ATTOM ByteCool: Direct-to-Chip Liquid Cooling System (technical brochure v1.4)

Original title ByteCool Direct-to-Chip Liquid Cooling System v1.4

Attom

ATTOM's ByteCool brochure gives technical data for a direct-to-chip product family, from a 100 kW 4U rack CDU and a 1,520 kW row CDU at 4 °C approach to a 150 kW sidecar CDU and a free-cooling chiller.

On this page

Overview

The brochure presents ByteCool as row- or rack-mounted liquid-to-liquid CDUs, row-level liquid-to-air CDUs, quick-connect manifolds, optional outdoor dry coolers, an optional natural-cooling chiller and an optional monitoring management system. The approach is maximum efficiency through free cooling and intelligent control integration from component to system.

The BT-100-RL rack CDU is liquid-to-liquid, 440x177x910 mm (4U), with 100 kW capacity, 0.5 kW power consumption and ASHRAE category W3. At 13 °C approach it runs primary 32/42 °C, secondary supply/return 45/55 °C, with 50 micron secondary and 200 micron primary filtration and PG25 and EG20 fluids, offering 2N pumps and dual power input.

The BT-1500-CL row CDU gives 1,520 kW at 4 °C approach (W3, primary 32/42 °C, secondary 36/52 °C) or 2,020 kW (W2, primary 27/37 °C, secondary 31/52 °C) at 1,500 LPM secondary flow, with 17.8 kW consumption, N+N pumps and DN100 connections. The BT-080-CA sidecar CDU gives 80 kW liquid-to-air (W3 liquid, A2 air, 16,000 m³/h, 27 °C inlet air) and needs no facility water; the DX-type BT-150-CA gives 150 kW (R513A, secondary 40/30 °C).

It also presents the AMF-21 manifold (316 stainless steel, 21 outlets and 21 inlets), the ChillFlow free-cooling chiller (100, 250, 500 and 1,000 kW; free-cooling mode at 5 °C ambient) and the KoolFlow cooling tower. Data are manufacturer statements and may change without notice.

Key points

  1. BT-100-RL rack CDU: 100 kW, 4U (440x177x910 mm), 0.5 kW consumption, 13 °C approach, ASHRAE W3.
  2. BT-100-RL temperatures: primary 32/42 °C, secondary 45/55 °C; filtration 50 micron (secondary) and 200 micron (primary); PG25 and EG20.
  3. BT-1500-CL row CDU: 1,500 LPM; 1,520 kW (W3) or 2,020 kW (W2) at 4 °C approach; power 17.8 kW.
  4. BT-1500-CL W2 variant: primary 27/37 °C, secondary supply 31 °C, return 52 °C.
  5. Sidecar BT-080-CA: 80 kW liquid-to-air, 16,000 m³/h, no facility water needed; 600x2200x1200 mm.
  6. Sidecar DX BT-150-CA: 150 kW, R513A, secondary 40/30 °C, 13.6 m³/h, 626 kg.
  7. AMF-21 manifold: 316 stainless steel, 21 outlets and 21 inlets, self-sealed quick connect.
  8. ChillFlow free-cooling chiller: 100-1,000 kW; free-cooling consumption is about one seventh of DX mode (e.g. C-1000GV 41.6 kW vs 316 kW).

Using it in design

  • Read ASHRAE W category and approach temperature together when selecting a CDU: the same BT-1500-CL frame gives 1,520 kW at W3 and 2,020 kW at W2.
  • In air-cooled halls with no facility water, consider the sidecar (liquid-to-air) option that rejects heat to the existing CRAC/CRAH system as a retrofit.
  • If high secondary temperatures (45-55 °C) are used, design them together with free-cooling heat rejection.
  • Compare filter fineness (secondary 50 micron) with the cold plate requirement and put the 200 micron primary strainer on the maintenance plan.
  • Match the 2N pump and dual power input requirement to the Tier target.
  • Match manifold port count (21 outlets/21 inlets) to servers per rack.

Who should read it

Mechanical designers and system integrators selecting CDUs, manifolds and heat rejection equipment for direct-to-chip halls.

Document contents

  1. ByteCool direct-to-chip liquid cooling system
  2. Efficiency approach
  3. Liquid cool CDU
  4. Rack CDU
  5. Row CDU
  6. Sidecar CDU
  7. Sidecar CDU DX type
  8. Manifold kits
  9. ChillFlow free cooling chiller
  10. KoolFlow cooling tower

Publication details

Authors
Attom
Publisher
Attom
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Attom (2026). ByteCool Direct-to-Chip Liquid Cooling System v1.4. Attom. https://attom.tech/wp-content/uploads/2026/05/Attom-ByteCool-liquid-cooling-brochure-en-v1.4.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.