Comparison of Neutral Wire Distribution Options for Data Centers

Schneider Electric · Malik Megdiche, Avelino De Oliveira et al.

This paper examines what happens when a 4-pole transfer switch at the main LV switchgear changes the UPS and downstream loads from a TN earthing system to an ungrounded system during generator changeover. It compares eight neutral distribution solutions.

On this page

Overview

The paper examines what happens when a 4-pole transfer switch at the main LV switchgear changes the UPS and downstream loads from a TN earthing system to an ungrounded system during generator changeover. It describes the resulting power-quality disturbances. The introduction also compares the typical 400/230 V global architecture with the 480/208/120 V North American one. One example of the disturbances is given: 25 µH x 100 A / 5 µs on a PEN conductor induces about 500 V. Transients of this kind show that the handling of the neutral conductor during changeover matters in design.

It then compares eight neutral distribution solutions, including isolation and PDU transformers, tabulating losses, footprint and cost trade-offs. Losses for transformer-based options are quantified: the PDU transformer option adds about 3% losses, and neutral conductor losses are about 1.1%. An isolation transformer on the UPS input adds about 1.98% at 100% load and about 0.7% in eco mode. These transients matter for power quality at sensitive IT equipment, and the choice of solution has a lasting effect on both initial investment and operating losses.

A limit is that the paper is a comparison of options rather than a design procedure, so the choice has to be made together with local regulations and site details. Even so, the figures show that earthing and neutral decisions feed directly into the efficiency calculation. Selecting among them therefore means weighing power quality, efficiency and cost together, instead of treating the neutral as a purely wiring detail.

Key points

  1. PEN conductor transient example: 25 µH x 100 A / 5 µs is about 500 V induced.
  2. The PDU transformer option adds about 3% losses; neutral conductor losses are about 1.1%.
  3. An isolation transformer on the UPS input adds about 1.98% losses at 100% load and about 0.7% in eco mode.
  4. Eight neutral distribution solutions are compared on losses, footprint and cost.
  5. The typical 400/230 V global architecture is compared with the 480/208/120 V North American one.

Using it in design

  • In the single-line builder, raise a warning when the transfer switch has 4 poles and the UPS neutral is not separately derived.
  • Show the options: a 3-pole switch with solid neutral, or an isolation transformer.
  • When a transformer is chosen, add its 1-3% losses to the efficiency model.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical engineers designing generator changeover, earthing and neutral distribution.

Related standards

  • IEC 60364-1
  • IEC 60364-4-44
  • IEC 62040-3
  • NEC 250

Publication details

Authors
Malik Megdiche; Avelino De Oliveira; Eric Brun
Publisher
Schneider Electric
Year
2022
Document number
WP 41
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Malik Megdiche; Avelino De Oliveira; Eric Brun (2022). Comparison of Neutral Wire Distribution Options for Data Centers. Schneider Electric. WP 41. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP41_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.