ATTOM ByteCool: Direct-to-Chip Liquid Cooling System (technical brochure v1.4)
Original title ByteCool Direct-to-Chip Liquid Cooling System v1.4
Attom
ATTOM's ByteCool brochure gives technical data for a direct-to-chip product family, from a 100 kW 4U rack CDU and a 1,520 kW row CDU at 4 °C approach to a 150 kW sidecar CDU and a free-cooling chiller.
On this page
Overview
The brochure presents ByteCool as row- or rack-mounted liquid-to-liquid CDUs, row-level liquid-to-air CDUs, quick-connect manifolds, optional outdoor dry coolers, an optional natural-cooling chiller and an optional monitoring management system. The approach is maximum efficiency through free cooling and intelligent control integration from component to system.
The BT-100-RL rack CDU is liquid-to-liquid, 440x177x910 mm (4U), with 100 kW capacity, 0.5 kW power consumption and ASHRAE category W3. At 13 °C approach it runs primary 32/42 °C, secondary supply/return 45/55 °C, with 50 micron secondary and 200 micron primary filtration and PG25 and EG20 fluids, offering 2N pumps and dual power input.
The BT-1500-CL row CDU gives 1,520 kW at 4 °C approach (W3, primary 32/42 °C, secondary 36/52 °C) or 2,020 kW (W2, primary 27/37 °C, secondary 31/52 °C) at 1,500 LPM secondary flow, with 17.8 kW consumption, N+N pumps and DN100 connections. The BT-080-CA sidecar CDU gives 80 kW liquid-to-air (W3 liquid, A2 air, 16,000 m³/h, 27 °C inlet air) and needs no facility water; the DX-type BT-150-CA gives 150 kW (R513A, secondary 40/30 °C).
It also presents the AMF-21 manifold (316 stainless steel, 21 outlets and 21 inlets), the ChillFlow free-cooling chiller (100, 250, 500 and 1,000 kW; free-cooling mode at 5 °C ambient) and the KoolFlow cooling tower. Data are manufacturer statements and may change without notice.
Key points
- BT-100-RL rack CDU: 100 kW, 4U (440x177x910 mm), 0.5 kW consumption, 13 °C approach, ASHRAE W3.
- BT-100-RL temperatures: primary 32/42 °C, secondary 45/55 °C; filtration 50 micron (secondary) and 200 micron (primary); PG25 and EG20.
- BT-1500-CL row CDU: 1,500 LPM; 1,520 kW (W3) or 2,020 kW (W2) at 4 °C approach; power 17.8 kW.
- BT-1500-CL W2 variant: primary 27/37 °C, secondary supply 31 °C, return 52 °C.
- Sidecar BT-080-CA: 80 kW liquid-to-air, 16,000 m³/h, no facility water needed; 600x2200x1200 mm.
- Sidecar DX BT-150-CA: 150 kW, R513A, secondary 40/30 °C, 13.6 m³/h, 626 kg.
- AMF-21 manifold: 316 stainless steel, 21 outlets and 21 inlets, self-sealed quick connect.
- ChillFlow free-cooling chiller: 100-1,000 kW; free-cooling consumption is about one seventh of DX mode (e.g. C-1000GV 41.6 kW vs 316 kW).
Using it in design
- Read ASHRAE W category and approach temperature together when selecting a CDU: the same BT-1500-CL frame gives 1,520 kW at W3 and 2,020 kW at W2.
- In air-cooled halls with no facility water, consider the sidecar (liquid-to-air) option that rejects heat to the existing CRAC/CRAH system as a retrofit.
- If high secondary temperatures (45-55 °C) are used, design them together with free-cooling heat rejection.
- Compare filter fineness (secondary 50 micron) with the cold plate requirement and put the 200 micron primary strainer on the maintenance plan.
- Match the 2N pump and dual power input requirement to the Tier target.
- Match manifold port count (21 outlets/21 inlets) to servers per rack.
Who should read it
Mechanical designers and system integrators selecting CDUs, manifolds and heat rejection equipment for direct-to-chip halls.
Document contents
- ByteCool direct-to-chip liquid cooling system
- Efficiency approach
- Liquid cool CDU
- Rack CDU
- Row CDU
- Sidecar CDU
- Sidecar CDU DX type
- Manifold kits
- ChillFlow free cooling chiller
- KoolFlow cooling tower
Publication details
- Authors
- Attom
- Publisher
- Attom
- Year
- 2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Attom (2026). ByteCool Direct-to-Chip Liquid Cooling System v1.4. Attom. https://attom.tech/wp-content/uploads/2026/05/Attom-ByteCool-liquid-cooling-brochure-en-v1.4.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.