White paperFree to read2011

AC vs. DC Power Distribution for Data Centers

Schneider Electric · Neil Rasmussen

Neil Rasmussen's paper models end-to-end electrical efficiency at 50% load for five distribution options and recommends 400/230 V AC with high-efficiency UPS and power supplies for new builds.

On this page

Overview

The options compared are North American 480/208 V AC with PDU transformers, 400/230 V AC, 48 V DC, 380 V DC and a hybrid 575 V DC system. At 50% load the product of UPS, distribution and IT power-supply efficiency comes out at 83.56% for 480 to 208 V AC, 86.39% for 400/230 V AC, 80.74% for 48 V DC, 87.64% for 380 V DC and 80.74% for hybrid 575 V DC. The paper attributes many published DC advantages to outdated AC efficiency assumptions.

It grants that 380 V DC may offer about a 1% efficiency edge over the best AC system at full load, about 1.5% less rack heat and about 10% copper saving (9.5 kW per wire against 8.625 kW for 400/230 V AC with 50 A wiring). Wiring conduction losses are insignificant in real data centres because load diversity keeps circuits well below rating. DC UPS cost is typically 10% to 20% lower than AC UPS, but 48 V DC distribution needs 10X or more copper weight and cost and is impractical above 20 kW per cabinet.

Safety and compliance are weighed too: 380 V DC would not be legal in Japan, where the regulatory limit is 300 V, and North America has no arc-flash regulations for commercial DC. In hosting sites with much telecom equipment, the 48 V DC requirement may reach 10% of the AC requirement, and point-of-use battery-less rack rectifiers are recommended. The conclusion is that the North American 480 V AC system with PDU transformers should be viewed as inefficient and obsolete for new designs.

Key points

  1. Overall efficiency at 50% load (UPS x distribution x IT PSU): 480 to 208 V AC 83.56%; 400/230 V AC 86.39%; 48 V DC 80.74%; 380 V DC 87.64%; hybrid 575 V DC 80.74%.
  2. Wiring conduction losses are insignificant in real data centres because load diversity keeps circuits well below rating, though wire sizing must still meet the worst case.
  3. 380 V DC may offer about 1% efficiency over the best AC system at full load, about 1.5% less rack heat and about 10% copper saving (9.5 kW per wire vs 8.625 kW).
  4. DC UPS cost is typically 10-20% below AC UPS, but 48 V DC distribution needs 10X or more copper weight and cost and is impractical above 20 kW per cabinet.
  5. 380 V DC would be illegal in Japan, where the limit is 300 V; North America has no arc-flash regulation for commercial DC.
  6. In hosting sites with much telecom equipment the 48 V DC need may reach 10% of the AC need; point-of-use battery-less rack rectifiers are recommended.
  7. The paper calls the North American 480 V AC system with PDU transformers inefficient and obsolete for new designs.

Using it in design

  • In the power-chain efficiency calculator multiply UPS, transformer/PDU, distribution and PSU efficiencies at the actual load fraction rather than nameplate, and offer architecture presets for the five options with Table 1 values as defaults.
  • In North American projects, suggest 415/240 V distribution to eliminate PDU transformers.
  • Warn when 48 V DC busway is proposed above 20 kW per cabinet, or when DC distribution exceeds a local regulatory voltage limit (for example 300 V in Japan).
  • Give PDU catalogue entries a hasTransformer flag and a part-load efficiency curve.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Review your power design in SoSo CAD

Inspect supply paths, equipment loads and UPS failure scenarios in one model.

Request a demo
Single-line diagram in the SoSo CAD power and capacity workspace

Who should read it

Electrical designers choosing the distribution voltage and UPS architecture of a new facility.

Related standards

  • IEC 60364
  • NFPA 70

Publication details

Authors
Neil Rasmussen
Publisher
Schneider Electric
Year
2011
Document number
WP 63
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Neil Rasmussen (2011). AC vs. DC Power Distribution for Data Centers. Schneider Electric. WP 63. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_SADE-5TNRLG_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.