Capital Cost Analysis of Immersive Liquid-Cooled vs. Air-Cooled Large Data Centers
Schneider Electric · Robert Bunger, Wendy Torell et al.
A Schneider Electric white paper comparing the capital cost of a 2 MW air-cooled data centre with a chassis-based immersive liquid-cooled design. Capex is roughly equal at equal density and falls with compaction.
On this page
Overview
The paper compares the capex of a 2 MW air-cooled data centre with a chassis-based immersive liquid-cooled design. At equal density, 10 kW per rack, the two cost about the same (reference build cost about $10/W): savings of about $0.91/W from removing chillers and CRAHs offset a liquid-cooling technology premium of about $0.77/W. The sensitivity range for the technology premium is $0.50 to $1.10/W.
Because liquid cooling allows compaction, the paper also models 20 kW and 40 kW per rack. Capex falls by about 10% at 20 kW per rack and about 14% at 40 kW, thanks to less building and white space. Assumptions drive the result: the liquid design uses 40 C/47.75 C facility water supply/return with 25% glycol, against 20/30 C for air. The air-cooled room supplies 24 C with a 14 C deltaT, and core and shell cost $90/ft2 ($969/m2).
On energy, IT fan savings are assumed at 9% of server energy (15 to 20% measured on high-intensity compute), the micro-pump penalty at 3% and rack heat loss to air at 5.5%. 40 C facility water is assumed to give full free cooling. Limits: costs are 2019 dollars and need escalation before use. The authors note the technology was not mature at the time and expect costs to fall. The result applies to chassis-based immersion only and does not transfer directly to other liquid-cooling methods.
Key points
- At 10 kW per rack in a 2 MW site, air-cooled and immersion capex are roughly equal (reference about $10/W).
- Compaction to 20 kW per rack saves about 10% capex; to 40 kW per rack about 14%.
- At 10 kW per rack, chiller/CRAH removal saves about $0.91/W; the liquid-cooling technology premium is about $0.77/W (sensitivity $0.50 to $1.10/W).
- Liquid design assumptions: 40 C/47.75 C facility water supply/return with 25% glycol, versus 20/30 C for air.
- IT fan savings assumed at 9% of server energy (15 to 20% measured on high-intensity compute), micro-pump penalty 3%, rack heat loss to air 5.5%.
- Air-cooled room supply 24 C with 14 C deltaT; core and shell cost $90/ft2 ($969/m2).
Using it in design
- Use as a seed for the TCO/capex comparison engine: liquidTechPremiumUsdPerW = 0.77 and chillerCrahSavingsUsdPerW = 0.91 (immersion).
- Compute compaction savings through smaller building area, and assume residual air heat of 5.5% of IT for immersion.
- Show the user that liquid cooling is roughly capex-neutral at equal density and cheaper when compacted.
- Label costs as 2019 USD and require escalation.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Finance, planning and design teams comparing the capital cost of liquid and air cooling.
Related standards
- ASHRAE TC9.9 Liquid Cooling Guidelines
- OCP Advanced Cooling Solutions
Publication details
- Authors
- Robert Bunger; Wendy Torell; Victor Avelar
- Publisher
- Schneider Electric
- Year
- 2019
- Document number
- WP 282
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Robert Bunger; Wendy Torell; Victor Avelar (2019). Capital Cost Analysis of Immersive Liquid-Cooled vs. Air-Cooled Large Data Centers. Schneider Electric. WP 282. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP282_EN