Using life cycle assessment to drive innovation for sustainable cool clouds
Nature (Springer Science and Business Media LLC) · Husam Alissa, Teresa Nick et al.
A Nature paper in which Microsoft and WSP ran a cradle-to-grave life cycle assessment comparing an air-cooled data centre with cold-plate, one-phase and two-phase immersion designs.
On this page
Overview
In this paper by Husam Alissa and co-authors, published in Nature in 2025 (vol. 641, issue 8062, pp. 331-338), Microsoft and WSP ran a cradle-to-grave life cycle assessment (LCA) comparing an air-cooled data centre with cold-plate, one-phase immersion and two-phase immersion designs. Impacts (GHG, non-renewable primary energy and blue water) were annualised and normalised per virtual core (Vcore), covering the building, servers, racks or tanks, support equipment, fluids, grid electricity and end-of-life.
Model assumptions: data centre lifetime 15 years; servers (compute, networking, storage) 6 years; racks, tanks and support equipment share the 15-year building lifetime. Data were collected per MW of IT capacity. Against the air-cooled baseline on 100% US-average grid electricity, savings were: GHG 15% (cold plate), 16% (one-phase immersion), 21% (two-phase immersion); energy demand 15%, 15%, 20%; blue water consumption 31%, 45%, 48%. Liquid cooling lowered impacts mainly by cutting use-phase energy and by allowing more servers, overclocking and longer server life; the building and the fluids mattered little.
The use phase is the largest contributor for every cooling technology; server manufacturing (embodied carbon) is second. Switching from 100% grid to 100% renewable electricity cut GHG emissions by 85-90%, energy demand by 6-7% and blue water consumption by 55-85%, so server embodied carbon became more significant. Use-phase energy was modelled as annual energy (MWh/yr) = IT capacity (MW) x load factor x PUE x 8,760 h/yr. As a limit, results depend on Microsoft and WSP's model assumptions and design deltas and cannot be generalised to every facility.
Key points
- Against the air-cooled baseline on 100% US-average grid: GHG savings 15% (cold plate), 16% (one-phase), 21% (two-phase); energy demand 15%, 15%, 20%; blue water 31%, 45%, 48%.
- Assumptions: data centre lifetime 15 years; servers 6 years; racks, tanks and support equipment share the 15-year building lifetime; data collected per MW of IT capacity.
- Design deltas versus air cooling: MW IT capacity +3% (cold plate) / +6% (immersion); PUE 3% / 6% lower; overclocking +20%, +10%, +20%; Vcores +28%, +25%, +36%; compute server count +6% / +13%.
- The use phase is the largest contributor for every technology; server manufacturing (embodied carbon) is second; building size reductions and cooling-fluid embodied impacts are small.
- Switching to 100% renewable electricity cut GHG by 85-90%, energy demand by 6-7% and blue water by 55-85%; server embodied carbon became more significant.
- Use-phase energy = IT capacity (MW) x load factor x PUE x 8,760 h/yr; for immersion fluid coolers adiabatic (wet) operation is assumed above 35 °C outdoor dry-bulb.
- Compute, networking and storage servers make up 70%, 10% and 20% of IT capacity; a network server has 1.3x the embodied impact of a compute server; server end-of-life is 100% recycling after 6 years.
Using it in design
- Add a cooling-technology comparison calculator that computes annual energy as IT MW x load factor x PUE x 8760 and applies the paper's Table 3 deltas (PUE -3%/-6%, IT capacity +3%/+6%) and Table 4 savings ranges as tagged defaults.
- Show results for both grid and renewable electricity.
- Use a 15-year facility lifetime and a 6-year server lifetime as default amortisation periods, and amortise racks or tanks over the building lifetime.
- Warn that under low-carbon electricity server embodied carbon dominates, and ask for per-SKU embodied data.
- Flag two-phase immersion fluids as PFAS under regulatory review and include an adiabatic-cooler switchover temperature (default 35 °C dry-bulb) in water estimates.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Designers choosing cooling technology, sustainability analysts and decision makers reporting carbon and water footprints.
Related standards
- ISO 14040:2006
- ISO 14044:2006
- IPCC AR5 GWP100
Publication details
- Authors
- Husam Alissa; Teresa Nick; Ashish Raniwala; Alberto Arribas Herranz; Kali Frost; Ioannis Manousakis; Kari Lio; Brijesh Warrier; Vaidehi Oruganti; T. J. DiCaprio; Kathryn Oseen-Senda; Bharath Ramakrishnan; Naval Gupta; Ricardo Bianchini; Jim Kleewein; Christian Belady; Marcus Fontoura; Julie Sinistore; Mukunth Natarajan; Lauren Johnson; VeeAnder Mealing; Praneet Arshi; Madeline Frieze
- Publisher
- Nature (Springer Science and Business Media LLC)
- Year
- 2025
- Volume
- 641
- Issue
- 8062
- Pages
- 331-338
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY-NC-ND 4.0 — share unaltered with attribution for noncommercial purposes
Original licence note
NonCommercial-NoDerivatives licence; citation only.
Citation
Husam Alissa; Teresa Nick; Ashish Raniwala; Alberto Arribas Herranz; Kali Frost; Ioannis Manousakis; Kari Lio; Brijesh Warrier; Vaidehi Oruganti; T. J. DiCaprio; Kathryn Oseen-Senda; Bharath Ramakrishnan; Naval Gupta; Ricardo Bianchini; Jim Kleewein; Christian Belady; Marcus Fontoura; Julie Sinistore; Mukunth Natarajan; Lauren Johnson; VeeAnder Mealing; Praneet Arshi; Madeline Frieze (2025). Using life cycle assessment to drive innovation for sustainable cool clouds. Nature (Springer Science and Business Media LLC). 641(8062), 331-338. https://doi.org/10.1038/s41586-025-08832-3
Events on this subject
- Data Centre World Frankfurt
- SC26 – International Conference for High Performance Computing, Networking, Storage and Analysis
- iMasons Climate Accord Summit
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.