Abu Dhabi Department of Energy

The Abu Dhabi Department of Energy policy (DoE/ED/G05/005), effective 1 September 2022, allows recycled, potable and sea water for district cooling towers and sets six objectives.

On this page

Overview

The policy complements the Abu Dhabi Department of Energy's district cooling (DC) regulatory framework. DC has an estimated 9% overall energy saving potential in the demand-side management strategy, but it is characterised by high net water consumption that offsets cooling tower evaporation, drift and blowdown. Availability of water of acceptable quality and quantity is a key feasibility criterion; without secure access DC would not be assessed as a feasible alternative to conventional cooling and the efficiency gain would be lost.

The policy allows recycled water (RW), potable water (PW) and seawater (SW) for DC use from environmental, demand-side management, techno-economic and quality perspectives, and promotes conserving potable water. DC benefits are listed as lower peak electricity demand, lower electricity consumption and lower greenhouse gas emissions from power generation. Whatever source is used, the plant produces wastewater discharge to the foul sewer, storm sewer or the sea.

Desalinated water offers stable quality but at a cost; RW or SW should be considered if available and technically and commercially feasible. The six objectives are: use the most feasible and cost-effective source; if that is PW, make it available to DC and plan for it in energy sector planning; allow demand to be met from RW, SW or blends; comply with DC regulations, water use, reuse and discharge rules and monitoring; provide water storage at the plant and a business continuity plan for extended interruptions; and reuse blowdown for non-drinking uses (irrigation, cleaning) where appropriate, supporting zero liquid discharge (ZLD).

Annexes list relevant entities (DMT, ADDC, AADC, ADNOC, EAD, TAQA, Tabreed and others), a policy overview and the roles of relevant agencies. The document is bilingual (English and Arabic) and refers to the Water Quality Regulations, Recycled Water and Biosolid Regulations, DC Technical Code and DC Metering Code.

Key points

  1. Effective 1 September 2022; document number DoE/ED/G05/005.
  2. DC has an estimated 9% overall energy saving potential in the demand-side management strategy.
  3. Water losses are evaporation, drift and blowdown; blowdown keeps TDS acceptable.
  4. The policy allows RW, PW and SW; desalinated water gives stable quality but costs more.
  5. Objective: the most feasible and cost-effective source, RW, SW or blends if required quality is met.
  6. Water storage at the plant is essential and a business continuity plan for extended interruptions is required.
  7. Blowdown should be reused for irrigation or cleaning where appropriate, supporting zero liquid discharge (ZLD).
  8. Whatever the source, plant wastewater goes to foul sewer, storm sewer or sea and must meet discharge regulations.

Using it in design

  • For a district cooling plant, compare RW, PW and SW make-up options on capital and operating cost, quality and discharge constraints, and select the most suitable source.
  • If blended sources are used, design treatment that delivers the water quality required by condensers and towers.
  • Size water storage per the water supply regulations and prepare a business continuity plan for extended outages.
  • Include blowdown reuse for irrigation or cleaning and the ZLD target in the plant water balance.
  • Identify the wastewater discharge point (foul sewer, storm sewer, sea) and show compliance with regulations and monitoring in the design.

Who should read it

Engineers, developers and regulators designing and operating district cooling plants in Abu Dhabi.

Document contents

  1. Introduction: Purpose, Scope, Responsibility, References, Distribution
  2. Definitions
  3. Policy Statement
  4. Annex A: List of Entities
  5. Annex B: Policy Overview
  6. Annex C: Roles of Relevant Agencies and Regulations

Publication details

Authors
Abu Dhabi Department of Energy
Publisher
Abu Dhabi Department of Energy
Year
2022
Document number
DoE/ED/G05/005, Version 0
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public official source inspected. No document-specific commercial redistribution permission established. Metadata and original brief summaries only; local evidence is not a redistribution package. The document expressly reserves reproduction rights despite its OPEN classification.

Citation

Abu Dhabi Department of Energy (2022). Water Management in District Cooling Plants Policy. Abu Dhabi Department of Energy. DoE/ED/G05/005, Version 0. https://www.doe.gov.ae/-/media/Project/DOE/Department-Of-Energy/Media-Center-Publications/Policy/Water-Management-in-District-Cooling-Plant-Policy-Final.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.