Techno-Economic Analysis of Waste Heat Utilization in Data Centers: Application of Absorption Chiller Systems
Energies (MDPI AG) · Leyla Amiri, Edris Madadian et al.
Dalhousie University authors analyse a hybrid scheme in which hot water from liquid-cooled racks drives an absorption chiller, which offsets part of the conventional compression chiller load in the same data centre.
CC BY 4.0 — share with attribution
On this page
Overview
Recovering the decentralised, low-quality waste heat of data centres is hard because of many technological and economic hurdles, and absorption chiller systems are a promising technology for waste-heat recovery at ultra-low temperatures. The authors derive closed-form equations for total cooling, hybrid electricity use and percentage savings in terms of compression and absorption chiller COPs. Hybrid electricity saving is given as 1 - COP_CC/(COP_CC + COP_AC × (1 + COP_CC)), expressed in %.
Calculations assumed at most 15 kW of waste heat per rack, water as coolant at 0.3 to 0.6 l/s, and a design outlet water temperature of 70 °C (below the typical 85 °C because of intermediate heat-exchanger losses). The equations were applied to 4.5 MW and 13.5 MW data centres. The system saves 4,340,000 kWh/year in the 4.5 MW data centre and 13,025,000 kWh/year in the 13.5 MW data centre.
These savings correspond to annual reductions of 3068 and 9208 tons CO2-eq respectively. Simple payback is estimated at 2.76 years for the 4.5 MW data centre and 2.56 years for the 13.5 MW one. On-site absorption cooling is thus a quick-payback reuse path when rack water leaves at around 70 °C.
Limits: the analysis rests on liquid-cooled racks and 70 °C outlet water and does not apply to air-cooled halls; simple payback is a basic economic measure, not detailed financial modelling.
Key points
- Hybrid electricity saving is given in closed form as 1 - COP_CC/(COP_CC + COP_AC × (1 + COP_CC)), in %.
- Calculations assumed at most 15 kW of waste heat per rack, water as coolant at 0.3 to 0.6 l/s, and a design outlet water temperature of 70 °C (below the typical 85 °C because of intermediate heat-exchanger losses).
- The system saves 4,340,000 kWh/year in the 4.5 MW data centre and 13,025,000 kWh/year in the 13.5 MW data centre.
- These savings correspond to annual reductions of 3068 and 9208 tons CO2-eq respectively.
- Simple payback is estimated at 2.76 years for the 4.5 MW data centre and 2.56 years for the 13.5 MW one.
Using it in design
- Evaluate an absorption chiller driven by roughly 70 °C water from liquid-cooled racks to cut compression chiller load; calculate the hybrid saving from the two COPs with the closed-form formula.
- Make waste heat per rack (at most 15 kW), water flow (0.3-0.6 l/s) and outlet water temperature (70 °C, with intermediate heat-exchanger losses) design inputs.
- Report payback as a simple measure (2.56-2.76 years) and verify with a detailed financial model.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Compare the cost of design decisions
Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.
Request a demo
Who should read it
Engineers assessing absorption cooling from waste heat in liquid-cooled data centres.
Document contents
- 1. Introduction
- 2. Methodology (heat recovery and absorption chiller equations)
- 3. Results and Discussion (3.1 Energy Performance: 4.5 MW and 13.5 MW, 3.2 Economic Performance, 3.3 Environmental Performance)
- 4. Conclusions
Related standards
- ASHRAE TC 9.9 thermal guidelines (A1-A4 classes)
Read the document
dc-waste-heat-absorption-chiller-tea-2021.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Leyla Amiri; Edris Madadian; Navid Bahrani; Seyed Ali Ghoreishi-Madiseh
- Publisher
- Energies (MDPI AG)
- Year
- 2021
- Volume
- 14
- Issue
- 9
- Pages
- 2433
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1 states the article is open access under the Creative Commons Attribution (CC BY 4.0) licence; MDPI publishes all articles under CC BY 4.0.
Citation
Leyla Amiri; Edris Madadian; Navid Bahrani; Seyed Ali Ghoreishi-Madiseh (2021). Techno-Economic Analysis of Waste Heat Utilization in Data Centers: Application of Absorption Chiller Systems. Energies (MDPI AG). 14(9), 2433. https://doi.org/10.3390/en14092433
Events on this subject
- Data Centre World Frankfurt
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
- iMasons Climate Accord Summit
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.