Performance evaluation and modeling of active tile in raised-floor data centers: An empirical study on the single rack
Frontiers in Energy Research (Frontiers Media SA) · Haoyu Gao, Qiuling Yue et al.
A field study in a production raised-floor data centre (78 racks, open cold aisles, 0.5 m plenum, 55%-porosity tiles) of a fan-assisted perforated tile; active tiles cooled the rack top but could pull hot air in through the under-rack gap.
CC BY 4.0: share with attribution
On this page
Overview
Raised-floor data centres suffer local hotspots from uneven cool air delivery. The study examines a prototype active tile with eight 12 V fans under a standard tile and speed control from 1-100%. The test hall had a 4 m room height, 0.5 m plenum, 78 standard 42U racks around five open cold aisles of 0.61 m × 0.61 m tiles, underfloor supply with flooded-ceiling return, five 81.4 kW perimeter CRACs and a peak rack load of 6 kW. CRACs were set to 21 °C but delivered 23 °C supply, and thermal load was about 65% of cooling capacity, so one CRAC was off.
Rack inlet temperature profiles, tile airflow (using a 3×3 flow hood) and plenum-to-aisle pressure differential were measured at 11 tile settings, with and without the under-rack gap sealed. Tile pressure differential along a cold aisle was negative near the CRAC units and positive further away, because high-velocity discharge creates a low-pressure zone (Venturi effect). Replacing a passive tile with an active tile at only 10% fan speed raised mean tile velocity from 0.92 to 1.37 m/s, a 49% increase, while an unpowered active tile delivered only about 0.45 m/s against 0.95 m/s for the passive tile.
Active tiles lowered rack-top inlet temperatures by up to 4 °C but worsened the rack bottom, because low pressure at the tile surface drew hot air through the under-rack gap. Sealing the under-rack gap cut rack-bottom inlet temperature by as much as 6 °C (at 20% fan speed) and reduced inlet temperature variance from 5.19 to 0.42 at 20% fan speed and from 2.64 to 0.057 at 100%. Measured plenum-to-aisle pressure differentials were within about 1-4 Pa, and of the data-driven thermal models (GPR, ANN, MLR) GPR achieved the smallest prediction error, about 0.3 °C.
Limits: one data centre, a single rack and a prototype tile; results depend on this hall's geometry and CRAC layout. The authors stress that accurate thermal modelling of the active tile is the prerequisite for advanced control policies.
Key points
- Test hall: 4 m room height, 0.5 m plenum, 78 standard 42U racks around five open cold aisles of 0.61 m × 0.61 m tiles with 55% porosity, five 81.4 kW perimeter CRACs, peak rack load 6 kW.
- CRACs were set to 21 °C but delivered 23 °C supply, and thermal load was about 65% of cooling capacity, so one CRAC was off.
- Tile pressure differential along a cold aisle was negative near the CRAC units and positive further away (Venturi effect).
- Replacing a passive tile with an active tile at only 10% fan speed raised mean tile velocity from 0.92 to 1.37 m/s (49%); an unpowered active tile delivered only about 0.45 m/s against 0.95 m/s for the passive tile.
- Active tiles lowered rack-top inlet temperatures by up to 4 °C but worsened the rack bottom, because low pressure at the tile surface drew hot air through the under-rack gap.
- Sealing the under-rack gap cut rack-bottom inlet temperature by as much as 6 °C (at 20% fan speed); inlet temperature variance fell from 5.19 to 0.42 at 20% and from 2.64 to 0.057 at 100%.
- Measured plenum-to-aisle pressure differentials were within about 1-4 Pa, and the GPR thermal model achieved the smallest prediction error, about 0.3 °C.
Using it in design
- With active tiles, always seal under-rack gaps; if left open, low pressure at the tile surface pulls hot air in under the rack and worsens the lower servers.
- Consider a fan-assisted tile for rack-top hotspots (up to 4 °C reduction), and remember an unpowered active tile adds flow resistance relative to a passive tile (0.45 instead of 0.95 m/s).
- Check in tile airflow design that a Venturi effect near CRACs can create negative plenum-to-aisle pressure differentials.
Who should read it
Cooling engineers and operators dealing with air distribution and hotspot removal in raised-floor data centres.
Document contents
- 1 Introduction
- 2 Related work (2.1 Passive tile, 2.2 Adaptive vent tile (AVT), 2.3 Active tile)
- 3 Experiment setup (3.1 Measurement tools, 3.2 Measurement strategies)
- 4 Experimental results and analysis (4.1 Rack inlet temperature, 4.2 Tile flow velocity, 4.3 Pressure differential)
- 5 Data-driven models (5.1 Gaussian Process regression, 5.2 Artificial neural network approach, 5.3 Multivariate Linear Regression)
- 6 Conclusion
Related standards
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
Read the document
active-tile-raised-floor-2023.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Haoyu Gao; Qiuling Yue; Yuqing Kou; Jianxiong Wan; Leixiao Li; Lijun Fu
- Publisher
- Frontiers in Energy Research (Frontiers Media SA)
- Year
- 2023
- Volume
- 11
- Pages
- 1073879
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.frontiersin.org
Original licence note
PDF p.1: open-access article distributed under the terms of the Creative Commons Attribution License (CC BY).
Citation
Haoyu Gao; Qiuling Yue; Yuqing Kou; Jianxiong Wan; Leixiao Li; Lijun Fu (2023). Performance evaluation and modeling of active tile in raised-floor data centers: An empirical study on the single rack. Frontiers in Energy Research (Frontiers Media SA). 11, 1073879. https://doi.org/10.3389/fenrg.2023.1073879
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.