System Integration of a Computing Cluster, a Heat Recovery System and an Adsorption Chiller for Cold Production (OCP EMEA Summit 2025, Future Technologies Symposium)

Open Compute Project Foundation · Remi Bouzel

This Qarnot presentation describes coupling 65 C rack waste heat to a silica-gel/water adsorption chiller to produce 15 C chilled water.

On this page

Overview

The presentation was given by Remi Bouzel at the OCP EMEA Summit 2025 (Dublin), in the Future Technologies Symposium session on Data Center Sustainability. Qarnot is an HPC cloud provider that builds heat-reuse racks on OCP hardware, and it describes coupling its 65 C rack waste heat to a silica-gel/water adsorption chiller to produce 15 C chilled water.

The deck first compares the carbon footprint of a conventional 5 MW site with one reusing its heat, using PUE and ERE: PUE 1.6 / ERE 1.6 for the conventional data center and PUE 1.05 / ERE 0.10 for the heat-reuse data center. These figures are a scenario comparison, not measured site data. It then walks through the adsorption cycle and an experimental rig of about 8 kW.

The adsorption chiller is thermally driven; the heat source can be as low as 65 C, using a silica gel/water pair. The cycle temperatures shown are 65 C hot water drive, 25 C cooling water and 15 C chilled water. The experimental rig uses about 8 kW of compute electricity and 0.1 kW of pumps, with 65 C IT waste heat feeding the chiller.

The aim was to quantify cold production per computing load without harming PUE/ERE. Next steps include raising technology readiness and supporting adsorbents that regenerate below 65 C. This shows how low-grade heat can serve cooling demand when no heat customer exists. The work is at an experimental stage and the results belong to a single rig. ISO/IEC 30134-6 (ERF) is named as a related standard.

Key points

  1. Scenario for a 5 MW site: conventional DC PUE 1.6 / ERE 1.6 versus heat-reuse DC PUE 1.05 / ERE 0.10.
  2. The adsorption chiller is thermally driven; the heat source can be as low as 65 C, using a silica gel/water pair.
  3. Cycle temperatures: 65 C hot water drive, 25 C cooling water, 15 C chilled water.
  4. Experimental rig: about 8 kW of compute electricity, 0.1 kW of pumps, 65 C IT waste heat feeding the chiller.
  5. The aim was to quantify cold production per computing load without harming PUE/ERE.
  6. Next steps: raising technology readiness and adsorbents that regenerate below 65 C.
  7. Low-grade heat can serve cooling demand when no heat customer exists.
  8. Related standard: ISO/IEC 30134-6 (ERF).

Using it in design

  • In heat-reuse modelling, allow an adsorption-chiller sink with a minimum drive temperature (around 65 C).
  • Check whether the chosen liquid-cooling return temperature is high enough.
  • Report ERE alongside PUE when heat is exported.
  • For sites with no heat customer, consider cold production as a heat-use option.
  • Set up a reporting structure compatible with ISO/IEC 30134-6 (ERF).

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Compare the cost of design decisions

Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.

Request a demo
CAPEX and TCO estimates in the SoSo CAD cost workspace

Who should read it

Mechanical designers and sustainability leads who weigh heat recovery and liquid cooling together with sustainability metrics.

Related standards

  • ISO/IEC 30134-6 (ERF)

Publication details

Authors
Remi Bouzel
Publisher
Open Compute Project Foundation
Year
2025
Document number
OCP EMEA Summit 2025, FTS Data Center Sustainability
Event
OCP EMEA Summit 2025, Dublin
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Remi Bouzel (2025). System Integration of a Computing Cluster, a Heat Recovery System and an Adsorption Chiller for Cold Production (OCP EMEA Summit 2025, Future Technologies Symposium). Open Compute Project Foundation. OCP EMEA Summit 2025, FTS Data Center Sustainability. OCP EMEA Summit 2025, Dublin. https://drive.google.com/file/d/1kIs1xzI5EgvnQ9Hllwk0Zv2c0O63XpTF/view

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.