White paperFree to read2025

10 Data Center Sustainability Improvements Quantified by Environmental Impact

Schneider Electric · Victor Avelar

Schneider Electric WP 188 takes a reference 1 MW data center and quantifies the carbon, energy and water effect of ten site-selection, design and operational improvements; the largest lever is a zero-Scope-2 electricity supply.

On this page

Overview

The reference facility is 1 MW and the combined effect is given against the baseline: total GHG falls from 84,100 to 11,300 t CO2e (-87%). PUE goes from 1.33 to 1.13 and total energy over the study period from 120,000 to 98,000 MWh (-18%). CUE drops from 0.441 to 0.003 t CO2e/MWh and WUE from 2.39 to 0.0 m3/MWh. The study dates from 2025.

The scope split: Scope 3 falls from 43,600 to 11,000 t CO2e and Scope 2 from 40,200 to 0. The calculation uses the 2024 US average grid emission factor of 454 kg CO2e/MWh (337 Scope 2 + 117 Scope 3 upstream); hydro is about 24, France about 27 and Sweden about 18 kg/MWh (2024). The spread between the US average and hydro, about 454 against 24 kg/MWh, means the same facility's Scope 2 emissions would differ by roughly a factor of 19 by location.

The ranking is clear: zero-Scope-2 supply is the single most effective action, with low-embodied-carbon IT second; direct-to-chip liquid cooling and IT life extension are also significant. Extending IT equipment life cuts total carbon about 7%. Results are given with PUE, CUE and WUE together so trade-offs such as water versus energy are visible. The limit is that the figures belong to one US-based reference facility; on other grids the Scope 2 share would differ widely.

Key points

  1. Total GHG falls from 84,100 to 11,300 t CO2e (-87%).
  2. PUE 1.33 to 1.13; total energy 120,000 to 98,000 MWh (-18%).
  3. CUE 0.441 to 0.003 t CO2e/MWh; WUE 2.39 to 0.0 m3/MWh.
  4. Scope 3 43,600 to 11,000 t CO2e; Scope 2 40,200 to 0.
  5. 2024 US average grid factor 454 kg CO2e/MWh (337 Scope 2 + 117 Scope 3); hydro about 24, France about 27, Sweden about 18 kg/MWh.
  6. Extending IT equipment life cuts total carbon about 7%.
  7. Zero-Scope-2 supply is the most effective single action; low-embodied-carbon IT is second.

Using it in design

  • In the sustainability panel compute operational CO2e = IT MWh x PUE x grid EF, with a grid-EF catalog by country/region (default US 454 kg CO2e/MWh incl. upstream) and a renewable-PPA toggle.
  • Add embodied carbon of IT and facility with a refresh-cycle parameter.
  • Show PUE, WUE and CUE together so trade-offs are visible, e.g. evaporative cooling lowers PUE but raises WUE.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Compare the cost of design decisions

Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.

Request a demo
CAPEX and TCO estimates in the SoSo CAD cost workspace

Who should read it

Sustainability leads and designers prioritizing among carbon, energy and water targets.

Related standards

  • GHG Protocol
  • ISO/IEC 30134-8
  • ISO/IEC 30134-9
  • EN 50600-4-8
  • EU Energy Efficiency Directive (data center reporting)

Publication details

Authors
Victor Avelar
Publisher
Schneider Electric
Year
2025
Document number
WP 188
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Victor Avelar (2025). 10 Data Center Sustainability Improvements Quantified by Environmental Impact. Schneider Electric. WP 188. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP188_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.