Numerical Investigation of Thermal Performance with Adaptive Terminal Devices for Cold Aisle Containment in Data Centers
Buildings (MDPI AG) · Hongyin Chen, Dezhi Li et al.
A motorised deflector unit fitted at the rack air inlet inside a cold-aisle-contained, raised-floor hall redistributes cold air vertically according to the measured power of each server slot, suppressing local hot spots without changing CRAH set points.
CC BY 4.0: share with attribution
On this page
Overview
The study starts from the problem that the adjustment scale of many airflow organisation methods is too large to support refined data-centre operation. The proposed device adapts cooling capacity to server power in the rack by adjusting deflector angles. A full-scale CFD model of a real Shanghai data hall was built: 21.5 × 20.3 × 4.9 m, seven rack rows, 10 CRAHs, 48U racks of 0.6 × 1.2 × 2.2 m, a 0.75 m plenum and 0.6 × 0.6 m perforated tiles with 35% opening ratio. It was validated with 21 K-type thermocouples (±0.1 K) at each of rack inlet and outlet in seven layers; measured CRAH outlet was 14 °C at 2.7 m/s.
The RNG k-epsilon model took 27.4% longer to compute than standard k-epsilon while differing in accuracy by no more than 6.7%, so standard k-epsilon was used, with perforated tiles as porous-jump boundaries. A grid study from 260,000 to 1,340,000 cells showed results stabilising at about 560,000 cells. Servers in the bottom 1st-2nd rack positions received very little air because the thick rack base frame created a vortex at the inlet.
The device adjusts per-server airflow between roughly 0.5 and 1.5 times the mean flow, and cut the maximum rack temperature by up to 4.2 K (for example rack F7 from 310.9 K to 306.7 K). To remove the same hot spot, lowering CRAH supply from 293 K to 291 K dropped COP from about 3.2 to 2.6; the device saved 20.1% of cooling energy versus that approach and 4.2% versus raising airflow 1.1 times. The spread of server exhaust temperatures narrowed.
Limits: only a CFD study, validated against a single rack inlet and outlet; the device itself was not tested in the field. Reliability, control latency and cost of moving deflectors were not assessed.
Key points
- Modelled hall is 21.5 × 20.3 × 4.9 m with seven rack rows, 10 CRAHs, 48U racks of 0.6 × 1.2 × 2.2 m, a 0.75 m plenum and 0.6 × 0.6 m perforated tiles with 35% opening ratio.
- RNG k-epsilon took 27.4% longer than standard k-epsilon while differing in accuracy by no more than 6.7%; standard k-epsilon was used and tiles were modelled as porous-jump boundaries.
- A grid study at 260,000 to 1,340,000 cells showed results stabilising at about 560,000 cells.
- Validation used 21 K-type thermocouples (±0.1 K) at each of rack inlet and outlet in seven layers; measured CRAH outlet was 14 °C at 2.7 m/s.
- Servers in the bottom 1st-2nd positions received very little air because the thick rack base frame created a vortex at the inlet.
- The device adjusts per-server airflow between roughly 0.5 and 1.5 times the mean flow and cut maximum rack temperature by up to 4.2 K (rack F7 310.9 K to 306.7 K).
- To remove the same hot spot, lowering CRAH supply from 293 K to 291 K dropped COP from about 3.2 to 2.6; the device saved 20.1% of cooling energy versus that approach and 4.2% versus raising airflow 1.1 times.
Using it in design
- For hot-spot removal, before choosing lower supply temperature or higher airflow outright, compare the COP drop (3.2 to 2.6) and the energy difference (20.1% and 4.2%) with a rack-specific air distribution option.
- Check in rack layout and blanking design that details such as a thick rack base frame creating an inlet vortex starve the lowest servers.
- Add to operating scenarios that when server power distribution changes (high-power server in lower positions), local air distribution may need adjustment.
Who should read it
Cooling engineers assessing rack-specific air distribution and energy efficiency in cold-aisle-contained raised-floor halls.
Document contents
- 1. Introduction
- 2. Methodology (2.1 Adaptive Terminal Device for Air Supply, 2.2 Adjustment Strategy of Terminal Device)
- 3. Numerical Simulation (3.1 Simulation Model: geometric model, governing equations and boundary conditions, grid independent study and validation experiments; 3.2 Numerical Investigation Setup)
- 4. Results and Discussion (4.3 Energy Efficiency Analysis)
- 5. Conclusions
Related standards
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
Read the document
cac-adaptive-terminal-devices-2023.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Hongyin Chen; Dezhi Li; Songcen Wang; Tianheng Chen; Ming Zhong; Yi Ding; Ye Li; Xianxu Huo
- Publisher
- Buildings (MDPI AG)
- Year
- 2023
- Volume
- 13
- Issue
- 2
- Pages
- 268
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1 states the article is distributed under the terms of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Citation
Hongyin Chen; Dezhi Li; Songcen Wang; Tianheng Chen; Ming Zhong; Yi Ding; Ye Li; Xianxu Huo (2023). Numerical Investigation of Thermal Performance with Adaptive Terminal Devices for Cold Aisle Containment in Data Centers. Buildings (MDPI AG). 13(2), 268. https://doi.org/10.3390/buildings13020268
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.