Impact of High Density Hot Aisles on IT Personnel Work Conditions
Schneider Electric · Jim Fink
This paper uses CFD to compare staff heat stress in an uncontained raised-floor room and in a room with an enclosed hot aisle. It finds containment raises heat stress only slightly.
On this page
Overview
The paper uses CFD to compare heat stress for staff in an uncontained raised-floor room and in a room with an enclosed hot aisle. Heat stress is expressed as WBGT, the metric used in OSHA and ISO work/rest limits. The finding is that containment raises hot-aisle WBGT by only about 1 degF, because IT exhaust air is dry (typically below 20 percent RH) and evaporation from people still works. In the uncontained case the air behind racks averaged about 4.4 C (8 F) above the cold aisle.
OSHA WBGT limits for moderate work are about 30 C (86 F) for continuous work, 87 F for 75/25 work/rest, 89 F for 50/50 and 32.2 C (90 F) for 25/75. Bulk room conditions were historically about 22 C (72 F). At the densities studied, hot-aisle heat stress stays well below the regulatory limits. The results depend on specific assumptions: 3 kW per rack, 45 percent RH control and a 0.91 m (36 in) unobstructed raised floor. For designs that depart from those assumptions, especially shallower or obstructed floors, the conclusions may not hold.
In a design tool a hot-aisle work-environment check can be defined. Hot-aisle dry-bulb temperature is estimated as supply temperature plus rack deltaT, and WBGT is estimated from humidity. Above 30 C WBGT, work/rest scheduling is needed; 32.2 C is the limit of the 25/75 regimen. The check should appear in the containment designer and in operations and maintenance notes.
Key points
- Containment raised hot-aisle heat stress by only about 1 degF WBGT versus an uncontained room
- OSHA WBGT limits (moderate work): continuous about 86 F/30 C; 75/25 87 F; 50/50 89 F; 25/75 90 F (32.2 C)
- Bulk room conditions historically about 22 C (72 F); IT exhaust typically below 20 percent RH
- CFD study fixed at 3 kW per rack, 45 percent RH control, 0.91 m (36 in) unobstructed raised floor
- Air behind racks averaged about 4.4 C (8 F) above the cold aisle in the uncontained case
Using it in design
- Add a hot-aisle work-environment check
- Estimate hot-aisle dry-bulb as supply temperature + rack deltaT, and estimate WBGT from humidity
- Warn when WBGT exceeds 30 C (work/rest scheduling needed) or 32.2 C (the 25/75 limit)
- Show this check in the containment designer and in O&M notes
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Engineers designing hot-aisle containment and data-centre operations safety officers.
Related standards
- OSHA heat stress (WBGT)
- ISO 7243
- ASHRAE TC9.9 Thermal Guidelines
Publication details
- Authors
- Jim Fink
- Publisher
- Schneider Electric
- Year
- 2010
- Document number
- WP 123
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Jim Fink (2010). Impact of High Density Hot Aisles on IT Personnel Work Conditions. Schneider Electric. WP 123. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_JFIK-645ST7_EN
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.