Technical guideFree to read2025

Canatec Smart Cooling (Chilled Water) 2025-A

Original title Canatec Smart Cooling CW 2025-A

Canatec

The Canatec Smart Cooling chilled-water CRAH series gives 19.0 to 193.0 kW across 7 models; the brochure lists two rating conditions (36 °C and 24 °C return air).

On this page

Overview

Canatec Smart Cooling (Chilled Water) is a raised-floor precision cooling unit combining chilled water and EC fans, recommended for data centres, server rooms, production facilities and telecom structures. The brochure states a range of 40 to 180 kW and highlights a symmetrical V coil, a 2-way modulating valve, upthrow or downthrow airflow and EC Fan Co-Work, which links unit main boards for backup.

The technical table gives seven models (0401 to 1901) at two conditions. At 36 °C return air and 18/26 °C water, total and sensible capacity are equal (SHR 1.00) and range from 19.0 to 141.0 kW. At 24 °C return air and 7/12 °C water, total capacity is 29.6 to 193.0 kW and sensible 29.6 to 145.9 kW, with SHR from 1.00 to 0.76. Airflow is 9,000 to 33,000 m³/h, power input 1.5 to 6.9 kW and external static pressure 75 Pa.

Physical data: unit width 930 to 2,730 mm, depth 1,000 mm, height 1,975-1,980 mm, weight 350 to 800 kg, water connections DN40 or DN50, supply 380-415 V 3P1N 50/60 Hz. Standard accessories are a G4 filter, dirty-filter pressure switch and water leak sensor; active harmonic filter, ATS, battery backup, energy valve and smoke detector are optional. Relative humidity is not stated and sensible capacity is not labelled as net.

Key points

  1. Seven models (0401-1901), total capacity 19.0-193.0 kW depending on condition.
  2. Condition 1: return air 36 °C, water 18/26 °C; total and sensible capacity equal, SHR 1.00.
  3. Condition 2: return air 24 °C, water 7/12 °C; total 29.6-193.0 kW, sensible 29.6-145.9 kW.
  4. SHR in condition 2 ranges from 1.00 to 0.76, lowest on the largest model (1901).
  5. Airflow 9,000-33,000 m³/h; power input 1.5-6.9 kW; external static pressure 75 Pa.
  6. Water flow is 0.61-4.43 L/s in condition 1 and 1.49-9.57 L/s in condition 2.
  7. Dimensions: width 930-2,730 mm, depth 1,000 mm, height 1,975-1,980 mm; weight 350-800 kg.
  8. EC plug fans, 1 to 3 per unit; water connections DN40 or DN50.

Using it in design

  • Read capacity from the condition closest to the project's return air and water temperatures, and confirm interpolation between the two with the manufacturer.
  • Because sensible capacity is not labelled net and humidity is not given, ask the manufacturer for net sensible values where dehumidification matters.
  • Define the EC Fan Co-Work link and unit count (N+1) for redundancy in the design.
  • Check the under-floor plenum and the 75 Pa external static pressure against the air distribution calculation.
  • Add options such as active harmonic filter, ATS and battery backup to the electrical diagram.

Who should read it

Mechanical designers and specification engineers selecting precision cooling units for data halls and server rooms.

Document contents

  1. Features and benefits
  2. Raised floor airflow
  3. Specifications

Publication details

Authors
Canatec
Publisher
Canatec
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Canatec (2025). Canatec Smart Cooling CW 2025-A. Canatec. https://www.canatec.com.sg/wp-content/uploads/2025/11/CANATEC-SMART-COOLING-Chilled-Water-2025-A_compressed.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.