StandardFree to read2020

Edge Computing: Considerations for Reliable Operation (ASHRAE TC 9.9 Technical Bulletin)

ASHRAE · ASHRAE TC 9.9

A short September 2020 bulletin from ASHRAE TC 9.9 warning that edge sites in outdoor or semi-controlled enclosures can expose IT equipment to temperature, humidity, dust and pollution excursions during servicing, putting reliability and warranty at risk.

On this page

Overview

This technical bulletin explains that edge computing deployments carry a different environmental risk from conventional data centres. IT equipment in outdoor or semi-controlled enclosures can be exposed to cold, humid, dusty or polluted air when a door is opened for servicing. The bulletin discusses how this may affect equipment reliability and the manufacturer's warranty, and it proposes practical countermeasures.

The text runs through warranties, enclosure design, servicing practices, monitoring and site selection. Figures 3a to 3d show that opening an enclosure door can let in air that bypasses filtration. The moment of servicing should therefore be treated as a distinct and critical environmental condition, separate from steady-state operation.

The recommendations are concrete. The IT supplier's warranty environmental limits should be checked and the enclosure designed to the narrowest of them. For temperature change during servicing, the ASHRAE guideline is restated: 20 C in an hour and no more than 5 C in any 15 minutes. Technicians are advised to monitor IT inlet temperature and humidity in real time throughout servicing.

Being a short bulletin, it offers no detailed calculation method or numeric design tables, and it should be read alongside ASHRAE Thermal Guidelines, 5th edition. The overall message is that edge site design must account for servicing conditions as well as normal operation.

Key points

  1. Opening an edge enclosure door can admit cold, humid, dusty or polluted air that bypasses filtration.
  2. Check the IT supplier's warranty environmental limits and design the enclosure to the narrowest specification.
  3. Temperature change guideline: 20 C in an hour and no more than 5 C in any 15 minutes.
  4. Technicians should monitor IT inlet temperature and humidity in real time during servicing.
  5. The bulletin covers warranties, enclosure design, servicing practices, monitoring and site selection.
  6. Read it together with ASHRAE Thermal Guidelines, 5th edition.

Using it in design

  • Assess the vestibule and servicing conditions of edge enclosures.
  • Include real-time IT inlet-temperature and relative-humidity sensing in edge enclosure design.
  • Add a servicing-weather warning to the operations checklist, with a rule to postpone servicing in unsuitable weather.
  • Add a check comparing the enclosure's environmental limits with the warranty limits of the selected IT equipment.

Who should read it

Engineers who design, build and operate edge and distributed sites, and field service teams.

Related standards

  • ASHRAE Thermal Guidelines 5th ed.

Publication details

Authors
ASHRAE TC 9.9
Publisher
ASHRAE
Year
2020
Document number
TC 9.9 Technical Bulletin (Sep 2020)
Document language
English
Source type
Standard
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Free download from ASHRAE but (c) ASHRAE, all rights reserved; ASHRAE also prohibits entering its publication content into AI tools. Metadata/citation only; facts limited to short paraphrase.

Citation

ASHRAE TC 9.9 (2020). Edge Computing: Considerations for Reliable Operation (ASHRAE TC 9.9 Technical Bulletin). ASHRAE. TC 9.9 Technical Bulletin (Sep 2020). https://www.ashrae.org/file%20library/technical%20resources/bookstore/tb_edgecomputing_sep2020.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.