Meta 2025 Environmental Data Index (data center PUE and WUE)
Meta
Meta's annual data tables with fleet-level data centre electricity use, PUE, water withdrawal and WUE for 2020-2024.
On this page
Overview
Meta's annual environmental data tables cover fleet-level data centre electricity use, PUE, water withdrawal and WUE for 2020-2024. PUE was 1.10 in 2020, 1.09 in 2021 and 1.08 in 2022-2024. Meta's owned data centres report PUE of about 1.08 and WUE below 0.2 L/kWh. The series shows a hyperscale operator improving slowly and then levelling off. The PUE has been flat at 1.08 since 2022.
The WUE series shows a clearer improvement: 0.30 in 2020, 0.26 in 2021, 0.20 in 2022, 0.18 in 2023 and 0.19 in 2024 L/kWh. WUE here is defined as water withdrawal (L) divided by IT electricity load (kWh), so it is withdrawal-based, not consumption-based. The small rise from 2023 to 2024 shows the improvement is not linear. A withdrawal-based WUE reads higher than a consumption-based value for systems that return water, so comparisons need the same definition.
The scale data illustrate growth: total electricity consumption went from 7,170,000 MWh in 2020 to 18,423,634 MWh in 2024 (about 2.6 times), and total water withdrawal from 3,726 ML to 5,637 ML. Efficiency held steady while absolute use grew fast. The tables are company statements, and the withdrawal-based WUE definition can differ from the site water use definition in ISO/IEC 30134-9.
Key points
- Data centre PUE: 1.10 (2020), 1.09 (2021), 1.08 (2022-2024).
- Annual WUE: 0.30 (2020), 0.26 (2021), 0.20 (2022), 0.18 (2023), 0.19 (2024) L/kWh.
- WUE = water withdrawal (L) / IT electricity load (kWh).
- Total electricity consumption 7,170,000 MWh (2020) -> 18,423,634 MWh (2024).
- Total water withdrawal 3,726 ML (2020) -> 5,637 ML (2024).
Using it in design
- Take hyperscale best-in-class WUE of about 0.2 L/kWh (withdrawal basis) and PUE of about 1.08 as benchmarks.
- In the WUE calculator let users choose withdrawal or consumption basis and label the result.
- Meta and Microsoft use withdrawal-based WUE while ISO/IEC 30134-9 defines site water use; state in the report which one applies.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Compare the cost of design decisions
Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.
Request a demo
Who should read it
Engineers seeking external benchmarks for WUE and PUE targets and sustainability reporters.
Related standards
- ISO/IEC 30134-2
- ISO/IEC 30134-9
Publication details
- Authors
- Meta
- Publisher
- Meta
- Year
- 2025
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Meta (2025). Meta 2025 Environmental Data Index (data center PUE and WUE). Meta. https://sustainability.atmeta.com/asset/2025-environmental-data-index
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.