Attom SmoothAir Rear Door Heat Exchanger brochure v1.2 (DX and CW)

Original title SmoothAir RDHx Rear Door Heat Exchanger

ATTOM

Attom's SmoothAir RDHx brochure covers rear door heat exchangers of 25 kW in DX type and 31.2-65.8 kW in chilled-water (CW) type, with R134a, EC fans, an inverter compressor and operation up to 55 °C ambient.

On this page

Overview

The brochure, dated May 2026, describes Attom's SmoothAir rear door heat exchanger (RDHx) for data centres where HPC, machine learning and AI loads raise heat density. Rear-door mounting brings heat removal closer to the heat source and gets maximum efficiency from the high return air temperature leaving the rack. The brochure states it can comfortably handle the typical 20-65 kW high power density of HPC racks.

The DX type is notable for up to 25 kW capacity, no need for complex water loops and manifolds, and no water leak concern thanks to ECO-type R134a. R134a has zero ODP and a GWP of 1430 and supports continuous operation in -40 to 55 °C ambient. Components: EC fan, smart controller, electronic expansion valve (EEV) and an inverter compressor that saves energy at part load.

The DX model S-025DA: 25.1 kW total capacity, SHR 100 %, 5,000 m³/h airflow, 2,000 x 600 x 380 mm (H x W x D), 115 kg, 208-240 V single or two phase (FLA 9.0 A). The outdoor unit KSF38AC comes with 380-415 V three phase (FLA 21.2 A), 200-230 V three phase (36.4 A) and 460 V 60 Hz three phase (17.5 A) options. Capacity is at 40 °C / 20 % RH return air and 45 °C condensing temperature.

The CW models are S-030DC, S-045DC and S-065DC: water temperature in/out 15/20 °C, total capacity (40 °C / 20 % RH return air) 31.2, 46 and 65.8 kW, airflow 6,000, 9,000 and 11,400 m³/h, weight 120, 150 and 180 kg, depth 310 mm. The CW type has a ball water valve installed with a single bolt and an actuator with full-stroke automatic overload protection. The brochure also summarises Attom's air and liquid cooling platforms.

Key points

  1. DX type up to 25 kW; CW type up to 65 kW; optimised for ambient up to 55 °C.
  2. S-025DA (DX): 25.1 kW, SHR 100 %, 5,000 m³/h, 2,000 x 600 x 380 mm, 115 kg.
  3. S-030DC / 045DC / 065DC (CW, water 15/20 °C): 31.2 / 46 / 65.8 kW; 6,000 / 9,000 / 11,400 m³/h; 120 / 150 / 180 kg.
  4. Capacity condition: return air 40 °C / 20 % RH; for DX, condensing temperature 45 °C.
  5. R134a: zero ODP, GWP 1430, continuous operation in -40 to 55 °C ambient.
  6. The DX type needs no water loop or manifold; no leak risk (ECO-type R134a).
  7. EC fan, smart controller, EEV and inverter compressor; the CW type has a ball valve and overload-protected actuator.
  8. Typical HPC rack power density is stated as 20-65 kW.

Using it in design

  • Classify rack heat load in the 20-65 kW range; consider DX up to 25 kW and CW up to 65 kW as candidates.
  • For CW models, set the 15/20 °C water regime to suit the cooling plant design (free-cooling potential).
  • If DX is chosen, plan the outdoor unit position and refrigerant line length; order the three-phase supply option (380-415 V, 200-230 V, 460 V) to match the site grid.
  • Remember that capacities are given for 40 °C / 20 % RH return air; obtain confirmation from the manufacturer for other return temperatures.
  • Check that the flexible piping design does not obstruct door opening, and the effect of the 310-380 mm depth on aisle width.

Who should read it

Mechanical engineers selecting rear-door cooling for AI, ML and HPC cabinets.

Document contents

  1. Why work with Attom
  2. Certifications
  3. SmoothAir RDHx overview and density ranges
  4. Features and benefits
  5. DX type components and technical data
  6. CW type components and technical data
  7. Precision cooling product platform

Publication details

Authors
ATTOM
Publisher
ATTOM
Year
Year not stated
Document number
SmoothAir-RDx-BR-v1.2
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ATTOM SmoothAir RDHx Rear Door Heat Exchanger. ATTOM. SmoothAir-RDx-BR-v1.2. https://attom.tech/wp-content/uploads/2026/05/Brochure_SmoothAir-Rear-Door-Heat-Exchanger-v1.2.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.