Research paperFree to read2022

Distributed cooling with server heat pipes

Original title Design and Thermal Environment Analysis of a Decentralized Cooling System with Surface-Mount Heat Pipe Exchangers on Servers in Data Centers

Buildings (MDPI AG) · Xiaolei Yuan, Xuetao Zhou et al.

This 2022 Buildings study compares decentralised cooling that combines room air conditioning with server-level heat-pipe exchangers across 18 placement cases; placing them 0.01 m below servers cuts hotspot temperature by 6.8 °C.

On this page

Overview

The study proposes a decentralised cooling system that combines a conventional CRAC unit with server-level heat-pipe exchangers. Two strategies, with exchangers above and below the servers, are compared with the original CRAC system for thermal environment. Simulation results of the original data-centre model agree well with on-site measurements.

A total of 18 cases with exchangers at different locations and heights are analysed. The thermal environment is best when exchangers are placed 0.01 m below each server: local hotspot temperature falls by 6.8 °C and rack temperature distribution becomes most uniform. The best arrangement is specific to the modelled server geometry.

Key points

  1. Two strategies: heat-pipe exchangers above and below servers; compared with the original CRAC system.
  2. Simulation results agree well with on-site measurements.
  3. 18 exchanger placement cases are analysed.
  4. Best case: exchangers 0.01 m below the server.
  5. Local hotspot temperature falls by 6.8 °C and rack temperature distribution is most uniform.

Using it in design

  • When evaluating server-level heat-pipe exchangers, simulate placement position and height separately for your server geometry.
  • Examine the heat-pipe decentralised solution for hotspot reduction together with the option to lower CRAC capacity.
  • Validate the CFD model against on-site measurements before running placement scenarios.

Who should read it

Mechanical designers and researchers exploring server-level cooling and hotspot reduction.

Publication details

Authors
Xiaolei Yuan; Xuetao Zhou; Yumin Liang; Yiqun Pan; Risto Kosonen; Zhongping Lin
Publisher
Buildings (MDPI AG)
Year
2022
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Article-specific publisher copyright/rights statement explicitly grants CC BY; version 4.0 is corroborated by publisher-deposited Crossref license metadata. Third-party material may have separate rights. Round 3/4 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Xiaolei Yuan; Xuetao Zhou; Yumin Liang; Yiqun Pan; Risto Kosonen; Zhongping Lin (2022). Design and Thermal Environment Analysis of a Decentralized Cooling System with Surface-Mount Heat Pipe Exchangers on Servers in Data Centers. Buildings (MDPI AG). https://doi.org/10.3390/buildings12071015

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.