Diesel Rotary UPS (DRUPS) vs. Static UPS: A Quantitative Comparison for Cooling and IT Applications
Schneider Electric · Han Ming Kuang, Hng Yong Way et al.
A vendor-authored Schneider Electric white paper (WP 222, 2016) comparing low-voltage diesel rotary UPS with low-voltage static UPS in a 3 MW, 500-rack, 2N facility on losses, floor area and 10-year TCO.
On this page
Overview
The paper compares low-voltage DRUPS with low-voltage static UPS for a 3 MW, 500-rack facility in a 2N architecture covering IT and cooling loads, with chilled-water buffer tanks providing thermal ride-through in the static case. It challenges common DRUPS claims about efficiency, scalability, space and cooling energy, arguing they rest on old SCR-based static UPS curves and long VRLA autonomy. The base case is 3 MW IT at 6 kW per rack, 945 RT of cooling, N+1 water-cooled chilled water at 8-15 C, 2N electrical, a 5-minute static UPS battery and 2 x 28.6 m3 tanks for 8 minutes of ride-through.
At 47% IT utilisation, DRUPS part-load efficiency is 93% (226 kW loss) versus 97% (93 kW) for static; on the cooling side 91% (115 kW) versus 96% (15 kW). Total losses are 341 kW versus 108 kW, 68% lower for static. Plant floor area including maintenance access is about 1,128 m2 for DRUPS versus 1,176 m2 for static with thermal storage, only 4.3% more. DRUPS ride-through is about 8-12 seconds from utility loss to completed diesel start. The 10-year TCO is $82,001,841 for DRUPS and $76,109,746 for static, a 7.2% saving, with capex 27.8% and maintenance/cyclical replacement 25.2% lower for static.
The conclusion is conditional: including colocation rental gains (assumed $1,285 per rack per month) cuts the static saving to 3.7%, and for a 2N IT-only case DRUPS TCO becomes 10.6% better. The low-voltage limit is 6,300 A (about 4.36 MVA at 400 V), so no more than two 2 MVA DRUPS can be paralleled on one common bus. Li-ion batteries are cited as using 50-80% less space than VRLA. The study is vendor-authored with Singapore pricing converted to USD; appendices cover IT-only, cooling-only and tri-redundant variants.
Key points
- Base case: 3 MW IT (500 racks at 6 kW), 945 RT cooling, 2N, static UPS 5 min battery, 2 x 28.6 m3 tanks for 8 min.
- DRUPS ride-through about 8-12 seconds.
- At 47% IT utilisation: DRUPS 93% (226 kW loss) vs static 97% (93 kW); cooling side 91% (115 kW) vs 96% (15 kW).
- Total losses 341 kW vs 108 kW; static 68% lower.
- Plant area: DRUPS about 1,128 m2 vs static with thermal storage 1,176 m2 (4.3% more).
- 10-year TCO: DRUPS $82,001,841 vs static $76,109,746 (7.2% saving).
- With colocation rental the static saving drops to 3.7%; for 2N IT-only, DRUPS is 10.6% better.
- LV limit 6,300 A (about 4.36 MVA at 400 V): at most two 2 MVA DRUPS on one bus.
Using it in design
- Store full UPS efficiency curves (10/25/50/75/100% load), ride-through, footprint and service clearance, and a technology field (static VRLA, static Li-ion, DRUPS) rather than one peak value.
- Compute losses at the actual per-module utilisation implied by the redundancy scheme (2N typically below 50%).
- When cooling is not on UPS, require a thermal ride-through strategy (buffer tank volume versus generator start and chiller restart).
- Warn when a LV bus paralleling DRUPS exceeds 6,300 A / 4.36 MVA and suggest MV distribution; include battery replacement every 5 years, engine overhaul and optional space rental value in the TCO tool.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Designers and decision makers choosing UPS technology and redundancy architecture.
Related standards
- IEC 62040-3
- IEC 88528-11
- ISO 8528-1
Publication details
- Authors
- Han Ming Kuang; Hng Yong Way; Sanjeet Sandhu
- Publisher
- Schneider Electric
- Year
- 2016
- Document number
- WP 222
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Han Ming Kuang; Hng Yong Way; Sanjeet Sandhu (2016). Diesel Rotary UPS (DRUPS) vs. Static UPS: A Quantitative Comparison for Cooling and IT Applications. Schneider Electric. WP 222. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_VAVR-9WFNHS_EN
Events on this subject
- Electricity Eurasia 2027
- ELECO 2026 Elektrik-Elektronik ve Biyomedikal Mühendisliği Konferansı
- Data Center Frontier Trends Summit
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.