High Efficiency Indirect Air Economizer-based Cooling for Data Centers

Schneider Electric · Wendy Torell

A Schneider Electric white paper showing that an indirect air-to-air economizer with evaporative assist can match or beat direct fresh-air cooling on energy, without bringing outside contaminants and humidity swings into the IT space.

On this page

Overview

Wendy Torell's paper argues that an indirect air economizer can keep outside contaminants and humidity swings out of the IT space while matching the energy performance of direct fresh-air cooling. Four design principles carry the argument: make economizer the primary operating mode, use mechanical cooling only as trim or backup, widen the IT temperature window, and build the system modular, pre-engineered and with integrated controls.

The numbers show the effect. Air-to-air alone gives 2,419 hours of full economizer (28% of the year) at 21.1 C IT inlet and 4,070 hours (47%) at 27 C. With evaporative assist, this rises to 4,394 hours (50%) at 21.1 C and 6,289 hours (72%) at 27 C. A traditional chilled-water plant runs economizer about 25% of the year, against more than 50% for the indirect evaporative design. The paper claims these principles cut cooling energy by about 50% versus traditional designs.

Footprint and water are compared too. Typical data centres lose 10 to 20% of white space to physical infrastructure; indirect modules placed outside use about 30 m2 per 100 kW of IT, roughly 5% of computer-room space. On water, cooling towers use about 40 gpm per 1,000 tons (151.4 L/min) every hour of the year, while the indirect evaporative system uses water only when evaporative assist runs. The text is a design argument, and the energy-saving claim rests on the author's design principles; the hour counts are given for one climate and specific IT inlet temperatures. For a different site, economizer hours need to be recalculated.

Key points

  1. The design principles are claimed to cut cooling energy by about 50% versus traditional designs.
  2. Air-to-air only: 2,419 h (28% of the year) of full economizer at 21.1 C IT inlet; 4,070 h (47%) at 27 C.
  3. With evaporative assist: 4,394 h (50%) at 21.1 C; 6,289 h (72%) at 27 C.
  4. Typical data centres lose 10 to 20% of white space to physical infrastructure.
  5. Indirect modules placed outside use about 30 m2 per 100 kW of IT, about 5% of computer-room space.
  6. A traditional chilled-water plant runs economizer about 25% of the year versus more than 50% for the indirect evaporative design.
  7. Cooling towers use about 40 gpm per 1,000 tons (151.4 L/min) every hour; indirect evaporative cooling uses water only when evaporative assist runs.

Using it in design

  • Add the indirect evaporative cooler (IEC) as a plant type, with parameters for approach temperature, wet-bulb effectiveness, trim DX capacity fraction and water use only during evaporative hours.
  • In the economizer-hours calculator, give a slider for IT inlet setpoint from 21 to 27 C and show the change in hours live.
  • At sites where direct outside air is ruled out by air quality or humidity, compare the indirect module against the direct fresh-air option on the same energy metric.
  • Reserve the module footprint (about 30 m2 per 100 kW of IT) as outdoor area on the site plan.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Designers and investors who want low-energy cooling but cannot accept direct fresh air because of air quality or humidity.

Related standards

  • ASHRAE TC9.9 Thermal Guidelines
  • ASHRAE 90.4

Publication details

Authors
Wendy Torell
Publisher
Schneider Electric
Year
2017
Document number
WP 136
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Wendy Torell (2017). High Efficiency Indirect Air Economizer-based Cooling for Data Centers. Schneider Electric. WP 136. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WTOL-8DNR9U_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.