Technical guideFree to readYear not stated

Accelsius NeuCool MR250 Specifications

Original title NeuCool MR250 product specifications

Accelsius

Accelsius NeuCool MR250 is a two-phase, row-based direct-to-chip cooling CDU giving up to 250 kW for 1-4 racks, with 1+1 redundant pumps and a maximum system input of 2.6 kW.

On this page

Overview

Accelsius presents the NeuCool MR250 as the industry's first two-phase, row-based CDU. The unit provides up to 250 kW of liquid cooling capacity for large-scale deployments of high-density racks. A reservoir supplies inlet pressure for the pumps and expansion volume for transients from zero to full power; a brazed plate heat exchanger condenses refrigerant vapour and transfers heat to the facility water loop, with the facility water connection at top-rear, bottom-rear or through the bottom.

Configurations include 1×250 kW rack, 2×125 kW rack and warm rack expansions. The system supports two dielectric refrigerants: Eco+ (R-1233zd(E)) and Performance+ (R-515B), both with zero ODP, low GWP and an A1 safety rating. Pumps (1+1 redundant with automatic switchover on failure), power supplies and control boards are hot-swappable. The specification table gives 250 kW total cooling capacity and 2.6 kW maximum system input.

Key points

  1. Up to 250 kW of two-phase cooling capacity; 1×250 kW or 2×125 kW rack configuration.
  2. Maximum system input is 2.6 kW.
  3. Two pumps 1+1 redundant; automatic pump switchover.
  4. Refrigerant options R-1233zd(E) (Eco+) and R-515B (Performance+); ODP 0, A1.
  5. 15-inch NeuView touchscreen with DCIM integration.

Using it in design

  • The table supports one or two racks while the introductory copy mentions four; confirm the project configuration with the manufacturer.
  • Assess facility water temperature separately for the rated and derated compatibility ranges.
  • Hot-swappable pumps, power supplies and control boards shorten service time in the redundancy scheme.
  • Choose the refrigerant (R-1233zd(E) or R-515B) by GWP and safety class requirement.

Who should read it

Liquid-cooled data-centre designers evaluating two-phase direct-to-chip cooling.

Publication details

Authors
Accelsius
Publisher
Accelsius
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Accelsius NeuCool MR250 product specifications. Accelsius. https://accelsius.com/single-product-mr250/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.