Toxic fluoride gas emissions from lithium-ion battery fires
Scientific Reports (Springer Science and Business Media LLC) · Fredrik Larsson, Petra Andersson et al.
Seven types of commercial lithium-ion cells and packs were burned over a propane burner at RISE while heat release and fluoride gases were measured; burning cells release large amounts of hydrogen fluoride (HF) per unit of stored energy.
CC BY 4.0 — share with attribution
On this page
Overview
The study asks how much toxic fluoride gas burning Li-ion batteries release and whether water mist changes it. Seven types of commercial cells and packs (LCO, LFP, NCA/LATP and a laptop pack) were burned over a propane burner under the Single Burning Item hood at RISE, across several states of charge. Heat release and fluoride gases were measured, with HF cross-checked by FTIR and by gas-washing bottles. In total 39 fire tests were run using a 16 kW propane burner; HRR was measured in 38 tests, FTIR in 35 and gas-washing bottles in 19.
Burning Li-ion batteries released 20 to 200 mg/Wh of HF relative to nominal energy capacity, verified by two independent methods. Extrapolated, this is 2-20 kg of HF for a 100 kWh battery system and 20-200 kg for a 1000 kWh system such as a small stationary storage installation. For comparison, the IDLH level for HF is 0.025 g/m³ (30 ppm) and the 10-minute lethal AEGL-3 is 0.0139 g/m³ (170 ppm). POF3 was measured at 15-22 mg/Wh, but only for one cell type (type A) at 0% SOC. Four repeat tests of type B LFP pouch cells at 100% SOC gave a mean FTIR-measured HF release of 166.8 mg/Wh (standard deviation 11.5 mg/Wh).
Water mist (851 g of water applied) increased the peak HF production rate by 35% but had no significant effect on the total HF released; it delayed the fire and briefly raised the HF production rate. The authors argue that toxic gas, not only heat, must be included in risk assessments for large battery installations, especially in confined spaces.
Limits: measurements come from small-scale fire tests of cells and packs and are extrapolated linearly to large systems; POF3 was measured for a single cell type at 0% SOC; and the water-mist test used a limited amount of water.
Key points
- Burning Li-ion batteries released 20 to 200 mg/Wh of HF relative to nominal energy capacity, verified by two independent measurement methods.
- Extrapolated, this is 2-20 kg of HF for a 100 kWh battery system and 20-200 kg for a 1000 kWh system.
- For comparison, the IDLH level for HF is 0.025 g/m³ (30 ppm) and the 10-minute lethal AEGL-3 is 0.0139 g/m³ (170 ppm).
- POF3 was measured at 15-22 mg/Wh, but only for one cell type (type A) at 0% SOC.
- Water mist (851 g of water applied) increased the peak HF production rate by 35% but had no significant effect on the total HF released.
- Four repeat tests of type B LFP pouch cells at 100% SOC gave a mean FTIR-measured HF release of 166.8 mg/Wh (standard deviation 11.5 mg/Wh).
- In total 39 fire tests were run with a 16 kW propane burner; HRR was measured in 38 tests, FTIR in 35 and gas-washing bottles in 19.
Using it in design
- Add HF toxicity to risk assessments for enclosed battery rooms and BESS: take 20-200 mg/Wh of stored energy and compare the resulting room concentration with the IDLH (0.025 g/m³) and 10-minute AEGL-3 values.
- Knowing water mist does not reduce total HF and only delays the fire while raising peak production rate, do not justify the suppression system as an HF-reduction measure; add evacuation and ventilation controls.
- Check the HF yield input of probabilistic models against this study's mg/Wh range.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Bring standards pre-checks into your project
Review model-based TS EN 50600 and Tier pre-checks, missing inputs and items requiring engineering review in SoSo CAD.
Request a demo
Who should read it
Engineers assessing fire and toxic-gas risk for Li-ion battery installations in enclosed spaces.
Document contents
- Introduction
- Results (fire tests, heat release, fluoride gas emissions, repeatability, water mist measurements)
- Conclusions
- Methods (batteries, fire tests, HF measurement, water mist test)
Related standards
- NFPA 855
- UL 9540A
- IEC 62619
Read the document
li-ion-fire-fluoride-gas-emissions-2017.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Fredrik Larsson; Petra Andersson; Per Blomqvist; Bengt-Erik Mellander
- Publisher
- Scientific Reports (Springer Science and Business Media LLC)
- Year
- 2017
- Volume
- 7
- Issue
- 1
- Pages
- 10018
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- www.nature.com
Original licence note
PDF p.13 states 'This article is licensed under a Creative Commons Attribution 4.0 International License'. The PDF header notes that an Author Correction to this article was published separately.
Citation
Fredrik Larsson; Petra Andersson; Per Blomqvist; Bengt-Erik Mellander (2017). Toxic fluoride gas emissions from lithium-ion battery fires. Scientific Reports (Springer Science and Business Media LLC). 7(1), 10018. https://doi.org/10.1038/s41598-017-09784-z