autotherm LEAN CDU: Coolant Distribution Unit for Direct Liquid Cooling (technical document)
Original title Coolant Distribution Unit LEAN: Technische Information
autotherm Nenninger
autotherm's German LEAN CDU document describes a CDU in five models (A-CDU27L to 324L, 355 to 6,420 kW) that separates primary and secondary loops, with temperature control to ±0.5 K and back-pressure control to ±0.1 bar.
On this page
Overview
The document (in German) describes the CDU as the central interface between the facility cooling loop and the IT secondary loop for direct liquid cooling (DLC). The two loops are hydraulically and control-wise decoupled, so pressure fluctuations, different media or control actions on the facility side do not reach the IT loop. The design philosophy rests on four principles: stability, precision, predictability and transparency.
Performance data: secondary supply temperature setting range +20 to +80 °C, supply pressure limit 1-3 bar, steady-state temperature control of ±0.5 K and back-pressure control of ±0.1 bar. The secondary medium is inhibited water-glycol (25% glycol) or water; the primary side uses a 20-40% glycol mix or water. Control is a Siemens S7 with colour touchscreen; BACnet, SNMP, MQTT, Modbus TCP/IP, OPC UA and Profinet interfaces are selectable.
Five standard models (A-CDU27L, 54L, 108L, 216L, 324L) run from 27 to 324 m³/h with a frequency-controlled pump against 2.5 bar. Cooling capacity at a 3 K difference between primary inlet and secondary supply ranges from 355 kW (27 m³/h, ΔT 12 K) to 6,420 kW (324 m³/h, ΔT 18 K). Connections are DN65 to DN250, rated power 4.6 to 44.4 kW, protection class IP54, ambient +15 to +42 °C and 15-65% relative humidity.
Options: strainers (four units, two each on primary and secondary, with differential pressure monitoring, in two 50% lines), dew point control, a spring-return primary valve moving to the open safe position on control or power loss, secondary pump switching to 50 Hz mains on control loss, dual supply with automatic changeover (not uninterrupted) and event-based operating data recording.
Key points
- Primary and secondary loops are hydraulically and control-wise decoupled.
- Secondary supply temperature setting range is +20 to +80 °C; supply pressure limit 1-3 bar.
- Steady-state control quality: temperature ±0.5 K, back pressure ±0.1 bar.
- Five models A-CDU27L to 324L: 27-324 m³/h, capacity 355 to 6,420 kW (ΔT 12 K or 18 K).
- Capacity data assume a deliberate 3 K difference between primary inlet and secondary supply, enabling higher primary temperatures.
- Primary water temperature +15 to +60 °C, pressure up to 6 bar, plant pressure loss below 1.5 bar.
- Supply 3/PE 380-420 V 50 Hz or 440-480 V 60 Hz; IP54; rated power 4.6-44.4 kW.
- Heat released to the room is about 5% of rated electrical power; PT100 class AA temperature sensors.
Using it in design
- Select CDU capacity by design ΔT: the same model gives 355 kW at 12 K and 532 kW at 18 K.
- Design the primary inlet 3 K below secondary supply to make higher primary temperatures and dry-cooler-led rejection feasible.
- Add the spring-return primary valve and 50 Hz pump emergency operation to the specification so cooling continues on control loss.
- Plan dew point control with additional temperature and humidity sensors to avoid condensation at low water temperatures.
- In the dual supply option, account in the power design for the changeover not being uninterrupted.
- Decide on the strainer option for clogging monitoring and for the remaining line carrying load during maintenance.
Who should read it
Mechanical and automation engineers selecting CDUs and defining control for DLC halls.
Document contents
- Model LEAN: overview
- Design philosophy
- Performance data and technical equipment
- Control and interfaces
- Measurement technology and installation conditions
- Material selection
- Options (strainers, dew point, spring-return valve, emergency pump, dual supply, data recording)
- Standard device variants and temperature levels
Publication details
- Authors
- autotherm Nenninger
- Publisher
- autotherm Nenninger
- Year
- 2026
- Document language
- German
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
autotherm Nenninger (2026). Coolant Distribution Unit LEAN: Technische Information. autotherm Nenninger. https://www.autotherm.net/de/wp-content/uploads/sites/2/2026/08/autotherm-coolant-distribution-unit-lean-deutsch.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.