Whitepaper Rittal PDU international
Rittal
Rittal's guide to rack power distribution units covers placement, phase and current ratings, connector types and temperature rating. It argues that cheap socket strips are a reliability and fire risk under German electrical rules, and that metered, managed PDUs belong in modern racks.
On this page
Overview
PDUs come single- or three-phase with 16, 32 or 63 A; a 63 A three-phase PDU distributes a little over 43 kW, and nearly 90 kW with two redundant PDUs on separate paths. C14 inlets carry up to 10 A and C20 up to 16 A for large consumers such as blade PSUs. At 27 C inlet, servers exhaust 42-45 C air, so PDUs should be rated for ambient up to 45 C.
Relay design is examined: permanently energised mechanical relays can draw up to 50 W in a fully populated PDU, whereas bistable relays avoid this and keep their state on supply loss. Energy (kWh) is metered to +/-1 % and other values to +/-2 %; the cited PDU MTBF is 80,000 h and CMC III handles up to 32 external sensors or devices.
The power-factor section touches UPS sizing: UPSs are designed for +0.8 inductive PF while blade servers present -0.95 to -0.90 capacitive PF, so UPSs reach their limits sooner than planned. On security, SNMP v1/v2 send passwords in clear text, and SNMPv3 (RFC 3410-3419) with USM should be preferred. The paper rests on German rules (DIN VDE 0100-420) and reflects a manufacturer view.
Key points
- PDUs come single- or three-phase at 16, 32 or 63 A; a 63 A three-phase unit distributes a little over 43 kW, nearly 90 kW with two redundant PDUs.
- C14 inlets carry up to 10 A; C20 up to 16 A for large consumers.
- At 27 C inlet servers exhaust 42-45 C air; PDUs should be rated for 45 C ambient.
- Permanently energised mechanical relays can draw up to 50 W in a full PDU; bistable relays avoid this.
- UPSs are designed for +0.8 inductive PF while blade servers show -0.95 to -0.90 capacitive PF.
- kWh metered to +/-1 %, other values +/-2 %; PDU MTBF 80,000 h; CMC III handles up to 32 sensors/devices.
- SNMP v1/v2 send passwords in clear text; SNMPv3 should be preferred.
Using it in design
- Keep PDU catalogue fields for phases, input A, max kW, outlet types, ambient rating, metering accuracy, relay type and management protocol (SNMPv3).
- Warn if a rear-mounted PDU rating is below the design exhaust temperature, and compute per-PDU kW from V x A x phases.
- In UPS sizing allow a (leading) load power-factor input and warn when IT PF is capacitive against the UPS rating.
- Flag SNMP v1/v2-only devices in the security check.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Electrical designers selecting rack PDUs and accounting for UPS power-factor effects, plus network security owners.
Related standards
- DIN VDE 0100-420
- EN 60950-1
- IEC 60320
- RFC 3410-3419 (SNMPv3)
Publication details
- Authors
- Rittal
- Publisher
- Rittal
- Year
- 2014
- Document number
- 5_2236
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Rittal (2014). Whitepaper Rittal PDU international. Rittal. 5_2236. https://www.rittal.com/imf/none/5_2236
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.