Generators protection: Ekip G trip unit for SACE Emax 2 (White Paper)

ABB

A 2012 ABB white paper explaining the Ekip G trip unit of the SACE Emax 2 breaker for low-voltage generators, covering ANSI 51V, 40, 32, 81, 27/59, 81R, 59N, 25 and overcurrent functions with setting ranges and examples.

On this page

Overview

The white paper notes that generators, as rotating machines, are exposed to internal faults and to anomalies from the connected system, that protection is usually provided by separate multifunction relays, and that Ekip G integrates these into the SACE Emax 2 breaker. The applications section separates two main cases: autoproducers running permanently in parallel with the network (cogeneration, small hydro, biomass) and generators in island mode (for example ships and industrial emergency sets). With a medium-voltage connection the breaker protects each low-voltage generator with ANSI 40, 27, 59, 50, 51, 81H, 81L, 49 and 32RP; with a low-voltage network connection and several generators ANSI 25 synchronism check and 81R (anti-islanding on frequency creep) are added.

Three main sections cover the functions one by one: voltage-controlled overcurrent (ANSI 51V, dual threshold, step and linear modes; thresholds 0.6-10 x In, times 0.05-30 s, voltage parameter 0.2-1 x Vn), loss of excitation and reverse reactive power (ANSI 40 and 32RQ, threshold -1 to -0.1 x Sn, time 0.5-100 s), reverse active power (32RP), maximum and minimum power (32P, 32Q, 37), maximum and minimum frequency (81H, 81L), maximum and minimum voltage (27, 59), 81R, maximum homopolar voltage (59N), earth fault (51N/51G), synchronism check (25) and overload with short circuit (49, 51, 50). For each function it gives working modes, characteristics, setting ranges and numerical setting examples.

One numerical example sets the 51V thresholds on a 2500 kVA generator, another sets the power protections on a power base for a 2000 A breaker. It is a 2012 vendor white paper with parameter ranges specific to Ekip G; for other manufacturers' relays the method and setting logic should be read as an example.

Key points

  1. Ekip G integrates generator protection into the SACE Emax 2 breaker trip unit and reduces the need for a separate multifunction relay.
  2. Common functions with a medium-voltage connection: ANSI 40, 27, 59, 50, 51, 81H, 81L, 49, 32RP.
  3. With several generators in parallel on a low-voltage network, ANSI 25 (synchronism) and 81R (anti-islanding on frequency creep) are needed.
  4. 51V thresholds are 0.6-10 x In (step 0.1 x In), time 0.05-30 s, voltage parameter 0.2-1 x Vn, threshold correction factor Ks 0.1-1.
  5. Loss of excitation and reverse reactive power threshold is -1 to -0.1 x Sn, slope -2 to 2, time 0.5-100 s.
  6. Reverse and maximum active power are set as a percentage of the trip unit rated power (example: 831.384 kW threshold at 0.5 s on a 2000 A breaker).
  7. Frequency lower and upper thresholds lie around 0.9-0.99 x fn with time 0.5-60 s.
  8. For each function, working mode, characteristic, setting range and a numerical setting example are given.

Using it in design

  • List which ANSI functions the generator output breaker needs by connection type (medium-voltage parallel, low-voltage parallel, island) and tie trip-unit selection to it.
  • In network-parallel operation, match ANSI 25 and 81R protections to the network operator's anti-islanding requirement.
  • For 51V protection, set the voltage-dependent thresholds using the generator's short-circuit decrement curve and system coordination.
  • Calculate reverse power and loss-of-excitation settings on a power base from the generator rating and breaker rated current.
  • Include the protection settings in the coordination study and the commissioning test plan (secondary injection).

Who should read it

Electrical engineers designing low-voltage generator protection, coordination and switchgear.

Document contents

  1. Introduction
  2. Applications of generators and protections
  3. Protections of the Ekip G trip unit
  4. Voltage controlled overcurrent protection (51V)
  5. Power protections: loss of excitation (40, 32RQ), reverse power (32RP), maximum power (32P, 32Q), minimum power (37)
  6. Maximum and minimum frequency (81H, 81L)
  7. Minimum and maximum voltage (27, 59)
  8. ROCOF (81R)
  9. Maximum homopolar voltage (59N)
  10. Earth fault protection (51N, 51G)
  11. Synchronism check (25)
  12. Protection against overload and short circuit

Related standards

  • IEEE C37.102
  • IEC 60255
  • IEC 60034-1

Publication details

Authors
ABB
Publisher
ABB
Year
2012
Document number
1SDC007409G0201
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

ABB white paper, free download; copyright ABB, no open licence.

Citation

ABB (2012). Generators protection: Ekip G trip unit for SACE Emax 2 (White Paper). ABB. 1SDC007409G0201. https://library.e.abb.com/public/29d8dfb6f07f249ec1257b480047e9da/1SDC007409G0201.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.