Bilgi ve İletişim Güvenliği Rehberi - 3.6.2 Sistem Odası/Veri Merkezine Yönelik Güvenlik Tedbirleri (Information and Communication Security Guide - measures for system rooms/data centres)

Original title Bilgi ve İletişim Güvenliği Rehberi – 3.6.2 Sistem Odası/Veri Merkezine Yönelik Güvenlik Tedbirleri (Information and Communication Security Guide – measures for system rooms/data centres)

T.C. Cumhurbaşkanlığı Siber Güvenlik Başkanlığı

This guide from the Presidency's Cyber Security Directorate contains three-level security measures for system rooms and data centres of public bodies and critical infrastructure. Though not a design standard, it is the compliance baseline Turkish public clients reference.

On this page

Overview

The guide is Version 1.1 (01.03.2026) published by the T.C. Cumhurbaşkanlığı Siber Güvenlik Başkanlığı; the section covered is 3.6.2. It is Turkey's national information-security guide for public bodies and critical infrastructure, and it grades measures for system rooms and data centres in three levels.

Beyond access control, it sets physical-infrastructure expectations. The power feed to the system room/data centre must be redundant; a dedicated UPS must carry the room until the generator starts, and no other devices may be connected to that UPS. The generator fuel tank must always be full and redundant, fuel checks must be recorded during long runs, and UPS and generator maintenance and tests must be logged.

Water, power, humidity, temperature and smoke must be monitored with thresholds and alarms, and monitoring must not be exposed externally. Rooms must be located away from kitchens, water and waste lines, water-based suppression, ducts, gas and flammables, with seismic resistance documented and lightning protection provided. Walls and floors must use moisture- and flame-resistant insulation, the room must be sealed with no openings for heat, humidity and air tightness, and data center earthing must be measured periodically.

Level 3 requires redundant precision air conditioning: one unit on standby starts automatically on failure or insufficient cooling, restarts automatically after power returns and raises fault alarms. Cables must be labelled individually and routed in separate cable trays, and entry must be authenticated and logged. The related sources are ISO/IEC 27001 and TS EN 50600-2-5.

Key points

  1. Power feed to the room must be redundant; a UPS must carry the room until the generator starts, with no other devices on that UPS (3.6.2.7, level 1).
  2. Generator fuel tank must always be full and redundant; UPS and generator maintenance/tests must be logged.
  3. Water, power, humidity, temperature and smoke must be monitored with thresholds and alarms; monitoring must not be exposed externally (3.6.2.5).
  4. Rooms must be away from kitchens, water/waste lines, water-based suppression, ducts, gas and flammables; seismic resistance documented; lightning protection provided (3.6.2.8).
  5. Moisture- and flame-resistant insulation in walls and floors; room sealed with no openings; data center earthing measured periodically.
  6. Level 3: redundant precision air conditioning with a standby unit that starts automatically, auto-restart after power return and fault alarms (3.6.2.15).
  7. Cables labelled individually and routed in separate cable trays; authenticated and logged entry.

Using it in design

  • Provide a Turkey public-sector compliance checklist mapping the measures to design objects: dedicated IT UPS, N+1 air conditioning with auto changeover, redundant feeds, generator fuel redundancy, room adjacency checks against wet areas.
  • Warn when a shared UPS or a single cooling unit is used for a room tagged as public-sector critical.
  • Design the monitoring system so it is not exposed externally.
  • Add cable labelling and separate cable tray requirements to the cabling specification.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Bring standards pre-checks into your project

Review model-based TS EN 50600 and Tier pre-checks, missing inputs and items requiring engineering review in SoSo CAD.

Request a demo
Selected rule packs and findings in the SoSo CAD standards panel

Who should read it

Engineers and compliance officers designing system rooms and data centers for public bodies and critical infrastructure in Turkey.

Related standards

  • ISO/IEC 27001
  • TS EN 50600-2-5

Publication details

Authors
T.C. Cumhurbaşkanlığı Siber Güvenlik Başkanlığı
Publisher
T.C. Cumhurbaşkanlığı Siber Güvenlik Başkanlığı
Year
2026
Document number
Sürüm 1.1 (01.03.2026), Bölüm 3.6.2
Document language
English
Source type
Turkish regulation
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

T.C. Cumhurbaşkanlığı Siber Güvenlik Başkanlığı (2026). Bilgi ve İletişim Güvenliği Rehberi – 3.6.2 Sistem Odası/Veri Merkezine Yönelik Güvenlik Tedbirleri (Information and Communication Security Guide – measures for system rooms/data centres). T.C. Cumhurbaşkanlığı Siber Güvenlik Başkanlığı. Sürüm 1.1 (01.03.2026), Bölüm 3.6.2. https://cdn.siberguvenlik.gov.tr/public/docs/bg_rehber.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.