Ablecom AbleCool CDR82 Rear Door Heat Exchanger specifications

Original title AbleCool CDR82 product specifications

Ablecom

Ablecom's AbleCool CDR82 is an active rear door heat exchanger for 48U-60U racks, with 78 kW base and 100 kW peak capacity at ATD 15 °C, six EC fans at 7,440 CFM and 100 LPM water flow.

On this page

Overview

The page presents the CDR82 model of Ablecom Technology's AbleCool (RDHx) family. The product is positioned as thermal management for next-generation GPU servers. The headline states 78 kW base and 100 kW peak capacity, a 6-piece EC centrifugal fan matrix with 7,440 CFM airflow, AC 200-277 V (1+1) supply with a 3.3 kW power envelope, 48U-60U racks and 100 LPM flow.

The specification table gives supported rack form 48U-60U, width 600-800 mm (23.62-31.50 in), depth 382.9-470 mm (15.07-18.50 in), cooling capacity 78 kW (100 kW at ATD = 15 °C) and fan quantity 6. The supply is dual-feed (1+1), providing redundancy. The page also has accessory and download tabs.

The Ablecom product page sits under the cooling solution heading and is aimed at AI, GPU and HPC racks. The page is limited to the values given as text: water inlet and outlet temperature, pressure drop, weight and water connection size are not on the page.

Key points

  1. Cooling capacity 78 kW base and 100 kW peak at ATD 15 °C.
  2. Six EC centrifugal fans; 7,440 CFM active airflow.
  3. Water flow 100 LPM.
  4. Supply AC 200-277 V (1+1), 3.3 kW power envelope.
  5. Rack form 48U-60U; width 600-800 mm; depth 382.9-470 mm.
  6. Active rear door heat exchanger (RDHx); positioned for GPU, AI and HPC racks.

Using it in design

  • Show in the rack load table that the 100 kW peak applies only at ATD 15 °C, while 78 kW is the general reference.
  • Connect the 1+1 supply to different UPS distribution legs; add the 3.3 kW fan power envelope to the rack load budget.
  • Size the secondary-circuit pipe diameter, pump and CDU capacity for 100 LPM; obtain the water temperature regime from the manufacturer.
  • Check on the plan the fit of 48U-60U height and 600-800 mm width, and the effect of door depth (382.9-470 mm) on aisle width.

Who should read it

Mechanical engineers selecting rear-door cooling for high-density GPU and HPC racks.

Document contents

  1. Product summary
  2. Specification table
  3. Accessory
  4. Downloads

Publication details

Authors
Ablecom
Publisher
Ablecom
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Ablecom AbleCool CDR82 product specifications. Ablecom. https://www.ablecom.com/en/product/Cooling_Solution/Rear_Door_Heat_Exchanger/RDHx_CDR82

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.