authors
- ASHRAE TC 9.9
- Publisher
- ASHRAE TC 9.9
- Year
- 2021
- Document number
- TC 9.9 White Paper
- Document language
- English
- Source type
- Standard
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
ASHRAE TC 9.9 (2021). Emergence and Expansion of Liquid Cooling in Mainstream Data Centers. ASHRAE TC 9.9. TC 9.9 White Paper. https://www.ashrae.org/File%20Library/Technical%20Resources/Bookstore/Emergence-and-Expansion-of-Liquid-Cooling-in-Mainstream-Data-Centers_WP.pdf
Events on this subject
- ISK-SODEX Istanbul 2027
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
- Data Center World Middle East
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.