Distributed cooling with server heat pipes
Original title Design and Thermal Environment Analysis of a Decentralized Cooling System with Surface-Mount Heat Pipe Exchangers on Servers in Data Centers
Buildings (MDPI AG) · Xiaolei Yuan, Xuetao Zhou et al.
This 2022 Buildings study compares decentralised cooling that combines room air conditioning with server-level heat-pipe exchangers across 18 placement cases; placing them 0.01 m below servers cuts hotspot temperature by 6.8 °C.
On this page
Overview
The study proposes a decentralised cooling system that combines a conventional CRAC unit with server-level heat-pipe exchangers. Two strategies, with exchangers above and below the servers, are compared with the original CRAC system for thermal environment. Simulation results of the original data-centre model agree well with on-site measurements.
A total of 18 cases with exchangers at different locations and heights are analysed. The thermal environment is best when exchangers are placed 0.01 m below each server: local hotspot temperature falls by 6.8 °C and rack temperature distribution becomes most uniform. The best arrangement is specific to the modelled server geometry.
Key points
- Two strategies: heat-pipe exchangers above and below servers; compared with the original CRAC system.
- Simulation results agree well with on-site measurements.
- 18 exchanger placement cases are analysed.
- Best case: exchangers 0.01 m below the server.
- Local hotspot temperature falls by 6.8 °C and rack temperature distribution is most uniform.
Using it in design
- When evaluating server-level heat-pipe exchangers, simulate placement position and height separately for your server geometry.
- Examine the heat-pipe decentralised solution for hotspot reduction together with the option to lower CRAC capacity.
- Validate the CFD model against on-site measurements before running placement scenarios.
Who should read it
Mechanical designers and researchers exploring server-level cooling and hotspot reduction.
Publication details
- Authors
- Xiaolei Yuan; Xuetao Zhou; Yumin Liang; Yiqun Pan; Risto Kosonen; Zhongping Lin
- Publisher
- Buildings (MDPI AG)
- Year
- 2022
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Article-specific publisher copyright/rights statement explicitly grants CC BY; version 4.0 is corroborated by publisher-deposited Crossref license metadata. Third-party material may have separate rights. Round 3/4 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Xiaolei Yuan; Xuetao Zhou; Yumin Liang; Yiqun Pan; Risto Kosonen; Zhongping Lin (2022). Design and Thermal Environment Analysis of a Decentralized Cooling System with Surface-Mount Heat Pipe Exchangers on Servers in Data Centers. Buildings (MDPI AG). https://doi.org/10.3390/buildings12071015
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.