Technical guideFree to read2024

Environmental Data Center Management & Monitoring

Legrand

This Legrand white paper explains which environmental sensors a white space needs and how to place them along aisles and on cabinets. As supply temperatures creep toward the top of the ASHRAE envelope, rack-level sensing becomes a design decision rather than an afterthought.

On this page

Overview

The paper opens by noting that legacy rooms were often held near 60 F (16 C), while the ASHRAE recommended range it cites is 65-80 F (18-27 C) and 20-80 % RH. Around 80 F is also where server fans begin to speed up. As operators push toward the top of that range, knowing each rack's inlet condition matters more than a room-average reading, and the text argues that measurement must cover several quantities, not temperature alone.

The sensor inventory has eight headings: temperature, humidity, differential pressure, airflow, leak, door, shock/vibration and air quality. The placement rule is concrete. Put at least one measuring point every 10-30 ft (3-9 m) of aisle or on every fourth cabinet, and measure aisle temperature about 4.9 ft (1.5 m) above the floor. That spacing is meant to expose a hot spot at aisle scale instead of leaving it hidden between sensors.

Psychrometric worked examples show why humidity gets its own sensor. Outside air at 40 F and 50 % RH, warmed to roughly 80 F, ends below 15 % RH, under the 20 % recommendation. In the opposite direction, 75 F air at 50 % RH carries about 0.019 lb of water per lb of air but saturates at about 0.004 lb/lb at 32 F, so the excess condenses on cold glass. Both cases tie economiser operation and cold surfaces to a measurable risk.

For vibration, the limit follows the most sensitive device in the cabinet: if two servers tolerate 5 g and 12 g peak shock, the cabinet should stay below the lower 5 g value. The closing section lists buying criteria, with an example specification of +/-2 C temperature accuracy, +/-5 % RH accuracy and up to 32 sensor packages cascaded over Cat5/6, plus DCIM integration. The author is a manufacturer, so the product-selection part reflects a vendor view.

Key points

  1. Legacy rooms were often held near 60 F (16 C); the cited ASHRAE recommendation is 65-80 F (18-27 C) and 20-80 % RH.
  2. About 80 F is near the point where server fans speed up.
  3. Place one measuring point every 10-30 ft (3-9 m) of aisle or every fourth cabinet.
  4. Aisle temperature is measured about 4.9 ft (1.5 m) above the floor.
  5. 40 F / 50 % RH outside air warmed to about 80 F falls below 15 % RH.
  6. 75 F / 50 % RH air holds about 0.019 lb/lb of water but only about 0.004 lb/lb at 32 F, so it condenses on cold glass.
  7. Cabinet vibration limit equals the weakest installed device (5 g in a 5 g / 12 g pair).
  8. Example sensor spec: temperature +/-2 C, RH +/-5 %, up to 32 sensor packages cascaded.

Using it in design

  • In the layout tool, auto-place temperature/humidity sensors at least every fourth cabinet or every 3-9 m of aisle, at inlet heights including about 1.5 m, and flag aisles with none.
  • Warn on direct outside-air economisation in cold climates without humidification, since RH can fall below 20 %.
  • Let rack records carry a vibration tolerance and compute the cabinet limit as the minimum across installed devices.
  • Add sensor catalogue fields for type, accuracy and cascade limit.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Assess redundancy through scenarios

Compare normal operation and equipment failures in SoSo CAD, with supplied loads and capacity shortfalls in one view.

Request a demo
Normal operation and failure scenario comparison in SoSo CAD

Who should read it

Engineers laying out white-space environmental monitoring and operators selecting a sensor system.

Related standards

  • ASHRAE TC 9.9 Thermal Guidelines
  • ISO 14644

Publication details

Authors
Legrand
Publisher
Legrand
Year
2024
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Legrand (2024). Environmental Data Center Management & Monitoring. Legrand. https://www.legrand.com/datacenter/sites/g/files/ocwmcr716/files/2025-05/White%20Paper%20-%20Environmental%20Data%20Center%20Management%20%26%20Monitoring.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.