WP#32 - Carbon Usage Effectiveness (CUE): A Green Grid Data Center Sustainability Metric
The Green Grid · Christian Belady, Dan Azevedo et al.
CUE divides a data centre's total CO2e emissions by its IT equipment energy, exposing the one thing PUE never shows: how carbon-intensive the energy is.
On this page
Overview
The Green Grid's 2010 white paper no. 32 (authors include Christian Belady and Dan Azevedo) answers a question PUE cannot: two sites with identical PUE do not impose the same environmental burden when one draws from a coal-heavy grid and the other from hydropower. CUE collapses that difference into one number. It is the CO2e emitted because of the facility's total energy use (kgCO2e) divided by the energy delivered to IT equipment (kWh), written in kgCO2e/kWh.
The most practical feature is the factorisation CUE = CEF x PUE, where CEF is the kgCO2e attached to each kWh of energy entering the site. It lets you trace where an improvement came from. Lowering PUE is an infrastructure-efficiency job; lowering CEF is a matter of grid choice, supply contract or on-site generation. Because the same CUE can be reached by two different routes, reports should show both factors separately.
The ideal CUE is zero, meaning no carbon-emitting energy is used at all. Where PUE has a floor of 1.0, CUE is bounded only by the emission factor and can reach 0 with fully carbon-free supply. The definition was later carried into ISO/IEC 30134-8, so the white paper is the historical source while the standard is the text to cite in reporting today. The full paper requires registration, so this page rests on the definition and the factorisation.
Key points
- CUE = total CO2e from all data centre energy (kgCO2e) / IT equipment energy (kWh); unit kgCO2e/kWh.
- Equivalent form: CUE = CEF x PUE, with CEF the kgCO2e per kWh of site energy.
- Ideal value is CUE = 0, i.e. no carbon-emitting energy.
- The factorisation separates the effect of grid/energy supply from the effect of infrastructure efficiency.
- The definition is standardised in ISO/IEC 30134-8; GHG Protocol Scope 2 guidance is the related accounting framework.
Using it in design
- Compute CUE as grid emission factor (kgCO2e/kWh, per region and hour) x PUE.
- Add emissions from on-site fuel burning such as generator testing and CHP; using the grid factor alone understates CUE.
- Show CUE next to PUE and WUE in the same summary so an option that cuts carbon while raising water use is visible.
- Let users choose between location-based and market-based (PPA) emission factors, and state which one a report used.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Compare the cost of design decisions
Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.
Request a demo
Who should read it
Facility engineers preparing sustainability reports and decision makers comparing energy supply contracts.
Related standards
- ISO/IEC 30134-8
- GHG Protocol Scope 2 Guidance
Publication details
- Authors
- Christian Belady; Dan Azevedo; Michael Patterson; Jack Pouchet; Roger Tipley
- Publisher
- The Green Grid
- Year
- 2010
- Document number
- WP 32
- Document language
- English
- Source type
- Industry body
- Access
- Citation only
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Christian Belady; Dan Azevedo; Michael Patterson; Jack Pouchet; Roger Tipley (2010). WP#32 - Carbon Usage Effectiveness (CUE): A Green Grid Data Center Sustainability Metric. The Green Grid. WP 32. https://www.thegreengrid.org/en/resources/library-and-tools/241-WP%2332---Carbon-Usage-Effectiveness-%28CUE%29%3A-A-Green-Grid-Data-Center-Sustainability-Metric
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.