Data Center Rack Density Has Doubled. And It's Still Not Enough

Data Center Knowledge · Bill Kleyman

An article using AFCOM State of the Data Center 2024 results to show that average rack density doubled from 6.1 to 12 kW in eight years yet remains far below what AI needs.

On this page

Overview

Using AFCOM State of the Data Center 2024 results, the author shows that average rack density doubled over eight years, from 6.1 to 12 kW, yet remains far below what AI systems need. The average was 6.1 kW in AFCOM's first report and 12 kW in the 2024 report. Sixty percent of respondents are working to increase density, with methods being airflow improvements at 58%, containment at 42% and liquid cooling at 40%.

Operators are mostly raising density through airflow improvements and containment, which are reaching their physical limits. Fifty-three percent believe generative AI will definitely increase colocation capacity requirements. A single NVIDIA DGX H100 system draws up to 10.2 kW, so a 12 kW rack fits only one. Operators are being asked to move from 6-12 kW to 40-60 kW or more per rack, beyond practical air cooling.

The author argues for rear-door heat exchangers (RDHx) as a retrofit path and direct-to-chip (DTC) cooling for the highest densities. RDHx suits medium and high density in existing air-cooled halls, and DTC and RDHx can be combined to move the full heat load to liquid. The piece is a freely accessible industry commentary; only the record's summary and key facts were used here and the full text was not read.

Key points

  1. AFCOM average rack density: 6.1 kW in the first report, 12 kW in the 2024 report.
  2. 60% of respondents are working to increase density; methods: airflow improvements 58%, containment 42%, liquid cooling 40%.
  3. 53% believe generative AI will definitely increase colocation capacity requirements.
  4. A single NVIDIA DGX H100 system draws up to 10.2 kW, so a 12 kW rack fits only one.
  5. Operators are being asked to move from 6-12 kW to 40-60 kW or more per rack, beyond practical air cooling.
  6. RDHx suits medium and high density in existing air-cooled halls; DTC and RDHx can be combined to move the full heat load to liquid.

Using it in design

  • When a user places GPU servers in a rack, compute kW from server count and warn if the rack budget is exceeded (e.g. one DGX H100 = 10.2 kW).
  • Offer RDHx as a retrofit cooling choice for existing air-cooled rooms.
  • Recommend DTC above about 40 kW.
  • In a density-increase plan, state the physical limits of airflow improvements and containment.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Operators and cooling designers planning to raise rack density in existing halls and prepare for AI loads.

Publication details

Authors
Bill Kleyman
Publisher
Data Center Knowledge
Year
2024
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Bill Kleyman (2024). Data Center Rack Density Has Doubled. And It's Still Not Enough. Data Center Knowledge. https://www.datacenterknowledge.com/cooling/data-center-rack-density-has-doubled-and-it-s-still-not-enough

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.