Advanced UPS Controls for AI Workloads Management: Enabling Stable Power Protection in High-Performance Computing Environments
Vertiv
This 2025 Vertiv technical note describes how a double-conversion UPS can be controlled to cope with the fast, repetitive power swings of GPU clusters.
On this page
Overview
The note starts from the load profile: representative AI cycles swing from about 10% idle to 80-100% roughly every minute, with sub-second bursts reaching 120-130% of GPU nominal power. That load pushes the battery into constant micro-cycling and stresses the upstream utility or generator. Two complementary firmware features are introduced: one that raises the DC-link voltage so short load steps are carried by the DC capacitors instead of the batteries, and input power smoothing that uses the battery as a buffer.
Input power smoothing works with a user-set fluctuation range FR%. In the example, a 1000 kW UPS at 900 kW average with FR 20% lets the input vary between 720 and 1080 kW. The example state-of-charge window is nominal 85%, minimum 50% and maximum about 97%; energy below the minimum is reserved for backup, and on generator the minimum can be lowered so smoothing may continue down to about 10% SOC at AI start-up.
Battery sizing results are decisive. In a simulation at 1200 kW, 30-100% load, 0.5 Hz and 50% duty, 7 Li-ion cabinets (64 A maximum recharge each) give only partial smoothing, while 14 cabinets give sustained full smoothing. On a gas-generator-fed GB300 installation, 6C-charge-capable modules reached 100% input smoothing with input variation limited to about 1% per second. The limits are rectifier current, generator load-step capability, battery charge/discharge current and SOC, and utility THDv tolerance; sizing should start from the measured load profile, not autonomy alone.
Key points
- Representative AI load cycles from idle (~10%) to 80-100% roughly every minute, with sub-second peaks at 120-130% of GPU nominal power.
- Input power smoothing uses a user-set FR%: a 1000 kW UPS at 900 kW average with FR 20% lets input vary 720-1080 kW.
- Example SOC window: nominal 85%, minimum 50%, maximum ~97%; energy below the minimum is reserved for backup, and on generator smoothing can continue to ~10% SOC.
- Simulation at 1200 kW, 30-100% load, 0.5 Hz, 50% duty: 7 Li-ion cabinets (64 A max recharge each) give partial smoothing, 14 give sustained full smoothing.
- With 6C-charge-capable modules on a gas-generator-fed GB300 installation, 100% input smoothing was reached with input variation limited to about 1% per second.
- Lab test on a large Li-ion UPS: load steps of 31-97% and 63-97% at 1 Hz kept input current nearly constant.
- Smoothing is bounded by rectifier current, generator load-step capability, battery charge/discharge current and SOC, and utility THDv tolerance.
Using it in design
- Add an AI load-profile object to IT loads (step amplitude %, repetition Hz, duty cycle, peak % of nominal) and use it in UPS and battery sizing alongside autonomy.
- Give UPS catalogue entries supportsBatteryShield, supportsInputPowerSmoothing, minimum FR% and overload capability, and battery entries maximum charge C-rate and recharge current per cabinet.
- When the upstream source is a generator or on-site gas turbine, compare its kW/s load-step tolerance with the smoothed input profile and warn if battery charge acceptance cannot sustain smoothing.
- Reserve a backup SOC floor in runtime calculations.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Electrical designers sizing UPS, batteries and upstream sources for GPU clusters.
Related standards
- IEC 62040-3
- ISO 8528-5
Publication details
- Authors
- Vertiv
- Publisher
- Vertiv
- Year
- 2025
- Document number
- SL-80384
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Vertiv (2025). Advanced UPS Controls for AI Workloads Management: Enabling Stable Power Protection in High-Performance Computing Environments. Vertiv. SL-80384. https://www.vertiv.com/4aebc7/globalassets/content---assets-2025/documents/advanced-ups-controls-for-ai-workloads-wp-en-gl-sl-80384-web.pdf
Events on this subject
- Electricity Eurasia 2027
- ELECO 2026 Elektrik-Elektronik ve Biyomedikal Mühendisliği Konferansı
- ICCI 2027 – Uluslararası Enerji ve Çevre Fuarı ve Konferansı
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.