Technical guideFree to read2013

OnRak Rear-door Heat Exchanger Technical Brochure (Airedale, 2013)

Original title OnRak rear-door heat exchanger technical brochure

Airedale

Airedale's 2013 OnRak brochure: a chilled-water rear door with EC fans up to 35 kW; the n model gives 34.9 kW at EER 114.45 and the n+1 model 29.4 kW at EER 183.02, adding only 200 mm to the rack.

On this page

Overview

The document is a 2013 technical brochure for the OnRak rear door heat exchanger from the UK manufacturer Airedale. OnRak is a door that cools the hot air leaving the server at the source, designed to remove hot spots in medium and high density environments. It adds only 200 mm to the rack depth and can be applied directly to 42-48U racks or through a mating frame for any maker's rack.

The manufacturer reports an 88% reduction in annual power consumption against a conventional chilled-water CRAC thanks to electronically commutated (EC) axial fans: 1,410 kWh against 11,383 kWh a year in the example. The comparison rests on OnRak EER 114.5 and CRAC EER 17.0. Integrated with a free-cooling chiller, energy savings of up to 50% are stated.

The technical table gives two configurations: LOR6042U-C033-0 (n) with 34.9 kW cooling, 0.306 kW power, EER 114.45, four fans, 1.8 m3/s air and 75 kg operating weight; and LOR6042U-C028-0 (n+1) with 29.4 kW, 0.161 kW, EER 183.02, 1.4 m3/s. Nominal conditions are 14/20 °C water and 46 °C entering air; data are calculated to BS EN 14511-2011 and Eurovent 6/6.

For resilience the n+1 fan option (if one fan fails the other three speed up), hot-swappable fans, aisle pressure control, water detection and automatic isolation are offered. The brochure is a manufacturer document; current product status must be confirmed separately.

Key points

  1. OnRak adds only 200 mm to rack depth; width 600 mm, height 2030 mm, operating weight 75 kg.
  2. LOR6042U-C033-0 (n): 34.9 kW, 0.306 kW power input, EER 114.45, 1.8 m3/s air.
  3. LOR6042U-C028-0 (n+1): 29.4 kW, 0.161 kW, EER 183.02, 1.4 m3/s (air volume 75% in the n+1 option).
  4. Nominal condition 14/20 °C water and 46 °C air; data follow BS EN 14511-2011 and Eurovent 6/6.
  5. The maker reports EC-fan OnRak using 1,410 kWh a year against 11,383 kWh for a conventional chilled-water CRAC, 88% less.
  6. Up to 50% energy saving is stated with a free-cooling chiller.
  7. On 20 kW racks the OnRak's compact hot aisle is 43 °C and the cold aisle 27 °C.
  8. In the n+1 fan option, if one fan fails the other three can speed up to 100% to hold total airflow.

Using it in design

  • For hot spots with rack loads above 20 kW, evaluate the rear-door solution against the 35 kW per rack limit and the 14/20 °C water condition.
  • Raise chilled-water temperature to extend free-cooling hours; the brochure highlights supply above 17 °C and free-cooling chiller integration.
  • Include the 200 mm added to rack depth in aisle width and door-swing allowances.
  • Use the capacity difference between n and n+1 fan options (34.9 and 29.4 kW); where racks need redundancy, base design on the n+1 value.
  • In EER comparisons, check that fan and control power are included and that manufacturer claims depend on stated conditions.

Who should read it

Mechanical engineers and data-centre designers evaluating rear-door cooling for high-density racks.

Document contents

  1. Cooling Hot Spots
  2. Energy Saving with EC Fans
  3. Free-cooling Integration
  4. Resilience and N+1 Fans
  5. Controls and Smart Networking
  6. Specifications Overview
  7. Nomenclature and Technical Specifications
  8. Case Studies

Publication details

Authors
Airedale
Publisher
Airedale
Year
2013
Document number
ENG-IT-ONRAK-07-13
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Airedale (2013). OnRak rear-door heat exchanger technical brochure. Airedale. ENG-IT-ONRAK-07-13. https://www.airedale.com/wp-content/uploads/2020/01/OnRak-V8-110713.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.