BEEHE RDHX-A2D-LT1C Rear Door Heat Exchanger specifications (30-75 kW)

Original title Rear Door Heat Exchanger (RDHX): A2D-LT1C technical specifications

BEEHE

The BEEHE RDHX-A2D-LT1C series of active rear door heat exchangers has four models rated 30, 50, 55 and 75 kW, with PG25 coolant, 45/25 °C rated temperature and N+1 fan redundancy.

On this page

Overview

The page presents BEEHE's active rear door heat exchangers, designed to dissipate heat from air-cooled components within server cabinets. The unit mounts to the cabinet rear door via adapters and a frame, with a maximum heat exchange capacity of up to 75 kW. Features include thickened pure-copper coils, special flow-channel and fin design for low flow resistance, an N+1 redundant multi-axial fan arrangement and online maintenance.

The integrated control system monitors temperature, humidity, pressure and leaks, with optional redundant power supplies. It adjusts fan speed and inlet flow automatically (the flow control valve is connected externally). The door has bottom casters and an opening angle above 90 degrees. Top and bottom water inlet and outlet are supported, and adapters fit various cabinet types. The product is designed to comply with UL and CE standards.

In the technical table the models are RDHX30, 50, 55 and 75-A2D-LT1C. Cabinet size is 600 mm/42U, 600 mm/47U, 800 mm/47U and 800 mm/48U; rated capacity 30, 50, 55 and 75 kW; coolant PG25; rated temperature (inlet/outlet) 45/25 °C; secondary-side medium temperature 14/23.2, 14/24, 14/24.5 and 14/22 °C.

Rated flow is 55, 78.3, 82.2 and 143.3 LPM; rated airflow 5,000, 7,800, 8,500 and 12,100 CFM; power consumption up to 1.6, 1.6, 3.4 and 4 kW; fan size 120 mm (first two models) and 200 mm (the others); fan count 18, 18, 10 and 10. Connection is a 1 in clamp and the power interface is C20.

Key points

  1. Four models: RDHX30 / 50 / 55 / 75-A2D-LT1C; rated capacity 30 / 50 / 55 / 75 kW.
  2. Cabinet: 600 mm/42U, 600 mm/47U, 800 mm/47U, 800 mm/48U.
  3. Coolant PG25; rated temperature 45/25 °C; secondary side 14/23.2 to 14/24.5 °C.
  4. Rated flow 55 / 78.3 / 82.2 / 143.3 LPM.
  5. Rated airflow 5,000 / 7,800 / 8,500 / 12,100 CFM.
  6. Power consumption 1.6 / 1.6 / 3.4 / 4 kW (maximum); fan count 18 / 18 / 10 / 10; N+1 fan and power redundancy.
  7. Control: temperature, humidity, pressure and leak monitoring; automatic fan speed and flow adjustment.
  8. Top or bottom connection; caster-mounted door; opening angle above 90 degrees; designed to UL and CE standards.

Using it in design

  • Select the model by cabinet height and width (42U-48U, 600-800 mm); the 75 kW model fits only the 800 mm/48U cabinet.
  • Use the rated flow (55 to 143.3 LPM) for CDU and secondary pipe sizing; include the external flow control valve in the order scope.
  • Show fan and supply N+1 redundancy on the rack critical-load diagram; add power consumption (1.6-4 kW) to the rack load budget.
  • Compare the water regime (45/25 °C rated, 14/22-24.5 °C secondary) with the cooling plant regime.
  • Check aisle service clearance for the door opening angle and casters.

Who should read it

Mechanical engineers selecting rear door heat exchangers for high-density cabinet cooling.

Document contents

  1. Product introduction
  2. Product features
  3. Technical specification

Publication details

Authors
BEEHE
Publisher
BEEHE
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

BEEHE Rear Door Heat Exchanger (RDHX): A2D-LT1C technical specifications. BEEHE. https://beehe.com/productinfo/3588888.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.